2206.9.1 Initial Tank Test
JUMP TO FULL CODE CHAPTER
Underground and aboveground tanks shall be tested hydrostatically at 15 pounds per square inch (psig)(103.4 kPa), or one and one-half times the maximum anticipated static head pressure, whichever is greater, for the inner tank, and pneumatically or hydrostatically at 5 pounds per square inch (psig)(34.5 kPa) for the annular space (secondary containment tank). When a pneumatic test is allowed, an inert gas shall be used; however, air may be used if the tank or piping system does not contain any liquid motor fuel or combustible vapor. Test pressure shall be maintained for a sufficient time to complete visual inspection, but not less than 1 hour. A tank shall be deemed to have passed the test if it shows no evidence of leakage or permanent deformation.
Related Code Sections
Section 1308 Fuel-Oil Piping and Storage, Testing
piping, and all tanks complying with the alternate tank design and construction standards contained in Section 1305.14, shall be hydrostatically tested ...
Section 1308 Fuel-Oil Piping and Storage, Testing
piping, and all tanks complying with the alternate tank design and construction standards contained in Section 1305.14, shall be hydrostatically tested ...
907.16 Fire Protection Systems, Acceptance Tests
, supervisory-signal initiating devices and circuits, signaling line circuits, and primary and secondary power supplies shall be tested in accordance ...
NYC Building Code 2008 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.16 Acceptance Tests
107.2 Administration, Testing
Where any work or installation does not pass an initial test or inspection ...
107.3 Administration, Testing
Where any work or installation does not pass an initial test or inspection ...