[F] 907.2.11.3 Installation Near Cooking Appliances
JUMP TO FULL CODE CHAPTER
Smoke alarms shall not be installed in the following locations unless this would prevent placement of a smoke alarm in a location required by Section 907.2.11.1 or 907.2.11.2:
- Ionization smoke alarms shall not be installed less than 20 feet (6096 mm) horizontally from a permanently installed cooking appliance.
- Ionization smoke alarms with an alarm-silencing switch shall not be installed less than 10 feet (3048 mm) horizontally from a permanently installed cooking appliance.
- Photoelectric smoke alarms shall not be installed less than 6 feet (1829 mm) horizontally from a permanently installed cooking appliance.
Related Code Sections
704.2.1.3 Fire Safety Requirements, Installation Near Cooking Appliances
a permanently installed cooking appliance. Photoelectric smoke alarms shall not be installed less than 6 feet (1829 mm) horizontally from a permanently ...
Property Maintenance Code 2015 of New York State > 7 Fire Safety Requirements > 704 Fire Protection Systems > 704.2 Single-And Multiple-Station Smoke Alarms > 704.2.1 Where Required > 704.2.1.3 Installation Near Cooking Appliances
704.6.1.3 Fire Safety Requirements, Installation Near Cooking Appliances
installed cooking appliance. Photoelectric smoke alarms shall not be installed less than 6 feet (1829 mm) horizontally from a permanently installed ...
2020 Property Maintenance Code of NYS > 7 Fire Safety Requirements > 704 Fire Protection Systems > 704.6 Single- or Multiple-Station Smoke Alarms > 704.6.1 Where Required > 704.6.1.3 Installation Near Cooking Appliances
907.2.10.3 Fire Protection and Life Safety Systems, Installation Near Cooking Appliances
cooking appliance. Ionization smoke alarms with an alarm-silencing switch shall not be installed less than 10 feet (3048 mm) horizontally from ...
2020 Building Code of New York State > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.10 Single- And Multiple-Station Smoke Alarms > 907.2.10.3 Installation Near Cooking Appliances
907.2.10.3 Fire Protection and Life Safety Systems, Installation Near Cooking Appliances
cooking appliance. Ionization smoke alarms with an alarm-silencing switch shall not be installed less than 10 feet (3048 mm) horizontally from ...
2020 Fire Code of NYS > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.10 Single- And Multiple-Station Smoke Alarms > 907.2.10.3 Installation Near Cooking Appliances
907.2.11.3 Fire Protection Systems, Installation Near Cooking Appliances
cooking appliance. Ionization smoke alarms with an alarm-silencing switch shall not be installed less than 10 feet (3048 mm) horizontally from ...
Fire Code 2015 of New York State > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.11 Single- And Multiple-Station Smoke Alarms > 907.2.11.3 Installation Near Cooking Appliances