C402.4.1.2 Increased Skylight Area With Daylight Responsive Controls
Go To Full Code Chapter
The skylight area shall be not more than 6 percent of the roof area provided that daylight responsive controls are installed in toplitdaylight zones.
Upcodes Diagrams
Related Code Sections
C402.4.1.2 [CE] Commercial Energy Efficiency, Increased Skylight Area With Daylight Responsive Controls
The skylight area shall be permitted to be not more than 5 percent of the roof area provideddaylight responsive controls complying with Section ...
C402.4.1.2 [CE] Commercial Energy Efficiency, Increased Skylight Area With Daylight Responsive Controls
The skylight area shall be not more than 6 percent of the roof area provided that daylight responsive controls are installed in toplitdaylight zones ...
C402.4.1.2 [CE] Commercial Energy Efficiency, Increased Skylight Area With Daylight Responsive Controls
The skylight area shall be not more than 6 percent of the roof area provided that daylight responsive controls complying with Section C405.2.3.1 ...
C402.4.3.2 [CE] Commercial Energy Efficiency, Increased Skylight U-factor
Where skylights are installed abovedaylight zones provided with daylight responsive controls , a maximum U -factor of 0.9 shall be permitted ...
C402.4.1.1 [CE] Commercial Energy Efficiency, Increased Vertical Fenestration Area With Daylight Responsive Controls
responsive controls are installed in daylight zones. Visible transmittance (VT) of vertical fenestration is not less than 1.1 times solar heat gain ...