[F] 415.11.5.1 HPM Rooms and Gas Rooms
JUMP TO FULL CODE CHAPTER
HPM rooms and gas rooms shall be separated from other areas by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. The fire-resistance rating shall be not less than 2 hours where the area is 300 square feet (27.9 m2) or more and not less than 1 hour where the area is less than 300 square feet (27.9 m2).
Related Code Sections
415.11.5.1 Special Detailed Requirements Based on Occupancy and Use, HPM Rooms and Gas Rooms
HPM rooms and gas rooms shall be separated from other areas by fire barriers constructed in accordance with Section 707 or horizontal assemblies ...
Building Code 2018 of Utah > 4 Special Detailed Requirements Based on Occupancy and Use > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.11 Group H-5 > 415.11.5 HPM Rooms, Gas Rooms, Liquid Storage Room Construction > 415.11.5.1 HPM Rooms and Gas Rooms
415.11.5.1 Special Detailed Requirements Based on Use and Occupancy, HPM Rooms and Gas Rooms
HPM rooms and gas rooms shall be separated from other areas by fire barriers constructed in accordance with Section 707 or horizontal assemblies ...
Building Code 2015 of Utah > 4 Special Detailed Requirements Based on Use and Occupancy > 415 Groups H-1, H-2, H-3, H-4 and H-5 > 415.11 Group H-5 > 415.11.5 HPM Rooms, Gas Rooms, Liquid Storage Room Construction > 415.11.5.1 HPM Rooms and Gas Rooms
2703.12.1.3 Semiconductor Fabrication Facilities, Liquid Storage Rooms, HPM Rooms and Gas Rooms
Emergency alarms for liquid storage rooms, HPM rooms and gas rooms shall comply with Section 5004.9 ...
Fire Code 2018 of Utah > 27 Semiconductor Fabrication Facilities > 2703 General Safety Provisions > 2703.12 Emergency Alarm System > 2703.12.1 Where Required > 2703.12.1.3 Liquid Storage Rooms, HPM Rooms and Gas Rooms
2704.3.1 Semiconductor Fabrication Facilities, HPM Storage
with the requirements of the International Building Code and this code for a liquid storage room, HPM room or gas room as appropriate for the materials stored ...
Fire Code 2018 of Utah > 27 Semiconductor Fabrication Facilities > 2704 Storage > 2704.3 Indoor Storage Outside of Fabrication Areas > 2704.3.1 HPM Storage
2705.3.3 Semiconductor Fabrication Facilities, Service Corridors
, HPM room, gas room or from the outside of a building to the perimeter wall of a fabrication area . Service corridors shall be designed ...
Fire Code 2018 of Utah > 27 Semiconductor Fabrication Facilities > 2705 Use and Handling > 2705.3 Transportation and Handling > 2705.3.3 Service Corridors