503.2 Ignition-Resistant Building Material
Go To Full Code Chapter
Ignition-resistant building materials shall comply with any one of the following:
-
Material shall be tested on all sides with the extended ASTM E84 (UL 723) test or ASTM E2768, except panel products shall be permitted to test only the front and back faces. Panel products shall be tested with a ripped or cut longitudinal gap of 1/8 inch (3.2 mm). Materials that, when tested in accordance with the test procedures set forth in ASTM E84 or UL 723 for a test period of 30 minutes, or with ASTM E2768, comply with the following:1.1. Flame spread. Material shall exhibit a flame spread index not exceeding 25 and shall not show evidence of progressive combustion following the extended 30-minute test.1.2. Flame front. Material shall exhibit a flame front that does not progress more than 101/2 feet (3200 mm) beyond the centerline of the burner at any time during the extended 30-minute test.1.3. Weathering. Ignition-resistant building materials shall maintain their performance in accordance with this section under conditions of use. Materials shall meet the performance requirements for weathering (including exposure to temperature, moisture and ultraviolet radiation) contained in the following standards, as applicable to the materials and the conditions of use:1.3.1. Method A "Test Method for Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing" in ASTM D2898, for fire-retardant-treated wood, wood-plastic composite and plastic lumber materials.1.3.2. ASTM D7032 for wood-plastic composite materials.1.3.3. ASTM D6662 for plastic lumber materials.1.4 Identification. Materials shall bear identification showing the fire test results.Exception: Materials composed of a combustible core and a noncombustible exterior covering made from either aluminum at a minimum 0.019 inch (0.48 mm) thickness or corrosion-resistant steel at a minimum 0.0149 inch (0.38 mm) thickness shall not be required to be tested with a ripped or cut longitudinal gap.
- Noncombustible material. Material that complies with the requirements for noncombustible materials in Section 202.
- Fire-retardant-treated wood. Fire-retardant-treated wood identified for exterior use and meeting the requirements of Section 2303.2 of the International Building Code.
- Fire-retardant-treated wood roof coverings. Roof assemblies containing fire-retardant-treated wood shingles and shakes that comply with the requirements of Section 1505.6 of the International Building Code and classified as Class A roof assemblies as required in Section 1505.2 of the International Building Code.
Upcodes Diagrams
Related Code Sections
503.2 Special Building Construction Regulations, Ignition-Resistant Building Material
Ignition-resistant building materials shall comply with any one of the following:
Material shall be tested on all sides with the extended ASTM ...
504.7 Special Building Construction Regulations, Appendages and Projections
-treated wood identified for exterior use and meeting the requirements of Section 2303.2 of the International Building Code. Ignition-resistant building ...
505.7 Special Building Construction Regulations, Appendages and Projections
-treated wood identified for exterior use and meeting the requirements of Section 2303.2 of the International Building Code. Ignition-resistant building ...
Section 504 Special Building Construction Regulations, Class 1 Ignition-Resistant Construction
for exterior use and meet the requirements of Section 2303.2 of the International Building Code. Ignition-resistant materials complying with Section ...
Section 202 Definitions, Definitions
in the International Building Code. IGNITION-RESISTANT BUILDING MATERIAL. A type of building material that resists ignition or sustained flaming combustion ...