[F] 907.6.3 Initiating Device Identification
JUMP TO FULL CODE CHAPTER
The Required fire alarm systems and
initiating devices shall identify the specific initiating device address, location, device type, floor level where applicable and status including indication of normal, alarm, trouble and supervisory status, as appropriate.
Exceptions:
- Fire alarm systems in single-story buildings less than 22,500 square feet (2090 m2) in area.
- Fire alarm systems that only include manual fire alarm boxes, waterflow initiating devices and not more than 10 additional alarm-initiating devices.
- Special initiating devices that do not support individual device identification.
- Fire alarm systems or devices that are replacing existing equipment.
The initiating device status shall be annunciated at an approved on-site location.
Related Code Sections
907.6.3.1 Fire Protection Systems, Annunciation
The initiating device status shall be annunciated at an approved on-site location ...
Ohio Building Code 2017 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.6 Installation and Monitoring > 907.6.3 Initiating Device Identification > 907.6.3.1 Annunciation
904.4.1 Fire Protection Systems, Inspection
, location and spacing of automatic- and manual-initiating devices. Size, placement and position of nozzles or discharge orifices. Location ...
Ohio Building Code 2011 > 9 Fire Protection Systems > 904 Alternative Automatic Fire-Extinguishing Systems > 904.4 Inspection and Testing > 904.4.1 Inspection
904.4.1 Fire Protection Systems, Inspection
hazard.
Type, location and spacing of automatic- and manual-initiating devices.
Size, placement and position of nozzles or discharge orifices ...
Ohio Building Code 2017 > 9 Fire Protection Systems > 904 Alternative Automatic Fire-Extinguishing Systems > 904.4 Inspection and Testing > 904.4.1 Inspection
904.4.1 Ohio Administrative Code 1301:7-7-09 Fire Protection Systems, Inspection
(ii) Type, location and spacing of automatic- and manual-initiating devices. (iii) Size, placement and position of nozzles or discharge orifices ...
Ohio Fire Code 2011 > Ohio Administrative Code 1301:7-7-09 Fire Protection Systems > 904 Alternative Automatic Fire-Extinguishing Systems > 904.4 Inspection and Testing > 904.4.1 Inspection
303.1 General Regulations, Identification
Each length of pipe and each pipe fitting, trap, fixture, material and device utilized in a plumbing system shall bear the identification ...