// CODE SNIPPET
(3) Household Ranges and Cooking Appliances
Go To Full Code Chapter
Branch-circuit conductors supplying household ranges, wall-mounted ovens, counter-mounted cooking units, and other household cooking appliances shall have an ampacity not less than the rating of the branch circuit and not less than the maximum load to be served. For ranges of 83/4 kW or more rating, the minimum branch-circuit rating shall be 40 amperes.
Exception No. 1: Conductors tapped from a branch circuit not exceeding 50 amperes supplying electric ranges, wall-mounted electric ovens, and counter-mounted electric cooking units shall have an ampacity of not less than 20 amperes and shall be sufficient for the load to be served. These tap conductors include any conductors that are a part of the leads supplied with the appliance that are smaller than the branch-circuit conductors. The taps shall not be longer than necessary for servicing the appliance.
Exception No. 2: The neutral conductor of a 3-wire branch circuit supplying a household electric range, a wall-mounted oven, or a counter-mounted cooking unit shall be permitted to be smaller than the ungrounded conductors where the maximum demand of a range of 83/4 kW or more rating has been calculated according to Column C of Table 220.55, but such conductor shall have an ampacity of not less than 70 percent of the branch-circuit rating and shall not be smaller than 10 AWG.
Related Code Sections
(3) Wiring and Protection, Household Ranges and Cooking Appliances
Branch-circuit conductors supplying household ranges, wall-mounted ovens, counter-mounted cooking units, and other household cooking appliances shall ...
(3) Wiring and Protection, Household Ranges and Cooking Appliances
Branch-circuit conductors supplying household ranges, wall-mounted ovens, counter-mounted cooking units, and other household cooking appliances shall ...
(E) Wiring and Protection, Tap Conductors
Tap conductors shall be permitted to be protected against overcurrent in accordance with the following: 210.19(A)(3) and (A)(4), Household Ranges ...
(E) Wiring and Protection, Tap Conductors
Tap conductors shall be permitted to be protected against overcurrent in accordance with the following: 210.19(A)(3) and (A)(4), Household Ranges ...
(A) Equipment for General Use, Individual Circuits
are listed for continuous loading at 100 percent of its rating. Branch circuits and branch-circuit conductors for household ranges and cooking ...