// CODE SNIPPET
[F] 907.4 Initiating Devices
JUMP TO FULL CODE CHAPTER
Where manual or automatic alarm initiation is required as part of a fire alarm system, the initiating devices shall be installed in accordance with Sections 907.4.1 through 907.4.3.1.
In areas that are not continuously occupied, a single smoke detector shall be provided at the location of each fire alarm control unit, notification appliance circuit power extenders, and supervising station transmitting equipment.
Exception: Where ambient conditions prohibit installation of a smoke detector, a heat detector shall be permitted.
Where a manual fire alarm system is required by another section of this code, it shall be activated by fire alarm boxes installed in accordance with Sections 907.4.2.1 through 907.4.2.6.
Manual fire alarm boxes shall be located not more than 5 feet (1524 mm) from the entrance to each exit. In buildings not protected by an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, additional manual fire alarm boxes shall be located so that the distance of travel to the nearest box does not exceed 200 feet (60 960 mm).
The height of the manual fire alarm boxes shall be not less than 42 inches (1067 mm) and not more than 48 inches (1372 mm) measured vertically, from the floor level to the activating handle or lever of the box.
Manual fire alarm boxes shall be red in color.
Where fire alarm systems are not monitored by a supervising station, an approved permanent sign shall be installed adjacent to each manual fire alarm box that reads: WHEN ALARM SOUNDS CALL FIRE DEPARTMENT.
Exception: Where the manufacturer has permanently provided this information on the manual fire alarm box.
The fire code official is authorized to require the installation of listed manual fire alarm box protective covers to prevent malicious false alarms or to provide the manual fire alarm box with protection from physical damage. The protective cover shall be transparent or red in color with a transparent face to permit visibility of the manual fire alarm box. Each cover shall include proper operating instructions. A protective cover that emits a local alarm signal shall not be installed unless approved. Protective covers shall not project more than that permitted by Section 1003.3.3.
Manual fire alarm boxes shall be provided with ready access, unobstructed, unobscured and visible at all times.
Where an automatic smoke detection system is required it shall utilize smoke detectors unless ambient conditions prohibit such an installation. In spaces where smoke detectors cannot be utilized due to ambient conditions, approved automatic heat detectors shall be permitted.
For conditions other than specific fire safety functions noted in Section 907.3, in areas where ambient conditions prohibit the installation of smoke detectors, an automatic sprinkler system installed in such areas in accordance with Section 903.3.1.1 or 903.3.1.2 and that is connected to the fire alarm system shall be approved as automatic heat detection.
Related Code Sections
(C) Special Equipment, Initiation Device
The initiation device(s) shall initiate the rapid shutdown function of the PV system. The device's "off" position shall indicate that the rapid ...
National Electrical Code 2020 of Illinois > 6 Special Equipment > 690 Solar Photovoltaic (PV) Systems > 690.12 Rapid Shutdown of PV Systems on Buildings > (C) Initiation Device
(C) Special Equipment, Initiation Device
The initiation device(s) shall initiate the rapid shutdown function of the PV system. The device "off" position shall indicate that the rapid ...
National Electrical Code 2017 of Illinois > 6 Special Equipment > 690 Solar Photovoltaic (PV) Systems > 690.12 Rapid Shutdown of PV Systems on Buildings > (C) Initiation Device
907.4 Fire Protection and Life Safety Systems, Initiating Devices
Where manual or automatic alarm initiation is required as part of a fire alarm system, the initiating devices shall be installed in accordance ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.4 Initiating Devices
907.4 Fire Protection and Life Safety Systems, Initiating Devices
be initiated by one or more of the following. Initiating devices shall be installed in accordance with Sections 907.4.1 through 907.4.3.1. Manual ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.4 Initiating Devices
415.11.3.5.4 Special Detailed Requirements Based on Occupancy and Use, Alarm-Initiating Devices
An approved emergency telephone system, local alarm manual pull stations, or other approved alarm-initiating devices are allowed to be used ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.11 Group H-5 > 415.11.3 Service Corridors > 415.11.3.5 Emergency Alarm System > 415.11.3.5.4 Alarm-Initiating Devices