E4203.4.5 Indoor Spas and Hot Tubs
Go To Full Code Chapter
-
Luminaires, lighting outlets and ceiling-suspended paddle fans located over the spa or hot tub or within 5 feet (1524 mm) from the inside walls of the spa or hot tub shall be not less than 7 feet, 6 inches (2286 mm) above the maximum water level and shall be protected by a ground-fault circuit interrupter. [680.43(B)(1)(b)]Luminaires, lighting outlets and ceiling-suspended paddle fans that are located 12 feet (3658 mm) or more above the maximum water level shall not require ground-fault circuit-interrupter protection. [680.43(B)(1)(a)]
-
Luminaires protected by a ground-fault circuit interrupter and complying with Item 2.1 or 2.2 shall be permitted to be installed less than 7 feet, 6 inches (2286 mm) over a spa or hot tub.2.1. Recessed luminaires shall have a glass or plastic lens and nonmetallic or electrically isolated metal trim, and shall be suitable for use in damp locations.2.2. Surface-mounted luminaires shall have a glass or plastic globe and a nonmetallic body or a metallic body isolated from contact. Such luminaires shall be suitable for use in damp locations. [680.43(B)(1)(c)(1) and (2)]
Related Code Sections
E4203.4.5 Swimming Pools, Indoor Spas and Hot Tubs
Luminaires, lighting outlets and ceiling-suspended paddle fans located over the spa or hot tub or within 5 feet (1524 mm) from the inside ...
E4202.1 Swimming Pools, General
A
A
—
Ad
Indoor spas and hot tubs, and other pool, spa or hot tub associated equipment: from branch circuit OCPD to equipment
A
A
A ...
E4204.5 Swimming Pools, Bonding of Indoor Hot Tubs and Spas
The following parts of indoor hot tubs and spas shall be bonded together: All metal fittings within or attached to the hot tub or spa structure ...