3307.7.6 Installation and Removal of Fences
JUMP TO FULL CODE CHAPTER
Fences required by this section shall be installed prior to the commencement of work. Such required fences shall not be removed until:
- The site has been filled and graded and all hazards to the public removed; or
- The façade has been enclosed, with all doors and windows installed, and all exterior work, except for incidental work including but not limited to landscaping, painting, weatherproofing, or installation of signs or fixtures, has been completed.
Related Code Sections
3307.7.6 Safeguards During Construction or Demolition, Installation and Removal of Fences
Fences required by this section shall be installed prior to the commencement of work. Such required fences shall not be removed until: The site has ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3307 Protection of Pedestrians > 3307.7 Fences > 3307.7.6 Installation and Removal of Fences
3307.10 Safeguards During Construction or Demolition, Repair, Maintenance and Removal
, shall immediately remove sidewalk sheds, fences, guard rails, temporary walkways, debris and other obstructions and leave such public property in as good ...
NYC Building Code 2008 > 33 Safeguards During Construction or Demolition > 3307 Protection of Pedestrians > 3307.10 Repair, Maintenance and Removal
3314.2 Safeguards During Construction or Demolition, Permit
and enclosed with a fence in accordance with Section 3307; and
The installation, use, and removal of the scaffold is confined within the site ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3314 Scaffolds > 3314.2 Permit
Section 3111 Special Construction, Fences
Fences are permitted to be erected to a maximum height of 10 feet (3048 mm) above the ground.
Exceptions:
In residence districts ...
Section 3112 Special Construction, Fences
Fences are permitted to be erected to a maximum height of 10 feet (3048 mm) above the ground. Exceptions: In residence districts ...