2.12-3.2.2.1 Individual Therapy Room
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.12 Specific Requirements for Outpatient Rehabilitation Therapy Facilities > 2.12-3 Patient Care and Diagnostic Areas > 2.12-3.2 Physical and Occupational Therapy > 2.12-3.2.2 Therapy Areas > 2.12-3.2.2.1 Individual Therapy Room
Go To Full Code Chapter
- Where patient disrobing is necessary to receive treatment, an individual therapy room(s) that meets the requirements in this section shall be provided.
- Space requirements
- Area. An individual therapy room shall have a minimum clear floor area of 80 square feet (7.43 square meters).
- Clearances. Room arrangement shall permit a minimum clearance of 2 feet 8 inches (81.28 centimeters) on at least three sides of the therapy furniture and equipment.
Related Code Sections
2.12-3.2.2.1 Specific Requirements for Outpatient Rehabilitation Therapy Facilities, Individual Therapy Room
Where patient disrobing is necessary to receive treatment, an individual therapy room(s) that meets the requirements in this section shall ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.12 Specific Requirements for Outpatient Rehabilitation Therapy Facilities > 2.12-3 Patient Care and Diagnostic Areas > 2.12-3.2 Physical and Occupational Therapy > 2.12-3.2.2 Therapy Areas > 2.12-3.2.2.1 Individual Therapy Room
2.4-2.18.3 Specific Requirements for Critical Access Hospitals, Therapy Services
least one individual treatment room with a minimum clear floor area of 80 square feet (7.43 square meters) shall be provided. Treatment bays ...
*2.1-3.6 Common Elements for Outpatient Facilities, Radiation Therapy
beam radiation therapy room. See Section 2.1-3.6.8.15 (Support Areas for Radiation Therapy-Examination room) for requirements ...
*2.2-3.5 Specific Requirements for General Hospitals, Radiation Therapy
be provided for each external beam radiation therapy room. See Section 2.2-3.5.8.15 (Support Areas for Radiation Therapy-Examination room) for requirements ...
*2.6-3.1 Specific Requirements for Rehabilitation Hospitals, Rehabilitation Therapy
Provision of a private therapy room(s) should be considered ...