REFERENCE
Amendment Styling
Industry-leading search
Suggested code sections
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

§22-01 Installation and Maintenance of Pressure Tanks Operating at a Pressure in Excess of 15 PSI and Their Proximity to Gas Supply or Service Lines

Title 1 ‒ Department of Buildings > 22 Pressure Tanks > §22-01 Installation and Maintenance of Pressure Tanks Operating at a Pressure in Excess of 15 PSI and Their Proximity to Gas Supply or Service Lines
JUMP TO FULL CODE CHAPTER
   (a)   Applicability. These regulations shall apply to tanks containing water and air in combination, under pressure exceeding 15 psi above atmospheric pressure, where the pressure is supplied and maintained by pumps connected directly to the tanks.
   (b)   Design. The system shall be designed by a registered Architect or a Licensed Professional Engineer. An application and plans shall be filed and the approval of the department obtained. The plans and application shall contain, but not be limited to:
      (1)   Size and location of high pressure tanks.
      (2)   The operating pressures and temperatures.
      (3)   The location, type and specifications of pressure relief valves.
   (c)   Location.
      (1)   All high pressure tanks shall be located a clear distance of at least five feet horizontally from a gas service or distribution line or its vertical projection upon the floor.
      (2)   All new high pressure tanks installations shall be located in rooms separated from gas service or distribution lines.
      (3)   In cases where the spatial relationship between tanks and gas services does not comply with the regulations, it shall be the responsibility of the party responsible for the last installation to correct the violation.
   (d)   Installation.
      (1)   Installation with the exception of welding, shall be under controlled inspection by the engineer responsible for the design, or by a Professional Engineer acceptable to him.
      (2)   The welding shall be under controlled inspection of an Engineer, supervising a welding inspection agency acceptable to the Department of Buildings.
      (3)   Welders shall be qualified for all pipe sizes, wall thicknesses and positions in accordance with either the American Petroleum Institute, 1801 K Street, N.W., Washington, D.C. 20006, Standard for Welding Pipelines and Related Facilities, Fourteenth Edition, January 1977, (API STD 1104-1977), or the American Society of Mechanical Engineers, Welding and Brazing Qualification, Section VIII, Boiler and Pressure Vessel Code, 1980, (ANSI/ASTM BPV-IX-1980), and requalified on an annual basis.
      (4)   The qualification testing shall be performed by an agency listed with the Department of Buildings, and the inspector shall have a minimum radiography qualification of Level II in accordance with the American Society for Nondestructive Testing, 3200 Riverside Drive, Columbus, Ohio 43221, Recommended Practice, Document No. SNT-TC-1A-1980.
      (5)   Copies of the certified welder qualification reports shall be maintained by the responsible welding agency and shall be made available upon request to the Department of Buildings.
      (6)   No reports from any welding inspection agency shall be accepted unless such agency has first requested and obtained approval from this Office, in accordance with Rule 2511(G)(1) of the Board of Standards and Appeals Welding Rules.
      (7)   All welded piping shall be butt welded.
      (8)   Radiography shall be performed on all butt welds in accordance with API STD 1104-1977 or ANSI/ASTM BPV-IX-1980.
      (9)   Testing — A hydrostatic test of the completed installation at 150 percent of the design pressure adjusted to compensate for the difference in gas or fluid pressure and the ambient temperature shall be conducted. Where the changes in an existing system incorporating high pressure tanks involves less than 30 percent of the piping system, the testing may be in accordance with Standard Power Piping, ANSI B31.1-1980.

Related Code Sections


Appendix A Selected Rules of the Department of Buildings [PDF] (page 3)
Installation and Maintenance of Pressure Tanks Operating at a Pressure in Excess of 15 PSI and Their Proximity to Gas Supply or Service Lines Ch. 23 ...
NYC 1968 Code (Vol II) [PDF] > A Selected Rules of the Department of Buildings
Appendix A Selected Rules of the Department of Buildings [PDF] (page 69)
Installation and Maintenance of Pressure Tanks Operating at a Pressure in Excess of 15 PSI and Their Proximity to Gas Supply or Service Lines ...
NYC 1968 Code (Vol II) [PDF] > A Selected Rules of the Department of Buildings
606.8 Water Supply and Distribution, Pressure Tanks
All pressure tanks shall be located in rooms separated from gas service or distribution lines ...
NYC Plumbing Code 2014 > 6 Water Supply and Distribution > 606 Installation of the Building Water Distribution System > 606.8 Pressure Tanks
E.2 Meters and Gas Service Piping, Gas Regulator and Gas Regulator Vent Outlets
Inside gas meter piping operating at a pressure in excess of 15 psig (103 kPa gauge) shall comply with the following ...
NYC Fuel Gas Code 2014 > E Meters and Gas Service Piping > E.2 Gas Regulator and Gas Regulator Vent Outlets
Reference Standard 16 Plumbing and Gas Piping [PDF] (page 31)
) Tank controls.-Supply lines to and from pressure 239 ...
NYC 1968 Code (Vol II) [PDF] > Reference Standard 16 Plumbing and Gas Piping
Help Contact Us Privacy Terms
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL LEARN MORE