The following replaces the indicated information in IECC Table C407.5.1(1).
IECC TABLE C407.5.1(1)
SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED DESIGNS
The vertical fenestration other than opaque doors section of this table is replaced with the following:
Vertical fenestration other than opaque doors Area
  1. The proposed vertical fenestration area; where the proposed vertical fenestration area is less than 30 percent of above-grade wall area.
  2. 30 percent of above-grade wall area where the proposed vertical fenestration area is 30 percent or more of the above-grade wall area.
As proposed
U-factor: as specified in Table C402. As proposed
SHGC: as specified in Table C402.4 except that for climates with no requirement (NR) SHGC = 0.40 shall be used As proposed
External shading and PF: None As proposed
Upcodes Diagrams

Related Code Sections

C407.4.1 [CE] Commercial Energy Efficiency, Compliance Report
checklist documenting the building component characteristics of the proposed design as specified in Table C407.5.1(1). The inspection checklist shall show ...