704.1.2.2 Identification of Hydrogen Piping Systems
JUMP TO FULL CODE CHAPTER
Hydrogen piping systems shall be marked in accordance with ANSI A13.1. Markings used for piping systems shall consist of the name of the contents and shall include a direction-of-flow arrow. Markings shall be provided at all of the following locations:
- At each valve.
- At wall, floor and ceiling penetrations.
- At each change of direction.
- At intervals not exceeding 20 feet (6096 mm).
Related Code Sections
704.1.2.2 Gaseous Hydrogen Systems, Identification of Hydrogen Piping Systems
Hydrogen piping systems shall be marked in accordance with ANSI A13.1. Markings used for piping systems shall consist of the name of the contents ...
2020 Fuel Gas Code of NYS > 7 Gaseous Hydrogen Systems > 704 Piping, Use and Handling > 704.1 Applicability > 704.1.2 Piping Systems > 704.1.2.2 Identification of Hydrogen Piping Systems
704.1.2.2 Gaseous Hydrogen Systems, Identification of Hydrogen Piping Systems
Hydrogen piping systems shall be marked in accordance with ANSI A13.1. Markings used for piping systems shall consist of the name of the contents ...
2010 Fuel Gas Code of NY > 7 Gaseous Hydrogen Systems > 704 Piping, Use and Handling > 704.1 Applicability > 704.1.2 Piping Systems > 704.1.2.2 Identification of Hydrogen Piping Systems
704.1.2.2 Gaseous Hydrogen Systems, Identification of Hydrogen Piping Systems
Hydrogen piping systems shall be marked in accordance with ANSI A13.1. Markings used for piping systems shall consist of the name of the contents ...
Fuel Gas Code 2015 of New York State > 7 Gaseous Hydrogen Systems > 704 (IFGC) Piping, Use and Handling > 704.1 Applicability > 704.1.2 Piping Systems > 704.1.2.2 Identification of Hydrogen Piping Systems
C102.6 Gray Water Recycling Systems, Identification
Distribution piping and reservoirs shall be identified as containing nonpotable water. Piping identification shall be in accordance with Section ...
2010 Plumbing Code of NY > C Gray Water Recycling Systems > C102 Systems for Flushing Water > C102.6 Identification
M1301.2 General Mechanical System Requirements, Identification
Each length of pipe and tubing and each pipe fitting utilized in a mechanical system shall bear the identification of the manufacturer ...
2020 Residential Code of New York State > 13 General Mechanical System Requirements > M1301 General > M1301.2 Identification