// CODE SNIPPET
2301.4 Indoor Motor Fuel-Dispensing Facilities
JUMP TO FULL CODE CHAPTER
Motor fuel-dispensing facilities located inside buildings shall comply with the International Building Code and NFPA 30A.
Where motor fuel-dispensing facilities are located inside buildings and the dispensers are located above spaces within the building, openings beneath dispensers shall be sealed to prevent the flow of leaked fuel to lower building spaces.
Related Code Sections
2301.4 Motor Fuel-Dispensing Facilities and Repair Garages, Indoor Motor Fuel-Dispensing Facilities
Motor fuel-dispensing facilities located inside buildings shall comply with the International Building Code and NFPA 30A ...
Fire Code 2021 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2301 General > 2301.4 Indoor Motor Fuel-Dispensing Facilities
2301.4 Motor Fuel-Dispensing Facilities and Repair Garages, Indoor Motor Fuel-Dispensing Facilities
Motor fuel-dispensing facilities located inside buildings shall comply with the International Building Code and NFPA 30A ...
Fire Code 2018 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2301 General > 2301.4 Indoor Motor Fuel-Dispensing Facilities
2309.3.1.2.1 Motor Fuel-Dispensing Facilities and Repair Garages, Maintenance
Gaseous hydrogen systems and detection devices shall be maintained in accordance with the manufacturer's instructions ...
Fire Code 2021 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2309 Hydrogen Motor Fuel-Dispensing and Generation Facilities > 2309.3 Location on Property > 2309.3.1 Location of Operations and Equipment > 2309.3.1.2 Indoors > 2309.3.1.2.1 Maintenance
2309.3.1.2.1 Motor Fuel-Dispensing Facilities and Repair Garages, Maintenance
Gaseous hydrogen systems and detection devices shall be maintained in accordance with the manufacturer's instructions ...
Fire Code 2018 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2309 Hydrogen Motor Fuel-Dispensing and Generation Facilities > 2309.3 Location on Property > 2309.3.1 Location of Operations and Equipment > 2309.3.1.2 Indoors > 2309.3.1.2.1 Maintenance
2309.3.1.2.3 Motor Fuel-Dispensing Facilities and Repair Garages, Ignition Source Control
Open flames, flame-producing devices and other sources of ignition shall be controlled in accordance with Chapter 58 ...
Fire Code 2018 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2309 Hydrogen Motor Fuel-Dispensing and Generation Facilities > 2309.3 Location on Property > 2309.3.1 Location of Operations and Equipment > 2309.3.1.2 Indoors > 2309.3.1.2.3 Ignition Source Control