// CODE SNIPPET
1910.106(b)(2) Installation of Outside Aboveground Tanks
JUMP TO FULL CODE CHAPTER
Atmospheric storage tanks shall be adequately vented to prevent the development of vacuum or pressure sufficient to distort the roof of a cone roof tank or exceeding the design pressure in the case of other atmospheric tanks, as a result of filling or emptying, and atmospheric temperature changes.
Normal vents shall be sized either in accordance with:
The American Petroleum Institute Standard 2000 (1968), Venting Atmospheric and Low-Pressure Storage Tanks, which is incorporated by reference as specified in Sec. 1910.6; or
other accepted standard; or
shall be at least as large as the filling or withdrawal connection, whichever is larger but in no case less than 1 1/4 inch nominal inside diameter.
Low-pressure tanks and pressure vessels shall be adequately vented to prevent development of pressure or vacuum, as a result of filling or emptying and atmospheric temperature changes, from exceeding the design pressure of the tank or vessel. Protection shall also be provided to prevent overpressure from any pump discharging into the tank or vessel when the pump discharge pressure can exceed the design pressure of the tank or vessel.
If any tank or pressure vessel has more than one fill or withdrawal connection and simultaneous filling or withdrawal can be made, the vent size shall be based on the maximum anticipated simultaneous flow.
Unless the vent is designed to limit the internal pressure 2.5 p.s.i. or less, the outlet of vents and vent drains shall be arranged to discharge in such a manner as to prevent localized overheating of any part of the tank in the event vapors from such vents are ignited.
Tanks and pressure vessels storing Category 1 flammable liquids shall be equipped with venting devices which shall be normally closed except when venting to pressure or vacuum conditions. Tanks and pressure vessels storing Category 2 flammable liquids and Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C) shall be equipped with venting devices which shall be normally closed except when venting under pressure or vacuum conditions, or with approved flame arresters.
Tanks of 3,000 bbls (barrels). capacity or less containing crude petroleum in crude-producing areas and outside aboveground atmospheric tanks under 1,000 gallons capacity containing other than Category 1 flammable liquids may have open vents. (See paragraph (b)(2)(vi)(b) of this section.)
Flame arresters or venting devices required in paragraph (b)(2)(iv)(f) of this section may be omitted for Category 2 flammable liquids and Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C) where conditions are such that their use may, in case of obstruction, result in tank damage.
"Emergency relief venting for fire exposure for aboveground tanks."
Every aboveground storage tank shall have some form of construction or device that will relieve excessive internal pressure caused by exposure fires.
In a vertical tank the construction referred to in subdivision (a) of this subdivision may take the form of a floating roof, lifter roof, a weak roof-to-shell seam, or other approved pressure relieving construction. The weak roof-to-shell seam shall be constructed to fail preferential to any other seam.
Where entire dependence for emergency relief is placed upon pressure relieving devices, the total venting capacity of both normal and emergency vents shall be enough to prevent rupture of the shell or bottom of the tank if vertical, or of the shell or heads if horizontal. If unstable liquids are stored, the effects of heat or gas resulting from polymerization, decomposition, condensation, or self-reactivity shall be taken into account. The total capacity of both normal and emergency venting devices shall be not less than that derived from Table H-10 except as provided in subdivision (e) or (f) of this subdivision. Such device may be a self-closing manhole cover, or one using long bolts that permit the cover to lift under internal pressure, or an additional or larger relief valve or valves. The wetted area of the tank shall be calculated on the basis of 55 percent of the total exposed area of a sphere or spheroid, 75 percent of the total exposed area of a horizontal tank and the first 30 feet above grade of the exposed shell area of a vertical tank.
Square feet |
CFH | Square feet |
CFH | Square feet |
CFH |
20 | 21,100 | 200 | 211,000 | 1,000 | 524,000 |
30 | 31,600 | 250 | 239,000 | 1,200 | 557,000 |
40 | 42,100 | 300 | 265,000 | 1,400 | 587,000 |
50 | 52,700 | 350 | 288,000 | 1,600 | 614,000 |
60 | 63,200 | 400 | 312,000 | 1,800 | 639,000 |
70 | 73,700 | 500 | 354,000 | 2,000 | 662,000 |
80 | 84,200 | 600 | 392,000 | 2,400 | 704,000 |
90 | 94,800 | 700 | 428,000 | 2,800 | 742,000 |
100 | 105,000 | 800 | 462,000 | and | |
120 | 126,000 | 900 | 493,000 | 5over | |
140 | 147,000 | 1,000 | 524,000 | ||
160 | 168,000 | ||||
180 | 190,000 | ||||
200 | 211,000 |
For tanks and storage vessels designed for pressure over 1 p.s.i.g., the total rate of venting shall be determined in accordance with Table H-10, except that when the exposed wetted area of the surface is greater than 2,800 square feet, the total rate of venting shall be calculated by the following formula:
CFH = 1,107A0.82
NOTE: The foregoing formula is based on Q = 21,000A0.82.
CFH = 1,107A0.82
Where: | ||
CFH | = | Venting requirement, in cubic feet of free air per hour. |
A | = | Exposed wetted surface, in square feet. |
The total emergency relief venting capacity for any specific stable liquid may be determined by the following formula:
V | = | 1337 divided by L square root of M |
V | = | Cubic feet of free air per hour from Table H-10. |
L | = | Latent heat of vaporization of specific liquid in B.t.u. per pound. |
M | = | Molecular weight of specific liquids. |
The required airflow rate of subdivision (c) or (e) of this subdivision may be multiplied by the appropriate factor listed in the following schedule when protection is provided as indicated. Only one factor may be used for any one tank.
0.5 for drainage in accordance with subdivision (vii)(b) of this subparagraph
for tanks over 200 square feet of wetted area.
0.3 for approved water spray.
0.3 for approved insulation.
0.15 for approved water spray with approved insulation.
0.5 for drainage in accordance with subdivision (vii)(b) of this subparagraph
for tanks over 200 square feet of wetted area.
0.3 for approved water spray.
0.3 for approved insulation.
0.15 for approved water spray with approved insulation.
The outlet of all vents and vent drains on tanks equipped with emergency venting to permit pressures exceeding 2.5 p.s.i.g. shall be arranged to discharge in such a way as to prevent localized overheating of any part of the tank, in the event vapors from such vents are ignited.
Each commercial tank venting device shall have stamped on it the opening pressure, the pressure at which the valve reaches the full open position, and the flow capacity at the latter pressure, expressed in cubic feet per hour of air at 60 deg. F. and at a pressure of 14.7 p.s.i.a.
The flow capacity of tank venting devices 12 inches and smaller in nominal pipe size shall be determined by actual test of each type and size of vent. These flow tests may be conducted by the manufacturer if certified by a qualified impartial observer, or may be conducted by an outside agency. The flow capacity of tank venting devices larger than 12 inches nominal pipe size, including manhole covers with long bolts or equivalent, may be calculated provided that the opening pressure is actually measured, the rating pressure and corresponding free orifice area are stated, the word "calculated" appears on the nameplate, and the computation is based on a flow coefficient of 0.5 applied to the rated orifice area.
Vent piping shall be constructed in accordance with paragraph (c) of this section.
Where vent pipe outlets for tanks storing Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), are adjacent to buildings or public ways, they shall be located so that the vapors are released at a safe point outside of buildings and not less than 12 feet above the adjacent ground level. In order to aid their dispersion, vapors shall be discharged upward or horizontally away from closely adjacent walls. Vent outlets shall be located so that flammable vapors will not be trapped by eaves or other obstructions and shall be at least five feet from building openings.
When tank vent piping is manifolded, pipe sizes shall be such as to discharge, within the pressure limitations of the system, the vapors they may be required to handle when manifolded tanks are subject to the same fire exposure.
The area surrounding a tank or a group of tanks shall be provided with drainage as in subdivision (b) of this subdivision, or shall be diked as provided in subdivision (c) of this subdivision, to prevent accidental discharge of liquid from endangering adjoining property or reaching waterways.
Where protection of adjoining property or waterways is by means of a natural or manmade drainage system, such systems shall comply with the following:
The drainage system shall terminate in vacant land or other area or in an impounding basin having a capacity not smaller than that of the largest tank served. This termination area and the route of the drainage system shall be so located that, if the flammable liquids in the drainage system are ignited, the fire will not seriously expose tanks or adjoining property.
Where protection of adjoining property or waterways is accomplished by retaining the liquid around the tank by means of a dike, the volume of the diked area shall comply with the following requirements:
Except as provided in subdivision (2) of this subdivision, the volumetric capacity of the diked area shall not be less than the greatest amount of liquid that can be released from the largest tank within the diked area, assuming a full tank. The capacity of the diked area enclosing more than one tank shall be calculated by deducting the volume of the tanks other than the largest tank below the height of the dike.
For a tank or group of tanks with fixed roofs containing crude petroleum with boilover characteristics, the volumetric capacity of the diked area shall be not less than the capacity of the largest tank served by the enclosure, assuming a full tank. The capacity of the diked enclosure shall be calculated by deducting the volume below the height of the dike of all tanks within the enclosure.
Walls of the diked area shall be of earth, steel, concrete or solid masonry designed to be liquid tight and to withstand a full hydrostatic head. Earthen walls 3 feet or more in height shall have a flat section at the top not less than 2 feet wide. The slope of an earthen wall shall be consistent with the angle of repose of the material of which the wall is constructed.
The walls of the diked area shall be restricted to an average height of 6 feet above interior grade.
No loose combustible material, empty or full drum or barrel, shall be permitted within the diked area.
Openings for gaging shall be provided with a vaportight cap or cover.
For Category 2 flammable liquids and Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), other than crude oils, gasolines, and asphalts, the fill pipe shall be so designed and installed as to minimize the possibility of generating static electricity. A fill pipe entering the top of a tank shall terminate within 6 inches of the bottom of the tank and shall be installed to avoid excessive vibration.
Filling and emptying connections which are made and broken shall be located outside of buildings at a location free from any source of ignition and not less than 5 feet away from any building opening. Such connection shall be closed and liquidtight when not in use. The connection shall be properly identified.
The distance between any two flammable liquid storage tanks shall not be less than 3 feet.
Except as provided in paragraph (b)(2)(ii)(c) of this section, the distance between any two adjacent tanks shall not be less than one-sixth the sum of their diameters. When the diameter of one tank is less than one-half the diameter of the adjacent tank, the distance between the two tanks shall not be less than one-half the diameter of the smaller tank.
Where crude petroleum in conjunction with production facilities are located in noncongested areas and have capacities not exceeding 126,000 gallons (3,000 barrels), the distance between such tanks shall not be less than 3 feet.
Where unstable flammable liquids are stored, the distance between such tanks shall not be less than one-half the sum of their diameters.
When tanks are compacted in three or more rows or in an irregular pattern, greater spacing or other means shall be provided so that inside tanks are accessible for firefighting purposes.
Related Code Sections
1910.106(b)(2) Hazardous Materials, Installation of Outside Aboveground Tanks
Tanks of 3,000 bbls (barrels). capacity or less containing crude petroleum in crude-producing areas and outside aboveground atmospheric tanks ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(b) Tank Storage > 1910.106(b)(2) Installation of Outside Aboveground Tanks
1910.106(b)(2)(ii) Hazardous Materials, Spacing (Shell-To-Shell) Between Aboveground Tanks
The distance between any two flammable liquid storage tanks shall not be less than 3 feet ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(b) Tank Storage > 1910.106(b)(2) Installation of Outside Aboveground Tanks > 1910.106(b)(2)(ii) Spacing (Shell-To-Shell) Between Aboveground Tanks
1910.106(b)(2)(i) Hazardous Materials, [Reserved]
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(b) Tank Storage > 1910.106(b)(2) Installation of Outside Aboveground Tanks > 1910.106(b)(2)(i) [Reserved]
1910.106(b)(2)(iii) Hazardous Materials, [Reserved]
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(b) Tank Storage > 1910.106(b)(2) Installation of Outside Aboveground Tanks > 1910.106(b)(2)(iii) [Reserved]
1910.106(b)(2)(v) Hazardous Materials,
"Emergency relief venting for fire exposure for aboveground tanks ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(b) Tank Storage > 1910.106(b)(2) Installation of Outside Aboveground Tanks > 1910.106(b)(2)(v)