// CODE SNIPPET
C403.3.2 HVAC Equipment Performance Requirements
JUMP TO FULL CODE CHAPTER
Equipment shall meet the minimum efficiency requirements of Tables C403.3.2(1) through C403.3.2(16) when tested and rated in accordance with the applicable test procedure. Plate-type liquid-to-liquid heat exchangers shall meet the minimum requirements of AHRI 400. The efficiency shall be verified through certification under an approved certification program or, where a certification program does not exist, the equipment efficiency ratings shall be supported by data furnished by the manufacturer. Where multiple rating conditions or performance requirements are provided, the equipment shall satisfy all stated requirements. Where components, such as indoor or outdoor coils, from different manufacturers are used, calculations and supporting data shall be furnished by the designer that demonstrates that the combined efficiency of the specified components meets the requirements herein.
TABLE C403.3.2(1)
ELECTRICALLY OPERATED UNITARY AIR CONDITIONERS AND CONDENSING UNITS—MINIMUM EFFICIENCY REQUIREMENTSc, d
EQUIPMENT TYPE |
SIZE CATEGORY | HEADING SECTION TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY |
TEST PROCEDUREa |
Air conditioners, air cooled | < 65,000 Btu/hb | All | Split system, three phase and applications outside US single phaseb | 13.0 SEER before 1/1/2023 13.4 SEER2 after 1/1/2023 |
AHRI 210/240—2017 before 1/1/2023 AHRI 210/240—2023 after 1/1/2023 |
Single-package, three phase and applications outside US single phaseb | 14.0 SEER before 1/1/2023 13.4 SEER2 after 1/1/2023 |
||||
Space constrained, air cooled | ≤ 30,000 Btu/hb | All | Split system, three phase and applications outside US single phaseb | 12.0 SEER before 1/1/2023 11.7 SEER2 after 1/1/2023 |
AHRI 210/240—2017 before 1/1/2023 AHRI 210/240—2023 after 1/1/2023 |
Single package, three phase and applications outside US single phaseb | 12.0 SEER before 1/1/2023 11.7 SEER2 after 1/1/2023 |
||||
Small duct, high velocity, air cooled | < 65,000 Btu/hb | All | Split system, three phase and applications outside US single phaseb | 12.0 SEER before 1/1/2023 12.1 SEER2 after 1/1/2023 |
AHRI 210/240—2017 before 1/1/2023 AHRI 210/240—2023 after 1/1/2023 |
Air conditioners, air cooled | ≥ 65,000 Btu/h and < 135,000 Btu/h |
Electric resistance (or none) |
Split systemand single package | 11.2 EER 12.9 IEER before 1/1/2023 14.8 IEER after 1/1/2023 |
AHRI 340/360 |
All other | 11.0 EER 12.7 IEER before 1/1/2023 14.6 IEER after 1/1/2023 |
||||
≥ 135,000 Btu/h and < 240,000 Btu/h |
Electric resistance (or none) |
11.0 EER 12.4 IEER before 1/1/2023 14.2 IEER after 1/1/2023 |
|||
All other | 10.8 EER 12.2 IEER before 1/1/2023 14.0 IEER after 1/1/2023 |
||||
≥ 240,000 Btu/h and < 760,000 Btu/h |
Electric resistance (or none) |
Split system and single package |
10.0 EER 11.6 IEER before 1/1/2023 13.2 IEER after 1/1/2023 |
AHRI 340/360 | |
All other | 9.8 EER 11.4 IEER before 1/1/2023 13.0 IEER after 1/1/2023 |
||||
≥ 760,000 Btu/h | Electric resistance (or none) |
9.7 EER 11.2 IEER before 1/1/2023 12.5 IEERafter 1/1/2023 |
|||
All other | 9.5 EER 11.0 IEER before 1/1/2023 12.3 IEER after 1/1/2023 |
||||
Air conditioners, water cooled |
< 65,000 Btu/h | All | Split systemand single package |
12.1 EER 12.3 IEER |
AHRI 210/240 |
≥ 65,000 Btu/h and < 135,000 Btu/h |
Electric resistance (or none) |
12.1 EER 13.9 IEER |
AHRI 340/360 | ||
All other | 11.9 EER 13.7 IEER |
||||
≥ 135,000 Btu/h and < 240,000 Btu/h |
Electric resistance (or none) |
12.5 EER 13.9 IEER |
|||
All other | 12.3 EER 13.7 IEER |
||||
≥ 240,000 Btu/h and < 760,000 Btu/h |
Electric resistance (or none) |
12.4 EER 13.6 IEER |
|||
All other | 12.2 EER 13.4 IEER |
||||
≥ 760,000 Btu/h | Electric resistance (or none) |
12.2 EER 13.5 IEER |
|||
All other | 12.0 EER 13.3 IEER |
||||
Air conditioners, evaporatively cooled |
< 65,000 Btu/hb | All | Split system and single package | 12.1 EER 12.3 IEER |
AHRI 210/240 |
≥ 65,000 Btu/h and < 135,000 Btu/h |
Electric resistance (or none) |
12.1 EER 12.3 IEER |
AHRI 340/360 | ||
All other | 11.9 EER 12.1 IEER |
||||
≥ 135,000 Btu/h and < 240,000 Btu/h |
Electric resistance (or none) |
12.0 EER 12.2 IEER |
|||
All other | 11.8 EER 12.0 IEER |
||||
≥ 240,000 Btu/h and < 760,000 Btu/h |
Electric resistance (or none) |
11.9 EER 12.1 IEER |
|||
All other | 11.7 EER 11.9 IEER |
||||
≥ 760,000 Btu/h | Electric resistance (or none) |
11.7 EER 11.9 IEER |
|||
All other | 11.5 EER 11.7 IEER |
||||
Condensing units, air cooled | ≥ 135,000 Btu/h | — | — | 10.5 EER 11.8 IEER |
AHRI 365 |
Condensing units, water cooled | ≥ 135,000 Btu/h | — | — | 13.5 EER 14.0 IEER |
AHRI 365 |
Condensing units, evaporatively cooled |
≥ 135,000 Btu/h | — | — | 13.5 EER 14.0 IEER |
AHRI 365 |
For SI: 1 British thermal unit per hour = 0.2931 W.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- Single-phase, US air-cooled air conditioners less than 65,000 Btu/h are regulated as consumer products by the US Department of Energy Code of Federal Regulations DOE 10 CFR 430. SEER and SEER2 values for single-phase products are set by the US Department of Energy.
- DOE 10 CFR 430 Subpart B Appendix M1 includes the test procedure updates effective 1/1/2023 that will be incorporated in AHRI 210/240—2023.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-1 Electrically Operated Unitary Air Conditioners and Condensing Units—Minimum Efficiency Requirements.
ELECTRICALLY OPERATED AIR-COOLED UNITARY HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTSc, d
EQUIPMENT TYPE | SIZE CATEGORY | HEADING SECTION TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDUREa | |
Air cooled (cooling mode) | < 66,000 Btu/h | All | Split system, three phase and applications outside US single phaseb | 14.0 SEER before 1/1/2023 14.3 SEER2 after 1/1/2023 | AHRI 210/240—2017 before 1/1/2023 AHRI 210/240—2023 after 1/1/2023 |
|
Single package, three phase and applications outside US single phaseb | 14.0 SEER before 1/1/2023 13.4 SEER2 after 1/1/2023 | |||||
Space constrained, air cooled (cooling mode) | ≤ 30,000 Btu/h | All | Split system, three phase and applications outside US single phaseb | 12.0 SEER before 1/1/2023 11.7 SEER2 after 1/1/2023 | AHRI 210/240—2017 before 1/1/2023 AHRI 210/240—2023 after 1/1/2023 |
|
Single package, three phase and applications outside US single phaseb | 12.0 SEER before 1/1/2023 11.7 SEER2 after 1/1/2023 | |||||
Single duct, high velocity, air cooled (cooling mode) | < 65,000 | All | Split system, three phase and applications outside US single phaseb | 12.0 SEER before 1/1/2023 12.0 SEER2 after 1/1/2023 | AHRI 210/240—2017 before 1/1/2023 AHRI 210/240—2023 after 1/1/2023 |
|
Air cooled (cooling mode) | ≥ 65,000 Btu/h and < 135,000 Btu/h | Electric resistance (or none) | Split system and single package | 11.0 EER 12.2 IEER before 1/1/2023 14.1 IEER after 1/1/2023 | AHRI 340/360 | |
All other | 10.8 EER 12.0 IEER before 1/1/2023 13.9 IEER after 1/1/2023 | |||||
≥ 135,000 Btu/h and < 240,000 Btu/h | Electric resistance (or none) | 10.6 EER 11.6 IEER before 1/1/2023 13.5 IEER after 1/1/2023 | ||||
All other | 10.4 EER 11.4 IEER before 1/1/2023 13.3 IEER after 1/1/2023 | |||||
≥ 240,000 Btu/h | Electric resistance (or none) | 9.5 EER 10.6 IEER before 1/1/2023 12.5 IEER after 1/1/2023 | ||||
All other | 9.3 EER 10.4 IEER before 1/1/2023 12.3 IEER after 1/1/2023 | |||||
Air cooled (heating mode) | < 65,000 Btu/h | All | Split system, three phase and applications outside US single phaseb | 8.2 HSPF before 1/1/2023 7.5 HSPF2 after 1/1/2023 |
AHRI 210/240—2017 before 1/1/2023 AHRI 210/240—2023 after 1/1/2023 |
|
Single package, three phase and applications outside US single phaseb | 8.0 HSPF before 1/1/2023 6.7 HSPF2 after 1/1/2023 |
|||||
Space constrained, air cooled (heating mode) |
≤ 30,000 Btu/h | All | Split system, three phase and applications outside US single phaseb | 7.4 HSPF before 1/1/2023 6.3 HSPF2 after 1/1/2023 |
AHRI 210/240—2017 before 1/1/2023 AHRI 210/240—2023 after 1/1/2023 |
|
Single package, three phase and applications outside US single phaseb | 7.4 HSPF before 1/1/2023 6.3 HSPF2 after 1/1/2023 |
|||||
Small duct, high velocity, air cooled (heating mode) | < 65,000 Btu/h | All | Split system, three phase and applications outside US single phaseb | 7.2 HSPF before 1/1/2023 6.1 HSPF2 after 1/1/2023 |
AHRI 210/240—2017 before 1/1/2023 AHRI 210/240—2023 after 1/1/2023 |
|
Air cooled (heating mode) | ≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) |
All | 47°F db/43°F wb outdoor air |
3.30 COPH before 1/1/2023 3.40 COPH after 1/1/2023 |
AHRI 340/360 | |
17°F db/15°F wb outdoor air |
2.25 COPH |
|||||
≥ 135,000 Btu/h and < 240,000 Btu/h (cooling capacity) |
47°F db/43°F wb outdoor air |
3.20 COPH before 1/1/2023 3.30 SOPH after 1/1/2023 |
||||
17°F db/15°F wb outdoor air |
2.05 COPH | |||||
≥ 240,000 Btu/h (cooling capacity) | 47°F db/43°F wb outdoor air |
3.20 COPH | ||||
17°F db/15°F wb outdoor air |
2.05 COPH |
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) — 32]/1.8, wb = wet bulb, db = dry bulb.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- Single-phase, US air-cooled heat pumps less than 65,000 Btu/h are regulated as consumer products by the US Department of Energy Code of Federal Regulations DOE 10 CFR 430. SEER, SEER2 and HSPF values for single-phase products are set by the US Department of Energy.
- DOE 10 CFR 430 Subpart B Appendix M1 includes the test procedure updates effective 1/1/2023 that will be incorporated in AHRI 210/240—2023.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-2 Electrically Operated Air-Cooled Unitary Heat Pumps—Minimum Efficiency Requirements.
WATER-CHILLING PACKAGES—MINIMUM EFFICIENCY REQUIREMENTSa, b, e, f
EQUIPMENT TYPE |
SIZE CATEGORY | UNITS | PATH A | PATH B | TEST PROCEDUREc | ||
Air cooled chillers | < 150 tons | EER (Btu/Wh) | ≥ 10.100 FL | ≥ 9.700 FL | AHRI 550/590 | ||
≥ 13.700 IPLV.IP | ≥ 15.800 IPLV.IP | ||||||
≥ 150 tons | ≥ 10.100 FL | ≥ 9.700FL | |||||
≥ 14.000 IPLV.IP | ≥ 16.100 IPLV.IP | ||||||
Air cooled without condenser, electrically operated | All capacities | EER (Btu/Wh) | Air-cooled chillers without condenser must be rated with matching condensers and comply with air-cooled chiller efficiency requirements | AHRI 550/590 | |||
Water cooled, electrically operated positive displacement | < 75 tons | kW/ton | ≤ 0.750 FL | ≤ 0.780 FL | AHRI 550/590 | ||
≤ 0.600 IPLV.IP | ≤ 0.500 IPLV.IP | ||||||
≥ 75 tons and < 150 tons | ≤ 0.720 FL | ≤ 0.750 FL | |||||
≤ 0.560 IPLV.IP | ≤ 0.490 IPLV.IP | ||||||
≥ 150 tons and < 300 tons | ≤ 0.660 FL | ≤ 0.680 FL | |||||
≤ 0.540 IPLV.IP | ≤ 0.440 IPLV.IP | ||||||
≥ 300 tons and < 600 tons | ≤ 0.610 FL | ≤ 0.625 FL | |||||
≤ 0.520 IPLV.IP | ≤ 0.410 IPLV.IP | ||||||
≥ 600 tons | ≤ 0.560 FL | ≤ 0.585 FL | |||||
≤ 0.500 IPLV.IP | ≤ 0.380 IPLV.IP | ||||||
Water cooled, electrically operated centrifugal | < 150 tons | kW/ton | ≤ 0.610 FL | ≤ 0.695 FL | AHRI 550/590 | ||
≤ 0.550 IPLV.IP | ≤ 0.440 IPLV.IP | ||||||
≤ 0.610 FL | ≤ 0.635 FL | ||||||
≤ 0.550 IPLV.IP | ≤ 0.400 IPLV.IP | ||||||
≥ 300 tons and < 400 tons |
≤ 0.560 FL | ≤ 0.595 FL | |||||
≤ 0.520 IPLV.IP | ≤ 0.390 IPLV.IP | ||||||
≥ 400 tons and < 600 tons |
≤ 0.560 FL | ≤ 0.585 FL | |||||
≤ 0.500 IPLV.IP | ≤ 0.380 IPLV.IP | ||||||
≥ 600 tons | ≤ 0.560 FL | ≤ 0.585 FL | |||||
≤ 0.500 IPLV.IP | ≤ 0.380 IPLV.IP | ||||||
Air cooled absorption, single effect | All capacities | COP (W/W) | ≥ 0.600 FL | NAd | AHRI 560 | ||
Water cooled absorption, single effect | All capacities | COP (W/W) | ≥ 0.700 FL | NAd | AHRI 560 | ||
Absorption double effect, indirect fired | All capacities | COP (W/W) | ≥ 1.000 FL | NAd | AHRI 560 | ||
≥ 0.150 IPLV.IP | |||||||
Absorption double effect, direct fired | All capacities | COP (W/W) | ≥ 1.000 FL | NAd | AHRI 560 | ||
≥ 1.000 IPLV |
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- The requirements for centrifugal chillers shall be adjusted for nonstandard rating conditions per Section C403.3.2.1 and are applicable only for the range of conditions listed there. The requirements for air-cooled, water-cooled positive displacement and absorption chillers are at standard rating conditions defined in the reference test procedure.
- Both the full-load and IPLV.IP requirements must be met or exceeded to comply with this standard. When there is a Path B, compliance can be with either Path A or Path B for any application.
- NA means the requirements are not applicable for Path B, and only Path A can be used for compliance.
- FL is the full-load performance requirements, and IPLV.IP is for the part-load performance requirements.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-3 Water-Chilling Packages—Minimum Efficiency Requirements.
ELECTRICALLY OPERATED PACKAGED TERMINAL AIR CONDITIONERS, PACKAGED TERMINAL HEAT PUMPS, SINGLE-PACKAGE VERTICAL AIR CONDITIONERS, SINGLE-PACKAGE VERTICAL HEAT PUMPS, ROOM AIR CONDITIONERS AND ROOM AIR-CONDITIONER HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTSe
EQUIPMENT TYPE | SIZE CATEGORY (INPUT) | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCYd | TEST PROCEDUREa |
PTAC (cooling mode) standard size |
< 7,000 Btu/h | 95°F db/75°F wb outdoor airc |
11.9 EER | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h |
14.0 — (0.300 × Cap/1,000) EERd | |||
> 15,000 Btu/h | 9.5 EER | |||
PTAC (cooling mode) nonstandard sizea |
< 7,000 Btu/h | 95°F db/75°F wb outdoor airc |
9.4 EER | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h |
10.9 — (0.213 × Cap/1,000) EERd | |||
> 15,000 Btu/h | 7.7 EER | |||
PTHP (cooling mode) standard size |
< 7,000 Btu/h | 95°F db/75°F wb outdoor airc |
11.9 EER | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h |
14.0 — (0.300 × Cap/1,000) EERd | |||
> 15,000 Btu/h | 9.5 EER | |||
PTHP (cooling mode) nonstandard sizeb |
< 7,000 Btu/h | 95°F db/75°F wb outdoor airc |
9.3 EER | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h |
10.8 — (0.213 × Cap/1,000) EERd | |||
> 15,000 Btu/h | 7.6 EER | |||
PTHP (heating mode) standard size |
< 7,000 Btu/h | 47°F db/43°F wb outdoor air |
3.3 COPH | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h |
3.7 — (0.052 × Cap/1,000) COPHd | |||
> 15,000 Btu/h | 2.90 COPH | |||
PTHP (heating mode) nonstandard sizeb |
< 7,000 Btu/h | 47°F db/43°F wb outdoor air |
2.7 COPH | AHRI 310/380 |
≥ 7,000 Btu/h and ≤ 15,000 Btu/h |
2.9 — (0.026 × Cap/1000) COPHd | |||
> 15,000 Btu/h | 2.5 COPH | |||
SPVAC (cooling mode) single and three phase |
< 65,000 Btu/h | 95°F db/75°F wb outdoor airc |
11.0 EER | AHRI 390 |
≥ 65,000 Btu/h and ≤ 135,000 Btu/h |
10.0 EER | |||
≥ 135,000 Btu/h and ≤ 240,000 Btu/h |
10.0 EER | |||
SPVHP (cooling mode) | < 65,000 Btu/h | 95°F db/75°F wb outdoor airc |
11.0 EER | AHRI 390 |
≥ 65,000 Btu/h and ≤ 135,000 Btu/h |
10.0 EER | |||
≥ 135,000 Btu/h and ≤ 240,000 Btu/h |
10.1 EER | |||
SPVHP(heating mode) | < 65,000 Btu/h | 47°F db/43°F wb outdoor air |
3.3 COPH | AHRI 390 |
≥ 65,000 Btu/h and ≤ 135,000 Btu/h |
3.0 COPH | |||
≥ 135,000 Btu/h and ≤ 240,000 Btu/h |
3.0 COPH | |||
Room air conditioners without reverse cycle with louvered sides for applications outside US | < 6,000 Btu/h | — | 11.0 CEER | ANSI/AHAM RAC-1 |
≥ 6,000 Btu/h and < 8,000 Btu/h | — | 11.0 CEER | ||
≥ 8,000 Btu/h and < 14,000 Btu/h |
— | 10.9 CEER | ||
≥ 14,000 Btu/h and < 20,000 Btu/h |
— | 10.7 CEER | ||
≥ 20,000 Btu/h and < 28,000 Btu/h |
— | 9.4 CEER | ||
≥ 28,000 Btu/h | — | 9.0 CEER | ||
Room air conditioners without louvered sides | < 6,000 Btu/h | — | 10.0 CEER | ANSI/AHAM RAC-1 |
≥ 6,000 Btu/h and < 8,000 Btu/h | — | 10.0 CEER | ||
≥ 8,000 Btu/h and < 11,000 Btu/h |
— | 9.6 CEER | ||
≥ 11,000 Btu/h and < 14,000 Btu/h |
— | 9.5 CEER | ||
≥ 14,000 Btu/h and < 20,000 Btu/h |
— | 9.3 CEER | ||
≥ 20,000 Btu/h | — | 9.4 CEER | ||
Room air conditioners with reverse cycle, with louvered sides for applications outside US | < 20,000 Btu/h | 9.8 CEER | ANSI/AHAM RAC-1 | |
≥ 20,000 Btu/h | — | 9.3 CEER | ||
Room air conditioners with reverse cycle without louvered sides for applications outside US | < 14,000 Btu/h | — | 9.3 CEER | ANSI/AHAM RAC-1 |
≥ 14,000 Btu/h | — | 8.7 CEER | ||
Room air conditioners, casement only for applications outside US | All | — | 9.5 CEER | ANSI/AHAM RAC-1 |
Room air conditioners, casement slider for applications outside US | All | — | 10.4 CEER | ANSI/AHAM RAC-1 |
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) — 32]/1.8, wb = wet bulb, db = dry bulb.
"Cap" = The rated cooling capacity of the project in Btu/h. Where the unit's capacity is less than 7,000 Btu/h, use 7,000 Btu/h in the calculation. Where the unit's capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculations.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- Nonstandard size units must be factory labeled as follows: "MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW STANDARD PROJECTS." Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 inches (406 mm) high or less than 42 inches (1067 mm) wide and having a cross-sectional area less than 670 square inches (0.43 m2).
- The cooling-mode wet bulb temperature requirement only applies for units that reject condensate to the condenser coil.
- "Cap" in EER and COPH equations for PTACs and PTHPs means cooling capacity in Btu/h at 95°F outdoor dry-bulb temperature.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-4 Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air-Conditioner Heat Pumps—Minimum Efficiency Requirements.
WARM-AIR FURNACES AND COMBINATION WARM-AIR FURNACES/AIR-CONDITIONING UNITS, WARM-AIR DUCT FURNACES AND UNIT HEATERS—MINIMUM EFFICIENCY REQUIREMENTSg
EQUIPMENT TYPE | SIZE CATEGORY (INPUT) | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDUREa |
Warm-air furnace, gas fired for application outside the US | < 225,000 Btu/h | Maximum capacityc | 80% AFUE (nonweatherized) or 81% AFUE (weatherized) or 80% Etb, d |
DOE 10 CFR 430 Appendix N or Section 2.39, Thermal Efficiency, ANSI Z21.47 |
Warm-air furnace, gas fired | < 225,000 Btu/h | Maximum capacityc | 80% Etb, d before 1/1/2023 81% Etd after 1/1/2023 |
Section 2.39, Thermal Efficiency, ANSI Z21.47 |
Warm-air furnace, oil fired for application outside the US | < 225,000 Btu/h | Maximum capacityc | 83% AFUE (nonweatherized) or 78% AFUE (weatherized) or 80% Etb, d |
DOE 10 CFR 430 Appendix N or Section 42, Combustion, UL 727 |
Warm-air furnace, oil fired | < 225,000 Btu/h | Maximum capacityc | 80% Et before 1/1/2023 82% Etd after 1/1/2023 |
Section 42, Combustion, UL 727 |
Electric furnaces for applications outside the US | < 225,000 Btu/h | All | 96% AFUE | DOE 10 CFR 430 Appendix N |
Warm-air duct furnaces, gas fired | All capacities | Maximum capacityc | 80% Ece | Section 2.10, Efficiency, ANSI Z83.8 |
Warm-air unit heaters, gas fired | All capacities | Maximum capacityc | 80% Ece, f | Section 2.10, Efficiency, ANSI Z83.8 |
Warm-air unit heaters, oil fired | All capacities | Maximum capacityc | 80% Ece, f | Section 40, Combustion, UL 731 |
For SI: 1 British thermal unit per hour = 0.2931 W.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- Combination units (i.e., furnaces contained within the same cabinet as an air conditioner) not covered by DOE 10 CFR 430 (i.e., three-phase power or with cooling capacity greater than or equal to 65,000 Btu/h) may comply with either rating. All other units greater than 225,000 Btu/h sold in the US must meet the AFUE standards for consumer products and test using USDOE's AFUE test procedure at DOE 10 CFR 430, Subpart B, Appendix N.
- Compliance of multiple firing rate units shall be at the maximum firing rate.
- Et = thermal efficiency. Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75 percent of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space.
- Ec = combustion efficiency (100 percent less flue losses). See test procedure for detailed discussion.
- Units must also include an interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-5 Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct Furnaces, and Unit Heaters—Minimum Efficiency Requirements.
GAS- AND OIL-FIRED BOILERS—MINIMUM EFFICIENCY REQUIREMENTSi
EQUIPMENT TYPEb | SUBCATEGORY OR RATING CONDITION | SIZE CATEGORY (INPUT) | MINIMUM EFFICIENCY | EFFICIENCY AS OF 3/2/2022 |
TEST PROCEDUREa |
Boilers, hot water | Gas fired | < 300,000 Btu/hg, h for applications outside US |
82% AFUE | 82% AFUE | DOE 10 CFR 430 Appendix N |
≥ 300,000 Btu/h and ≤ 2,500,000 Btu/he |
80% Etd | 80% Etd | DOE 10 CFR 431.86 | ||
> 2,500,000 Btu/hb | 82% Ecc | 82% Ecc | |||
Oil firedf | < 300,000 Btu/hg,h for applications outside US |
84% AFUE | 84% AFUE | DOE 10 CFR 430 Appendix N | |
≥ 300,000 Btu/h and ≤ 2,500,000 Btu/he |
82% Etd | 82% Etd | DOE 10 CFR 431.86 | ||
> 2,500,000 Btu/hb | 84% Ecc | 84% Ecc | |||
Boilers, steam | Gas fired | < 300,000 Btu/hg for applications outside US |
80% AFUE | 80% AFUE | DOE 10 CFR 430 Appendix N |
Gas fired—all, except natural draft | ≥ 300,000 Btu/h and ≤ 2,500,000 Btu/he |
79% Etd | 79% Etd | DOE 10 CFR 431.86 | |
> 2,500,000 Btu/hb | 79% Etd | 79% Etd | |||
Gas fired—natural draft | ≥ 300,000 Btu/h and ≤ 2,500,000 Btu/he |
77% Etd | 79% Etd | ||
> 2,500,000 Btu/hb | 77% Etd | 79% Etd | |||
Oil firedf | < 300,000 Btu/hg for applications outside US |
82% AFUE | 82% AFUE | DOE 10 CFR 430 Appendix N | |
≥ 300,000 Btu/h and ≤ 2,500,000 Btu/he |
81% Etd | 81% Etd | DOE 10 CFR 431.86 | ||
> 2,500,000 Btu/hb | 81% Etd | 81% Etd |
For SI: 1 British thermal unit per hour = 0.2931 W.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- These requirements apply to boilers with rated input of 8,000,000 Btu/h or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers.
- Ec = Combustion efficiency (100 percent less flue losses).
- Et = Thermal efficiency.
- Maximum capacity—minimum and maximum ratings as provided for and allowed by the unit's controls.
- Includes oil-fired (residual).
- Boilers shall not be equipped with a constant burning pilot light.
- A boiler not equipped with a tankless domestic water-heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-6 Gas- and Oil-Fired Boilers—Minimum Efficiency Requirements.
PERFORMANCE REQUIREMENTS FOR HEAT REJECTION EQUIPMENT—MINIMUM EFFICIENCY REQUIREMENTSi
EQUIPMENT TYPE | TOTAL SYSTEM HEAT-REJECTION CAPACITY AT RATED CONDITIONS | SUBCATEGORY OR RATING CONDITIONh | PERFORMANCE REQUIREDb, c, d, f, g | TEST PROCEDUREa, e |
Propeller or axial fan open-circuit cooling towers | All | 95°F entering water 85°F leaving water 75°F entering wb |
≥ 40.2 gpm/hp | CTI ATC-105 and CTI STD-201 RS |
Centrifugal fan open-circuit cooling towers | All | 95°F entering water 85°F leaving water 75°F entering wb |
≥ 20.0 gpm/hp | CTI ATC-105 and CTI STD-201 RS |
Propeller or axial fan closed-circuit cooling towers | All | 102°F entering water 90°F leaving water 75°F entering wb |
≥ 16.1 gpm/hp | CTI ATC-105S and CTI STD-201 RS |
Centrifugal fan closed-circuit cooling towers | All | 102°F entering water 90°F leaving water 75°F entering wb |
≥ 7.0 gpm/hp | CTI ATC-105S and CTI STD-201 RS |
Propeller or axial fan dry coolers (air-cooled fluid coolers) | All | 115°F entering water 105°F leaving water 95°F entering wb |
≥ 4.5 gpm/hp | CTI ATC-105DS |
Propeller or axial fan evaporative condensers | All | R-448A test fluid 165°F entering gas temperature 105°F condensing temperature 75°F entering wb |
≥ 160,000 Btu/h × hp | CTI ATC-106 |
Propeller or axial fan evaporative condensers | All | Ammonia test fluid 140°F entering gas temperature 96.3°F condensing temperature 75°F entering wb |
≥ 134,000 Btu/h × hp | CTI ATC-106 |
Centrifugal fan evaporative condensers | All | R-448A test fluid 165°F entering gas temperature 105°F condensing temperature 75°F entering wb |
≥ 137,000 Btu/h × hp | CTI ATC-106 |
Centrifugal fan evaporative condensers | All | Ammonia test fluid 140°F entering gas temperature 96.3°F condensing temperature 75°F entering wb |
≥ 110,000 Btu/h × hp | CTI ATC-106 |
Air-cooled condensers | All | 125°F condensing temperature 190°F entering gas temperature 15°F subcooling 95°F entering db |
≥ 176,000 Btu/h × hp | AHRI 460 |
For SI: °C = [(°F) — 32]/1.8, L/s × kW = (gpm/hp)/(11.83), COP = (Btu/h × hp)/(2550.7), db = dry bulb temperature, wb = wet bulb temperature.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- For purposes of this table, open-circuit cooling tower performance is defined as the water-flow rating of the tower at the thermal rating condition listed in the table divided by the fan motor nameplate power.
- For purposes of this table, closed-circuit cooling tower performance is defined as the process water-flow rating of the tower at the thermal rating condition listed in the table divided by the sum of the fan motor nameplate power and the integral spray pump motor nameplate power.
- For purposes of this table, dry-cooler performance is defined as the process water-flow rating of the unit at the thermal rating condition listed in the table divided by the total fan motor nameplate power of the unit, and air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the total fan motor nameplate power of the unit.
- The efficiencies and test procedures for both open- and closed-circuit cooling towers are not applicable to hybrid cooling towers that contain a combination of separate wet and dry heat exchange sections. The certification requirements do not apply to field-erected cooling towers.
- All cooling towers shall comply with the minimum efficiency listed in the table for that specific type of tower with the capacity effect of any project-specific accessories and/or options included in the capacity of the cooling tower.
- For purposes of this table, evaporative condenser performance is defined as the heat rejected at the specified rating condition in the table, divided by the sum of the fan motor nameplate power and the integral spray pump nameplate power.
- Requirements for evaporative condensers are listed with ammonia (R-717) and R-448A as test fluids in the table. Evaporative condensers intended for use with halocarbon refrigerants other than R-448A must meet the minimum efficiency requirements listed with R-448A as the test fluid. For ammonia, the condensing temperature is defined as the saturation temperature corresponding to the refrigerant pressure at the condenser entrance. For R-448A, which is a zeotropic refrigerant, the condensing temperature is defined as the arithmetic average of the dew point and the bubble point temperatures corresponding to the refrigerant pressure at the condenser entrance.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-7 Performance Requirements for Heat Rejection Equipment—Minimum Efficiency Requirements.
ELECTRICALLY OPERATED VARIABLE-REFRIGERANT-FLOW AIR CONDITIONERS—MINIMUM EFFICIENCY REQUIREMENTSb
EQUIPMENT TYPE | SIZE CATEGORY | HEATING SECTION TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDUREa |
VRFair conditioners, air cooled | < 65,000 Btu/h | All | VRF multisplit system |
13.0 SEER | AHRI 1230 |
≥ 65,000 Btu/h and < 135,000 Btu/h |
Electric resistance (or none) |
VRF multisplit system |
11.2 EER 13.1 IEER 15.5 IEER |
||
≥ 135,000 Btu/h and < 240,000 Btu/h |
Electric resistance (or none) |
VRF multisplit system |
11.0 EER 12.9 IEER 14.9 IEER |
||
≥ 240,000 Btu/h | Electric resistance (or none) |
VRF multisplit system |
10.0 EER 11.6 IEER 13.9 IEER |
For SI: 1 British thermal unit per hour = 0.2931 W.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-8 Electrically Operated Variable-Refrigerant-Flow Air Conditioners—Minimum Efficiency Requirements.
ELECTRICALLY OPERATED VARIABLE-REFRIGERANT-FLOW AND APPLIED HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTSb
EQUIPMENT TYPE | SIZE CATEGORY | HEATING SECTION TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDUREa |
VRFair cooled (cooling mode) | < 65,000 Btu/h | All | VRF multisplit system | 13.0 SEER | AHRI 1230 |
≥ 65,000 Btu/h and < 135,000 Btu/h |
Electric resistance (or none) |
11.0 EER 12.9 IEER 14.6 IEER |
|||
VRF multisplit system with heat recovery |
10.8 EER 12.7 IEER 14.4 IEER |
||||
≥ 135,000 Btu/h and < 240,000 Btu/h |
VRF multisplit system | 10.6 EER 12.3 IEER 13.9 IEER |
|||
VRF multisplit system with heat recovery |
10.4 EER 12.1 IEER 13.7 IEER |
||||
≥ 240,000 Btu/h | VRF multisplit system | 9.5 EER 11.0 IEER 12.7 IEER |
|||
VRF multisplit system with heat recovery |
9.3 EER 10.8 IEER 12.5 IEER |
||||
VRF water source (cooling mode) | < 65,000 Btu/h | All | VRF multisplit systems 86°F entering water |
12.0 EER 16.0 IEER |
AHRI 1230 |
VRF multisplit systems with heat recovery 86°F entering water |
11.8 EER 15.8 IEER |
||||
≥ 65,000 Btu/h and < 135,000 Btu/h |
VRF multisplit system 86°F entering water |
12.0 EER 16.0 IEER |
|||
VRF multisplit system with heat recovery 86°F entering water |
11.8 EER 15.8 IEER |
||||
≥ 135,000 Btu/h and < 240,000 Btu/h |
VRF multisplit system 86°F entering water |
10.0 EER 14.0 IEER |
|||
VRF multisplit system with heat recovery 86°F entering water |
9.8 EER 13.8 IEER |
||||
≥ 240,000 Btu/h | VRF multisplit system 86°F entering water |
10.0 EER 12.0 IEER |
|||
VRF multisplit system with heat recovery 86°F entering water |
9.8 EER 11.8 IEER |
||||
VRFgroundwater source (cooling mode) | < 135,000 Btu/h | All | VRF multisplit system 59°F entering water |
16.2 EER | AHRI 1230 |
VRF multisplit system with heat recovery 59°F entering water |
16.0 EER | ||||
≥ 135,000 Btu/h | VRF multisplit system 59°F entering water |
13.8 EER | |||
VRF multisplit system with heat recovery 59°F entering water |
13.6 EER | ||||
VRFground source (cooling mode) | < 135,000 Btu/h | All | VRF multisplit system 77°F entering water |
13.4 EER | AHRI 1230 |
VRF multisplit system with heat recovery 77°F entering water |
13.2 EER | ||||
≥ 135,000 Btu/h | VRF multisplit system 77°F entering water |
11.0 EER | |||
VRF multisplit system with heat recovery 77°F entering water |
10.8 EER | ||||
VRFair cooled (heating mode) | < 65,000 Btu/h (cooling capacity) |
VRF multisplit system | 7.7 HSPF | AHRI 1230 | |
≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) |
VRF multisplit system 47°F db/43°F wb outdoor air |
3.3 COPH | |||
17°F db/15°F wb outdoor air |
2.25 COPH | ||||
≥ 135,000 Btu/h (cooling capacity) |
VRF multisplit system 47°F db/43°F wb outdoor air |
3.2 COPH | |||
17°F db/15°F wb outdoor air |
2.05 COPH | ||||
VRFwater source (heating mode) | < 65,000 Btu/h (cooling capacity) |
VRF multisplit system 68°F entering water |
4.2 COPH 4.3 COPH |
AHRI 1230 | |
≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) |
VRF multisplit system 68°F entering water |
4.2 COPH 4.3 COPH |
|||
≥ 135,000 Btu/h and < 240,000 Btu/h (cooling capacity) |
VRF multisplit system 68°F entering water |
3.9 COPH 4.0 COPH |
|||
≥ 240,000 Btu/h (cooling capacity) |
VRF multisplit system 68°F entering water |
3.9 COPH | |||
VRF groundwater source (heating mode) | < 135,000 Btu/h (cooling capacity) |
VRF multisplit system 50°F entering water |
3.6 COPH | AHRI 1230 | |
≥ 135,000 Btu/h (cooling capacity) |
VRF multisplit system 50°F entering water |
3.3 COPH | |||
VRF ground source (heating mode) | < 135,000 Btu/h (cooling capacity) |
VRF multisplit system 32°F entering water |
3.1 COPH | AHRI 1230 | |
≥ 135,000 Btu/h (cooling capacity) |
VRF multisplit system 32°F entering water |
2.8 COPH |
For SI: °C = [(°F) — 32]/1.8, 1 British thermal unit per hour = 0.2931 W, db = dry bulb temperature, wb = wet bulb temperature.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-9 Electrically Operated Variable-Refrigerant-Flow and Applied Heat Pumps—Minimum Efficiency Requirements.
FLOOR-MOUNTED AIR CONDITIONERS AND CONDENSING UNITS SERVING COMPUTER ROOMS—MINIMUM EFFICIENCY REQUIREMENTSb
EQUIPMENT TYPE | STANDARD MODEL | NET SENSIBLE COOLING CAPACITY | MINIMUM NET SENSIBLE COP | RATING CONDITIONS RETURN AIR (dry bulb/dew point) |
TEST PROCEDUREa |
Air cooled | Downflow | < 80,000 Btu/h | 2.70 | 85°F/52°F (Class 2) | AHRI 1360 |
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.58 | ||||
≥ 295,000 Btu/h | 2.36 | ||||
Upflow—ducted | < 80,000 Btu/h | 2.67 | |||
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.55 | ||||
≥ 295,000 Btu/h | 2.33 | ||||
Upflow—nonducted | < 65,000 Btu/h | 2.16 | 75°F/52°F (Class 1) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
2.04 | ||||
≥ 240,000 Btu/h | 1.89 | ||||
Horizontal | < 65,000 Btu/h | 2.65 | 95°F/52°F (Class 3) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
2.55 | ||||
≥ 240,000 Btu/h | 2.47 | ||||
Air cooled with fluid economizer | Downflow | < 80,000 Btu/h | 2.70 | 85°F/52°F (Class 1) | AHRI 1360 |
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.58 | ||||
≥ 295,000 Btu/h | 2.36 | ||||
Upflow—ducted | < 80,000 Btu/h | 2.67 | |||
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.55 | ||||
≥ 295,000 Btu/h | 2.33 | ||||
Upflow—nonducted | < 65,000 Btu/h | 2.09 | 75°F/52°F (Class 1) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
1.99 | ||||
≥ 240,000 Btu/h | 1.81 | ||||
Horizontal | < 65,000 Btu/h | 2.65 | 95°F/52°F (Class 3) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
2.55 | ||||
≥ 240,000 Btu/h | 2.47 | ||||
Water cooled | Downflow | < 80,000 Btu/h | 2.82 | 85°F/52°F (Class 1) | AHRI 1360 |
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.73 | ||||
≥ 295,000 Btu/h | 2.67 | ||||
Upflow—ducted | < 80,000 Btu/h | 2.79 | |||
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.70 | ||||
≥ 295,000 Btu/h | 2.64 | ||||
Upflow—nonducted | < 65,000 Btu/h | 2.43 | 75°F/52°F (Class 1) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
2.32 | ||||
≥ 240,000 Btu/h | 2.20 | ||||
Horizontal | < 65,000 Btu/h | 2.79 | 95°F/52°F (Class 3) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
2.68 | ||||
≥ 240,000 Btu/h | 2.60 | ||||
Water cooled with fluid economizer | Downflow | < 80,000 Btu/h | 2.77 | 85°F/52°F (Class 1) | AHRI 1360 |
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.68 | ||||
≥ 295,000 Btu/h | 2.61 | ||||
Upflow—ducted | < 80,000 Btu/h | 2.74 | |||
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.65 | ||||
≥ 295,000 Btu/h | 2.58 | ||||
Upflow—nonducted | < 65,000 Btu/h | 2.35 | 75°F/52°F (Class 1) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
2.24 | ||||
≥ 240,000 Btu/h | 2.12 | ||||
Horizontal | < 65,000 Btu/h | 2.71 | 95°F/52°F (Class 3) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
2.60 | ||||
≥ 240,000 Btu/h | 2.54 | ||||
Glycol cooled | Downflow | < 80,000 Btu/h | 2.56 | 85°F/52°F (Class 1) | AHRI 1360 |
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.24 | ||||
≥ 295,000 Btu/h | 2.21 | ||||
Upflow—ducted | < 80,000 Btu/h | 2.53 | |||
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.21 | ||||
≥ 295,000 Btu/h | 2.18 | ||||
Upflow, nonducted |
< 65,000 Btu/h | 2.08 | 75°F/52°F (Class 1) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
1.90 | ||||
≥ 240,000 Btu/h | 1.81 | ||||
Horizontal | < 65,000 Btu/h | 2.48 | 95°F/52°F (Class 3) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
2.18 | ||||
≥ 240,000 Btu/h | 2.18 | ||||
Glycol cooled with fluid economizer | Downflow | < 80,000 Btu/h | 2.51 | 85°F/52°F (Class 1) | AHRI 1360 |
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.19 | ||||
≥ 295,000 Btu/h | 2.15 | ||||
Upflow—ducted | < 80,000 Btu/h | 2.48 | |||
≥ 80,000 Btu/h and < 295,000 Btu/h |
2.16 | ||||
≥ 295,000 Btu/h | 2.12 | ||||
Upflow—nonducted | < 65,000 Btu/h | 2.00 | 75°F/52°F (Class 1) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
1.82 | ||||
≥ 240,000 Btu/h | 1.73 | ||||
Horizontal | < 65,000 Btu/h | 2.44 | 95°F/52°F (Class 3) | ||
≥ 65,000 Btu/h and < 240,000 Btu/h |
2.10 | ||||
≥ 240,000 Btu/h | 2.10 |
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) — 32]/1.8, COP = (Btu/h × hp)/(2,550.7).
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-10 Floor-Mounted Air Conditioners and Condensing Units Serving Computer Rooms—Minimum Efficiency Requirements.
VAPOR-COMPRESSION-BASED INDOOR POOL DEHUMIDIFIERS—MINIMUM EFFICIENCY REQUIREMENTSb
EQUIPMENT TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDUREa |
Single package indoor (with or without economizer) | Rating Conditions: A or C | 3.5 MRE | AHRI 910 |
Single package indoor water cooled (with or without economizer) | Rating Conditions: A, B or C | 3.5 MRE | |
Single package indoor air cooled (with or without economizer) | Rating Conditions: A, B or C | 3.5 MRE | |
Split systemindoor air cooled (with or without economizer) | Rating Conditions: A, B or C | 3.5 MRE |
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-12 Vapor-Compression-Based Indoor Pool Dehumidifiers—Minimum Efficiency Requirements.
ELECTRICALLY OPERATED DX-DOAS UNITS, SINGLE-PACKAGE AND REMOTE CONDENSER, WITHOUT ENERGY RECOVERY—MINIMUM EFFICIENCY REQUIREMENTSb
EQUIPMENT TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDUREa |
Air cooled (dehumidification mode) | — | 4.0 ISMRE | AHRI 920 |
Air-source heat pumps (dehumidification mode) | — | 4.0 ISMRE | AHRI 920 |
Water cooled (dehumidification mode) | Cooling tower condenser water | 4.9 ISMRE | AHRI 920 |
Chilled water | 6.0 ISMRE | ||
Air-source heat pump (heating mode) | — | 2.7 ISCOP | AHRI 920 |
Water-source heat pump (dehumidification mode) | Ground source, closed loop | 4.8 ISMRE | AHRI 920 |
Ground-water source | 5.0 ISMRE | ||
Water source | 4.0 ISMRE | ||
Water-source heat pump (heating mode) | Ground source, closed loop | 2.0 ISCOP | AHRI 920 |
Ground-water source | 3.2 ISCOP | ||
Water source | 3.5 ISCOP |
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-13 Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, without Energy Recovery—Minimum Efficiency Requirements.
ELECTRICALLY OPERATED DX-DOAS UNITS, SINGLE-PACKAGE AND REMOTE CONDENSER,
WITH ENERGY RECOVERY—MINIMUM EFFICIENCY REQUIREMENTSb
WITH ENERGY RECOVERY—MINIMUM EFFICIENCY REQUIREMENTSb
EQUIPMENT TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDUREa |
Air cooled (dehumidification mode) | — | 5.2 ISMRE | AHRI 920 |
Air-source heat pumps (dehumidification mode) | — | 5.2 ISMRE | AHRI 920 |
Water cooled (dehumidification mode) | Cooling tower condenser water | 5.3 ISMRE | AHRI 920 |
Chilled water | 6.6 ISMRE | ||
Air-source heat pump (heating mode) | — | 3.3 ISCOP | AHRI 920 |
Water-source heat pump (dehumidification mode) | Ground source, closed loop | 5.2 ISMRE | AHRI 920 |
Ground-water source | 5.8 ISMRE | ||
Water source | 4.8 ISMRE | ||
Water-source heat pump (heating mode) | Ground source, closed loop | 3.8 ISCOP | AHRI 920 |
Ground-water source | 4.0 ISCOP | ||
Water source | 4.8 ISCOP |
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-14 Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, with Energy Recovery—Minimum Efficiency Requirements.
ELECTRICALLY OPERATED WATER-SOURCE HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTSc
EQUIPMENT TYPE | SIZE CATEGORYb | HEATING SECTION TYPE | SUBCATEGORY OR RATING CONDITION | MINIMUM EFFICIENCY | TEST PROCEDUREa |
Water-to-air, water loop (cooling mode) | < 17,000 Btu/h | All | 86°F entering water | 12.2 EER | ISO 13256-1 |
≥ 17,000 Btu/h and < 65,000 Btu/h |
13.0 EER | ||||
≥ 65,000 Btu/h and < 135,000 Btu/h |
13.0 EER | ||||
Water-to-air, ground water (cooling mode) | < 135,000 Btu/h | All | 59°F entering water | 18.0 EER | ISO 13256-1 |
Brine-to-air, ground loop (cooling mode) | < 135,000 Btu/h | All | 77°F entering water | 14.1 EER | ISO 13256-1 |
Water-to-water, water loop (cooling mode) | < 135,000 Btu/h | All | 86°F entering water | 10.6 EER | ISO 13256-2 |
Water-to-water, ground water (cooling mode) | < 135,000 Btu/h | All | 59°F entering water | 16.3 EER | ISO 13256-2 |
Brine-to-water, ground loop (cooling mode) | < 135,000 Btu/h | All | 77°F entering water | 12.1 EER | ISO 13256-2 |
Water-to-water, water loop (heating mode) | < 135,000 Btu/h (cooling capacity) |
— | 68°F entering water | 4.3 COPH | ISO 13256-1 |
Water-to-air, ground water (heating mode) | < 135,000 Btu/h (cooling capacity) |
— | 50°F entering water | 3.7 COPH | ISO 13256-1 |
Brine-to-air, ground loop (heating mode) | < 135,000 Btu/h (cooling capacity) |
— | 32°F entering water | 3.2 COPH | ISO 13256-1 |
Water-to-water, water loop (heating mode) | < 135,000 Btu/h (cooling capacity) |
— | 68°F entering water | 3.7 COPH | ISO 13256-1 |
Water-to-water, ground water (heating mode) | < 135,000 Btu/h (cooling capacity) |
— | 50°F entering water | 3.1 COPH | ISO 13256-2 |
Brine-to-water, ground loop (heating mode) | < 135,000 Btu/h (cooling capacity) |
— | 32°F entering water | 2.5 COPH | ISO 13256-2 |
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) — 32]/1.8.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- Single-phase, US air-cooled heat pumps less than 19 kW are regulated as consumer products by DOE 10 CFR 430. SCOPC, SCOP2C, SCOPH and SCOP2H values for single-phase products are set by the USDOE.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-15 Electrically Operated Water-Source Heat Pumps—Minimum Efficiency Requirements.
HEAT-PUMP AND HEAT RECOVERY CHILLER PACKAGES—MINIMUM EFFICIENCY REQUIREMENTSg
HEATING OPERATION | |||||||||||||||||||||
EQUIPMENT TYPE | SIZE CATEGORY, tonR | COOLING-ONLY OPERATION COOLING EFFICIENCYc AIR-SOURCE EER (FL/IPLV), Btu/W × h WATER-SOURCE POWER INPUT PER CAPACITY (FL/IPLV), kW/tonR |
HEATING SOURCE CONDITIONS (entering/ leaving water) OR OAT (db/wb), °F |
HEAT-PUMP HEATING FULL-LOAD EFFICIENCY (COPH)b, W/W |
HEAT RECOVERY CHILLER FULL-LOAD EFFICIENCY (COPHR)c,d, W/W SIMULTANEOUS COOLING AND HEATING FULL-LOAD EFFICIENCY (COPSHC)c, W/W |
Test Procedurea |
|||||||||||||||
Leaving Heating Water Temperature | Leaving Heating Water Temperature | ||||||||||||||||||||
Low | Medium | High | Boost | Low | Medium | High | Boost | ||||||||||||||
Path A | Path B | 105°F | 120°F | 140°F | 140°F | 105°F | 120°F | 140°F | 140°F | ||||||||||||
Air source | All sizes | ≥ 9.595 FL ≥ 13.02 IPLV.IP |
≥ 9.215 FL ≥ 15.01 IPLV.IP |
47 db 43 wbe |
≥ 3.290 | ≥ 2.770 | ≥ 2.310 | NA | NA | NA | NA | NA | AHRI 550/590 | ||||||||
≥ 9.595 FL ≥ 13.30 IPLV.IP |
≥ 9.215 FL ≥ 15.30 IPLV.IP |
17 db 15 wbe |
≥ 2.230 | ≥ 1.950 | ≥ 1.630 | NA | NA | NA | NA | NA | |||||||||||
Water-source electrically operated positive displacement |
< 75 | ≤ 0.7885 FL ≤ 0.6316 IPLV.IP |
≤ 0.7875 FL ≤ 0.5145 IPLV.IP |
54/44f | ≥ 4.640 | ≥ 3.680 | ≥ 2.680 | NA | ≥ 8.330 | ≥ 6.410 | ≥ 4.420 | NA | AHRI 550/590 | ||||||||
75/65f | NA | NA | NA | ≥ 3.550 | NA | NA | NA | 6.150 | |||||||||||||
≥ 75 and < 150 |
≤ 0.7579 FL ≤ 0.5895 IPLV.IP |
≤ 0.7140 FL ≤ 0.4620 IPLV.IP |
54/44f | ≥ 4.640 | ≥ 3.680 | ≥ 2.680 | NA | ≥ 8.330 | ≥ 6.410 | ≥ 4.420 | NA | ||||||||||
75/65f | NA | NA | NA | ≥ 3.550 | NA | NA | NA | 6.150 | |||||||||||||
≥ 150 and < 300 |
≤ 0.6947 FL ≤ 0.5684 IPLV.IP |
≤ 0.7140 FL ≤ 0.4620 IPLV.IP |
54/44f | ≥ 4.640 | ≥ 3.680 | ≥ 2.680 | NA | ≥ 8.330 | ≥ 6.410 | ≥ 4.420 | NA | ||||||||||
75/65f | NA | NA | NA | ≥ 3.550 | NA | NA | NA | 6.150 | |||||||||||||
≥ 300 and < 600 |
≤ 0.6421 FL ≤ 0.5474 IPLV.IP |
≤ 0.6563 FL ≤ 0.4305 IPLV.IP |
54/44f | ≥ 4.930 | ≥ 3.960 | ≥ 2.970 | NA | ≥ 8.900 | ≥ 6.980 | ≥ 5.000 | NA | ||||||||||
75/65f | NA | NA | NA | ≥ 3.900 | NA | NA | NA | 6.850 | |||||||||||||
≥ 600 | ≤ 0.5895 FL ≤ 0.5263 IPLV.IP |
≤ 0.6143 FL ≤ 0.3990 IPLV.IP |
54/44f | ≥ 4.930 | ≥ 3.960 | ≥ 2.970 | NA | ≥ 8.900 | ≥ 6.980 | ≥ 5.000 | NA | ||||||||||
75/65f | NA | NA | NA | ≥ 3.900 | NA | NA | NA | 6.850 | |||||||||||||
Water-source electrically operated centrifugal | < 75 | ≤ 0.6421 FL ≤ 0.5789 IPLV.IP |
≤ 0.7316 FL ≤ 0.4632 IPLV.IP |
54/44f | ≥ 4.640 | ≥ 3.680 | ≥ 2.680 | NA | ≥ 8.330 | ≥ 6.410 | ≥ 4.420 | NA | AHRI 550/590 | ||||||||
75/65f | NA | NA | NA | ≥ 3.550 | NA | NA | NA | ≥ 6.150 | |||||||||||||
≥ 75 and < 150 |
≤ 0.5895 FL ≤ 0.5474 IPLV.IP |
≤ 0.6684 FL ≤ 0.4211 IPLV.IP |
54/44f | ≥ 4.640 | ≥ 3.680 | ≥ 2.680 | NA | ≥ 8.330 | ≥ 6.410 | ≥ 4.420 | NA | ||||||||||
75/65f | NA | NA | NA | ≥ 3.550 | NA | NA | NA | ≥ 6.150 | |||||||||||||
≥ 150 and < 300 |
≤ 0.5895 FL ≤ 0.5263 IPLV.IP |
≤ 0.6263 FL ≤ 0.4105 IPLV.IP |
54/44f | ≥ 4.640 | ≥ 3.680 | ≥ 2.680 | NA | ≥ 8.330 | ≥ 6.410 | ≥ 4.420 | NA | ||||||||||
75/65f | NA | NA | NA | ≥ 3.550 | NA | NA | NA | ≥ 6.150 | |||||||||||||
≥ 300 and < 600 |
≤ 0.5895 FL ≤ 0.5263 IPLV.IP |
≤ 0.6158 FL ≤ 0.4000 IPLV.IP |
54/44f | ≥ 4.930 | ≥ 3.960 | ≥ 2.970 | NA | ≥ 8.900 | ≥ 6.980 | ≥ 5.000 | NA | ||||||||||
75/65f | NA | NA | NA | ≥ 3.900 | NA | NA | NA | ≥ 6.850 | |||||||||||||
≥ 600 | ≤ 0.5895 FL ≤ 0.5263 IPLV.IP |
≤ 0.6158 FL ≤ 0.4000 IPLV.IP |
54/44f | ≥ 4.930 | ≥ 3.960 | ≥ 2.970 | NA | ≥ 8.900 | ≥ 6.980 | ≥ 5.000 | NA | ||||||||||
75/65f | NA | NA | NA | ≥ 3.900 | NA | NA | NA | ≥ 6.850 |
For SI: °C = [(°F) — 32]/1.8.
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- Cooling-only rating conditions are standard rating conditions defined in AHRI 550/590, Table 1.
- Heating full-load rating conditions are at rating conditions defined in AHRI 550/590, Table 1.
- For water-cooled heat recovery chillers that have capabilities for heat rejection to a heat recovery condenser and a tower condenser, the COPHR applies to operation at full load with 100 percent heat recovery (no tower rejection). Units that only have capabilities for partial heat recovery shall meet the requirements of Table C403.3.2(3).
- Outdoor air entering dry-bulb (db) temperature and wet-bulb (wb) temperature.
- Source-water entering and leaving water temperature.
- This table is a replica of ASHRAE 90.1 Table 6.8.1-16 Heat-Pump and Heat Recovery Chiller Packages—Minimum Efficiency Requirements.
CEILING-MOUNTED COMPUTER-ROOM AIR CONDITIONERS—MINIMUM EFFICIENCY REQUIREMENTSb
EQUIPMENT TYPE | STANDARD MODEL | NET SENSIBLE COOLING CAPACITY | MINIMUM NET SENSIBLE COP | RATING CONDITIONS RETURN AIR (dry bulb/dew point) |
TEST PROCEDUREa |
Air cooled with free air discharge condenser | Ducted | < 29,000 Btu/h | 2.05 | 75°F/52°F (Class 1) | AHRI 1360 |
≥ 29,000 Btu/h and < 65,000 Btu/h |
2.02 | ||||
≥ 65,000 Btu/h | 1.92 | ||||
Nonducted | < 29,000 Btu/h | 2.08 | |||
≥ 29,000 Btu/h and < 65,000 Btu/h |
2.05 | ||||
≥ 65,000 Btu/h | 1.94 | ||||
Air cooled with free air discharge condenser with fluid economizer | Ducted | < 29,000 Btu/h | 2.01 | 75°F/52°F (Class 1) | AHRI 1360 |
≥ 29,000 Btu/h and < 65,000 Btu/h |
1.97 | ||||
≥ 65,000 Btu/h | 1.87 | ||||
Nonducted | < 29,000 Btu/h | 2.04 | |||
≥ 29,000 Btu/h and < 65,000 Btu/h |
2.00 | ||||
≥ 65,000 Btu/h | 1.89 | ||||
Air cooled with ducted condenser | Ducted | < 29,000 Btu/h | 1.86 | 75°F/52°F (Class 1) | AHRI 1360 |
≥ 29,000 Btu/h and < 65,000 Btu/h |
1.83 | ||||
≥ 65,000 Btu/h | 1.73 | ||||
Nonducted | < 29,000 Btu/h | 1.89 | |||
≥ 29,000 Btu/h and < 65,000 Btu/h |
1.86 | ||||
≥ 65,000 Btu/h | 1.75 | ||||
Air cooled with fluid economizer and ducted condenser | Ducted | < 29,000 Btu/h | 1.82 | 75°F/52°F (Class 1) | AHRI 1360 |
≥ 29,000 Btu/h and < 65,000 Btu/h |
1.78 | ||||
≥ 65,000 Btu/h | 1.68 | ||||
Nonducted | < 29,000 Btu/h | 1.85 | |||
≥ 29,000 Btu/h and < 65,000 Btu/h |
1.81 | ||||
≥ 65,000 Btu/h | 1.70 | ||||
Water cooled | Ducted | < 29,000 Btu/h | 2.38 | 75°F/52°F (Class 1) | AHRI 1360 |
≥ 29,000 Btu/h and < 65,000 Btu/h |
2.28 | ||||
≥ 65,000 Btu/h | 2.18 | ||||
Nonducted | < 29,000 Btu/h | 2.41 | |||
≥ 29,000 Btu/h and < 65,000 Btu/h |
2.31 | ||||
≥ 65,000 Btu/h | 2.20 | ||||
Water cooled with fluid economizer | Ducted | < 29,000 Btu/h | 2.33 | 75°F/52°F (Class 1) | AHRI 1360 |
≥ 29,000 Btu/h and < 65,000 Btu/h |
2.23 | ||||
≥ 65,000 Btu/h | 2.13 | ||||
Nonducted | < 29,000 Btu/h | 2.36 | |||
≥ 29,000 Btu/h and < 65,000 Btu/h |
2.26 | ||||
≥ 65,000 Btu/h | 2.16 | ||||
Glycol cooled | Ducted | < 29,000 Btu/h | 1.97 | 75°F/52°F (Class 1) | AHRI 1360 |
≥ 29,000 Btu/h and < 65,000 Btu/h |
1.93 | ||||
≥ 65,000 Btu/h | 1.78 | ||||
Nonducted | < 29,000 Btu/h | 2.00 | |||
≥ 29,000 Btu/h and < 65,000 Btu/h |
1.98 | ||||
≥ 65,000 Btu/h | 1.81 | ||||
Glycol cooled with fluid economizer | Ducted | < 29,000 Btu/h | 1.92 | 75°F/52°F (Class 1) | AHRI 1360 |
≥ 29,000 Btu/h and < 65,000 Btu/h |
1.88 | ||||
≥ 65,000 Btu/h | 1.73 | ||||
Nonducted | < 29,000 Btu/h | 1.95 | |||
≥ 29,000 Btu/h and < 65,000 Btu/h |
1.93 | ||||
≥ 65,000 Btu/h | 1.76 |
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) — 32]/1.8, COP = (Btu/h × hp)/(2,550.7).
- Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.
- This is a replica of ASHRAE 90.1 Table 6.8.1-17 Ceiling-Mounted Computer-Room Air Conditioners—Minimum Efficiency Requirements.
Related Code Sections
C403.2.3 [CE] Commercial Energy Efficiency, HVAC Equipment Performance Requirements
Where multiple rating conditions or performance requirements are provided, the equipment shall satisfy all stated requirements. Where components ...
Energy Conservation Code 2015 of Colorado > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.2 Provisions Applicable to All Mechanical Systems (Mandatory) > C403.2.3 HVAC Equipment Performance Requirements
C403.3.2 [CE] Commercial Energy Efficiency, HVAC Equipment Performance Requirements
shall be supported by data furnished by the manufacturer. Where multiple rating conditions or performance requirements are provided, the equipment ...
Energy Conservation Code 2021 of Colorado > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.3 Heating and Cooling Equipment Efficiencies > C403.3.2 HVAC Equipment Performance Requirements
C403.3.2 [CE] Commercial Energy Efficiency, HVAC Equipment Performance Requirements (Mandatory)
ratings shall be supported by data furnished by the manufacturer. Where multiple rating conditions or performance requirements are provided, the equipment ...
Energy Conservation Code 2018 of Colorado > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.3 Heating and Cooling Equipment Efficiencies (Mandatory) > C403.3.2 HVAC Equipment Performance Requirements (Mandatory)
C403.2.3.1 [CE] Commercial Energy Efficiency, Water-Cooled Centrifugal Chilling Packages
Equipment not designed for operation at AHRI Standard 550/590 test conditions of 44°F (7°C) leaving chilled-water temperature and 2.4 gpm/ton ...
Energy Conservation Code 2015 of Colorado > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.2 Provisions Applicable to All Mechanical Systems (Mandatory) > C403.2.3 HVAC Equipment Performance Requirements > C403.2.3.1 Water-Cooled Centrifugal Chilling Packages
C406.2.2 [CE] Commercial Energy Efficiency, Five-Percent Cooling Efficiency Improvement
Equipment shall exceed the minimum cooling and heat rejection efficiency requirements by 5 percent. Where multiple cooling performance requirements ...
Energy Conservation Code 2021 of Colorado > 4 [CE] Commercial Energy Efficiency > C406 Additional Efficiency Requirements > C406.2 More Efficient HVAC Equipment Performance > C406.2.2 Five-Percent Cooling Efficiency Improvement