5.6.3 Input Data
Go To Full Code Chapter
5.6.3.1 Data
Input data for computer fire models shall be obtained in accordance with ASTM E1591, Standard Guide for Obtaining Data for Deterministic Fire Models. Data for use in analytical models that are not computer-based fire models shall be obtained using appropriate measurement, recording, and storage techniques to ensure the applicability of the data to the analytical method being used.
5.6.3.2 Data Requirements
A complete listing of input data requirements for all models, engineering methods, and other calculation or verification methods required or proposed as part of the performance-based design shall be provided.
5.6.3.3* Uncertainty and Conservatism of Data
Uncertainty in input data shall be analyzed and, as determined appropriate by the authority having jurisdiction, addressed through the use of conservative values.
Related Code Sections
5.6.3 Performance-Based Option, Input Data
Input data for computer fire models shall be obtained in accordance with ASTM E1591, Standard Guide for Obtaining Data for Deterministic Fire Models ...
5.8.7 Performance-Based Option, Input Data
Input data to models and assessment methods, including sensitivity analyses, shall be documented ...
5.4.2 Performance-Based Option, Assumptions and Design Specifications Data
Each assumption and design specification used in the design shall be accurately translated into input data specifications, as appropriate ...
5.5.4 Performance-Based Option, Design Fire Scenarios Data
Each design fire scenario used in the performance-based design proposal shall be translated into input data specifications, as appropriate ...