R403.5.3 Hot Water Pipe Insulation (Prescriptive)
JUMP TO FULL CODE CHAPTER
Insulation for hot water pipe with a minimum thermal resistance (R-value) of R-3 shall be applied to the following:
- Piping 3/4 inch (19.1 mm) and larger in nominal diameter.
- Piping serving more than one dwelling unit.
- Piping located outside the conditioned space.
- Piping from the water heater to a distribution manifold.
- Piping located under a floor slab.
- Buried piping.
- Supply and return piping in recirculation systems other than demand recirculation systems.
Related Code Sections
R403.5.3 [RE] Residential Energy Efficiency, Hot Water Pipe Insulation (Prescriptive)
Insulation for hot water pipe with a minimum thermal resistance ( R -value) of R-3 shall be applied to the following: Piping 3 / 4 inch (19.1 mm ...
Georgia State Minimum Standard Energy Code > 4 [RE] Residential Energy Efficiency > R403 Systems > R403.5 Service Hot Water Systems > R403.5.3 Hot Water Pipe Insulation (Prescriptive)
N1103.5.3 [RE] Energy Efficiency, (R403.5.3) Hot Water Pipe Insulation (Prescriptive)
Insulation for hot water piping with a thermal resistance, R -value, of not less than R-3 shall be applied to the following: Piping 3 / 4 inch ...
Georgia State Minimum Standard One and Two Family Dwelling Code > 11 [RE] Energy Efficiency > N1103 (R403) Systems > N1103.5 (R403.5) Service Hot Water Systems > N1103.5.3 (R403.5.3) Hot Water Pipe Insulation (Prescriptive)
607.5 Water Supply and Distribution, Pipe Insulation
Hot water piping in automatic temperature maintenance systems shall be insulated with 1 inch (25 mm) of insulation having a conductivity ...
Georgia State Minimum Standard Plumbing Code > 6 Water Supply and Distribution > 607 Hot Water Supply System > 607.5 Pipe Insulation
607.5 Water Supply and Distribution, Insulation of Piping
and piping conveying water heated by a water heater shall be insulated in accordance with Section C404.4 of the International Energy Conservation Code ...
Georgia State Minimum Standard Plumbing Code > 6 Water Supply and Distribution > 607 Hot Water Supply System > 607.5 Insulation of Piping
504.5 Commercial Energy Efficiency, Pipe Insulation
For automatic-circulating hot water systems, piping shall be insulated with 1 inch (25 mm) of insulation having a conductivity not exceeding 0.27 Btu ...
Georgia State Minimum Standard Energy Code > 5 Commercial Energy Efficiency > 504 Service Water Heating (Mandatory) > 504.5 Pipe Insulation