// CODE SNIPPET
1316.1.3 Hybrid Pressure
JUMP TO FULL CODE CHAPTER
The pipe size for each section of higher pressure gas piping shall be determined using the
longest length of piping from the point of delivery to the
most remote line pressure regulator. The pipe size from the
line pressure regulator to each outlet shall be determined
using the length of piping from the regulator to the most
remote outlet served by the regulator. [NFPA 54:6.1.3]
Related Code Sections
1215.1.3 Fuel Gas Piping, Hybrid Pressure
The pipe size for each section of higher pressure gas piping shall be determined using the longest length of piping from the point of delivery ...
Los Angeles Plumbing Code > 12 Fuel Gas Piping > 1215.0 Required Gas Piping Size > 1215.1 Pipe Sizing Methods > 1215.1.3 Hybrid Pressure
1315.1.3 Fuel Gas Piping, Hybrid Pressure
The pipe size for each section
of higher pressure gas piping shall be determined
using the longest length of piping from the point of delivery ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1315.0 Required Gas Piping Size > 1315.1 Pipe Sizing Methods > 1315.1.3 Hybrid Pressure
1316.1.3 Fuel Gas Piping, Hybrid Pressure
The pipe size for each section of higher pressure gas piping shall be determined using the
longest length of piping from the point of delivery ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1316.0 Required Gas Piping Size > 1316.1 Pipe Sizing Methods > 1316.1.3 Hybrid Pressure
412.1.3.1 Plumbing Fixtures and Fixture Fittings, Urinal, Hybrid
[BSC-CG] Where
approved, hybrid urinals shall be considered nonwater
urinals in compliance with Chapter 5, Division
A5.3 of the California Green ...
Los Angeles Plumbing Code > 4 Plumbing Fixtures and Fixture Fittings > 412.0 Urinals > 412.1 Application > 412.1.3 Nonwater Urinals > 412.1.3.1 Urinal, Hybrid
1224.28.5 Interior Environment, Hybrid Operating Room(s)
Hybrid operating rooms shall comply with the requirements of Section 1224.15 and comply with the requirements in this section ...
Los Angeles Building Code > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.28 Supplemental Surgery and Special Procedure Services > 1224.28.5 Hybrid Operating Room(s)