// CODE SNIPPET
2415.7 Inspections, Testing and Recertification
Go To Full Code Chapter
2415.7.1
A minimum of 1 percent of the structurally glazed panels shall be tested for load carrying capacity and sealant adhesion in accordance with Chapter 16 (High-Velocity Hurricane Zones) and ASTM E330.
2415.7.2
Structural glazed panels shall be inspected by a Florida-registered architect or professional engineer for conformance with the approved design and installation procedures determined by the authority having jurisdiction prior to the erection of such panels and after the seal curing period established by the silicone manufacturer.
2415.7.3
It shall be the responsibility of the contractor to verify the adhesion of the cured sealant periodically throughout the application to assure compliance with the manufacturer's specifications and quality of application.
2415.7.4
Structural glazing systems on threshold buildings shall be recertified by the owner as specified by the authority having jurisdiction at six month intervals for the first year after installation. Subsequently, such systems shall be recertified every five years at regular intervals.
2415.7.5
Such recertifications shall determine the structural condition and adhesion capacity of the silicone sealant.
Related Code Sections
2415.7 Glass and Glazing, Inspections, Testing and Recertification
A minimum of 1 percent of the structurally glazed panels shall be tested for load carrying capacity and sealant adhesion in accordance with Chapter ...
2415.7 Glass and Glazing, Inspections, Testing and Recertification
A minimum of 1 percent of the structurally glazed panels shall be tested for load carrying capacity and sealant adhesion in accordance with Chapter ...
2415.7 Glass and Glazing, Inspections, Testing and Recertification
A minimum of 1 percent of the structurally glazed panels shall be tested for load carrying capacity and sealant adhesion in accordance with Chapter ...
2415.7.2 Glass and Glazing,
Structural glazed panels shall be inspected by a Florida-registered architect or professional engineer for conformance with the approved design ...
2415.7.1 Glass and Glazing,
A minimum of 1 percent of the structurally glazed panels shall be tested for load carrying capacity and sealant adhesion in accordance with Chapter ...