R337.4.2 Ignition-Resistant Material
JUMP TO FULL CODE CHAPTER
Ignition-resistant
materials shall comply with one of the following:
- The requirements in Section R337.4.3 when tested in accordance with the test procedures set forth in ASTM E84 or UL 723,
- The test procedures and requirements set forth in SFM Standard 12-7A-5 "Ignition-Resistant Material", or
- One of the alternative methods in Section R337.4.4.
Related Code Sections
704A.2 [SFM] Materials and Construction Methods for Exterior Wildfire Exposure, Ignition-Resistant Material
Ignition-resistant materials
shall comply with one of the following:
The requirements in Section 704A.3 when tested in
accordance with the test ...
Los Angeles Building Code > 7A [SFM] Materials and Construction Methods for Exterior Wildfire Exposure > 704A Ignition-Resistant Construction > 704A.2 Ignition-Resistant Material
R337.4.2 Building Planning, Ignition-Resistant Material
Ignition-resistant
materials shall comply with one of the following:
The requirements in Section R337.4.3 when tested in
accordance with the test ...
Los Angeles Residential Code > 3 Building Planning > R337.4 Ignition-Resistant Construction > R337.4.2 Ignition-Resistant Material
R337.9.5 Building Planning, Requirements for Type of Ignition-Resistant Material in Section R337.9.3, Item 6
The material shall
be tested in accordance with ASTM E2632 and shall comply
with the following condition of acceptance. The ASTM
E2632 test shall ...
Los Angeles Residential Code > 3 Building Planning > R337.9 Decking > R337.9.5 Requirements for Type of Ignition-Resistant Material in Section R337.9.3, Item 6
709A.4 [SFM] Materials and Construction Methods for Exterior Wildfire Exposure, Requirements for Type of Ignition-Resistant Material in Section 709A.3, Item 1
The material shall be tested in
accordance with both ASTM E2632 and ASTM E2726 and
shall comply with the conditions of acceptance in Sections
709A ...
Los Angeles Building Code > 7A [SFM] Materials and Construction Methods for Exterior Wildfire Exposure > 709A Decking > 709A.4 Requirements for Type of Ignition-Resistant Material in Section 709A.3, Item 1
R337.9.4.1 Building Planning, Conditions of Acceptance for ASTM E2632
The ASTM E2632 test shall be conducted on a
minimum of three test specimens and the conditions of
acceptance in Items 1 through 3 below shall be met ...
Los Angeles Residential Code > 3 Building Planning > R337.9 Decking > R337.9.4 Requirements for Type of Ignition-Resistant Material in Section R337.9.3, Item 1 > R337.9.4.1 Conditions of Acceptance for ASTM E2632