18.5 In-Rack Sprinkler System Requirements for Protection of Rubber Tires
Go To Full Code Chapter
18.5.1
In-rack sprinklers, where provided, shall be installed in accordance with Chapter 17, except as modified by 18.5.2 through 18.5.4.
18.5.2
The maximum horizontal spacing of sprinklers in racks shall be 8 ft (2.4 m).
18.5.3
18.5.4
Sprinklers in racks shall discharge at not less than 30 psi (2.1 bar).