Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

702.7 Hot and Tempered Water Distribution

Dallas Green Construction Code > 7 Water Resource Conservation, Quality and Efficiency > 702 Fixtures, Fittings, Equipment and Appliances > 702.7 Hot and Tempered Water Distribution
JUMP TO FULL CODE CHAPTER
Water supply piping shall be in accordance with Section 702.7.1 or Section 702.7.2. The flow rate through 1/4-inch (6.4 mm) tubing shall not exceed 0.5 gpm (1.9 Lpm). The flow rate through 5/16-inch (7.9 mm) tubing shall not exceed 1 gpm (3.8 Lpm). The flow rate through 3/8-inch (9.5 mm) tubing shall not exceed 1.5 gpm (5.7 Lpm).

702.7.1 Maximum Allowable Pipe Length Method

The maximum allowable pipe length from the source of hot or tempered water to the termination of the fixture supply pipe shall be in accordance with the maximum pipe length columns in Tables 702.7.2(2) through 702.7.2(10), as appropriate for the type of pipe to be installed. Where the type of pipe to be installed is unknown or the type of pipe is not covered by Tables 702.7.2(2) through 702.7.2(10), Table 702.7.2(1) shall be used for design purposes. Where the length contains more than one size of pipe, the largest size shall be used for determining the maximum allowable length of the pipe in the tables.

702.7.2 Maximum Allowable Pipe Volume Method

The water volume in the piping shall be calculated in accordance with Section 702.7.2.1. The maximum volume of hot or tempered water in the piping to public lavatory faucets, metering or nonmetering, shall be 2 ounces (0.06 L). For fixtures other than public lavatory faucets, the maximum volume shall be 64 ounces (1.89 L) for hot or tempered water from a water heater or boiler; and 24 ounces (0.7 L) for hot or tempered water from a circulation loop pipe or an electrically heat-traced pipe. The water volume in the piping shall be calculated in accordance with Section 702.7.2.1.

TABLE 702.7.2(1) VOLUME AND MAXIMUM LENGTH OF PIPE OR TUBE OF A TYPE UNKNOWN OR NOT COVEREDb

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM PIPE OR TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a circulation
loop or heat-traced line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
1/4a 0.33 50 16 6
5/16a 0.5 50 16 4
3/8a 0.75 50 16 3
1/2 1.5 43 16 2
5/8 2 32 12 1
3/4 3 21 8 0.5
7/8 4 16 6 0.5
1 5 13 5 0.5
11/4 8 8 3 0.5
11/2 11 6 2 0.5
2 or larger 18 4 1 0.5

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. The flow rate for 1/4-inch size pipe or tube is limited to 0.5 gallons per minute; for 5/16-inch size, it is limited to 1 gpm; for 3/8-inch size, it is limited to 1.5 gpm.
b. Not covered means pipe or tube types not covered by Tables 702.7.2(2) through 702.7.2(10).


TABLE 702.7.2(2) VOLUME AND MAXIMUM LENGTH OF TYPE K COPPER TUBING

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a heat-traced
line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
3/8a 0.84 44.6 14.3 2.7
1/2 1.45 44.5 16.6 2.1
3/4 2.90 21.7 8.3 0.5
1 5.17 12.6 4.8 0.5
11/4 8.09 7.9 3.0 0.5
11/2 11.45 5.8 1.9 0.5
2 or larger 20.04 3.6 0.9 0.4

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. The flow rate for 3/8-inch size is limited to 1.5 gallons per minute.


TABLE 702.7.2(3) VOLUME AND MAXIMUM LENGTH OF TYPE L COPPER TUBING

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a circulation
loop or heat-traced line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
3/8a 0.97 38.7 12.4 2.3
1/2 1.55 41.6 15.5 1.9
3/4 3.22 19.6 7.5 0.5
1 5.49 11.8 4.6 0.5
11/4 8.38 7.6 2.9 0.5
11/2 11.83 5.6 1.9 0.5
2 or larger 20.58 3.5 0.9 0.4

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. The flow rate for 3/8-inch size is limited to 1.5 gpm.


TABLE 702.7.2(4) VOLUME AND MAXIMUM LENGTH OF TYPE M COPPER TUBING

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a circulation
loop or heat-traced line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
3/8a 1.06 35.4 11.3 2.1
1/2 1.69 38.2 14.2 1.8
3/4 3.43 18.4 7.0 0.4
1 5.81 11.2 4.3 0.4
11/4 8.70 7.4 2.8 0.5
11/2 12.18 5.4 1.8 0.5
2 or larger 21.08 3.4 0.9 0.4

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. The flow rate for 3/8-inch size is limited to 1.5 gpm.


TABLE 702.7.2(5) VOLUME AND MAXIMUM LENGTH OF CPVC TUBING, CTSa

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a circulation
loop or heat-traced line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
1/2 1.25 51.6 19.2 2.4
3/4 2.67 23.6 9.0 0.6
1 4.43 14.7 5.6 0.6
11/4 6.61 9.7 3.6 0.6
11/2 9.22 7.2 2.4 0.6
2 or larger 15.79 4.6 1.1 0.6

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. Copper tube size outside diameter dimension and SDR 11.


TABLE 702.7.2(6) VOLUME AND MAXIMUM LENGTH OF CPVC PIPE, SCHEDULE 40

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a circulation
loop or heat-traced line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
3/8a 1.17 32.1 10.3 1.9
1/2 1.89 34.1 12.7 1.6
3/4 3.58 17.6 6.7 0.4
1 5.53 11.8 4.5 0.5
11/4 9.66 6.6 2.5 0.4
11/2 13.20 5.0 1.7 0.4
2 or larger 21.88 3.3 0.8 0.4

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. The flow rate for 3/8-inch size is limited to 1.5 gpm.


TABLE 702.7.2(7) VOLUME AND MAXIMUM LENGTH OF CPVC PIPE, SCHEDULE 80

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a circulation
loop or heat-traced line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
3/8a 0.86 43.6 14.0 2.6
1/2 1.46 44.2 16.4 2.1
3/4 2.74 23.0 8.8 0.5
1 4.56 14.3 5.5 0.5
11/4 8.24 7.8 2.9 0.5
11/2 11.38 5.8 1.9 0.5
2 or larger 19.11 3.8 0.9 0.5

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. The flow rate for 3/8-inch size is limited to 1.5 gpm.


TABLE 702.7.2(8) VOLUME AND MAXIMUM LENGTH OF PE-AL-PE TUBING

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a circulation
loop or heat-traced line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
3/8a 0.63 59.5 19.0 3.6
1/2 1.31 49.2 18.3 2.3
3/4 3.39 18.6 7.1 0.4
1 5.56 11.7 4.5 0.4
11/4 8.49 7.5 2.8 0.5
11/2 13.88 4.8 1.6 0.4
2 or larger 21.48 3.4 0.8 0.4

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. The flow rate for 3/8-inch size is limited to 1.5 gpm.


TABLE 702.7.2(9) VOLUME AND MAXIMUM LENGTH OF PEX AND PE-RT TUBING, CTSb

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a circulation
loop or heat-traced line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
3/8a 0.6 58.6 18.8 3.5
1/2 1.18 54.7 20.3 2.5
3/4 2.35 26.8 10.2 0.6
1 3.91 16.6 6.4 0.6
11/4 5.81 11.0 4.1 0.7
11/2 8.09 8.2 2.7 0.7
2 or larger 13.86 5.2 1.3 0.6

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. The flow rate for 3/8-inch size is limited to 1.5 gpm.
b. Copper tube size outside diameter dimension and SDR 9, for both PEX and PE-RT types of tubing.


TABLE 702.7.2(10) VOLUME AND MAXIMUM LENGTH OF PEX-AL-PEX TUBING

NOMINAL PIPE OR TUBE
SIZE (inch)
LIQUID OUNCES PER FOOT
OF LENGTH
MAXIMUM TUBE LENGTH
System without a circulation
loop or heat-traced line (feet)
System with a circulation
loop or heat-traced line (feet)
Lavatory faucets — public
(metering and nonmetering)
(feet)
3/8a 0.63 59.5 19.0 3.6
1/2 1.31 49.2 18.3 2.3
3/4 3.39 18.6 7.1 0.4
1 5.56 11.7 4.5 0.4
11/4 8.49 7.5 2.8 0.5
11/2 13.88 4.8 1.6 0.4
2 or larger 21.48 3.4 0.8 0.4

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 ounce = 29.6 ml.
a. The flow rate for 3/8-inch size is limited to 1.5 gpm.

702.7.2.1 Water Volume Determination

The volume shall be the sum of the internal volumes of pipe, fittings, valves, meters and manifolds between the source of hot water and the termination of the fixture supply pipe. The volume shall be determined from the liquid ounces per foot column of Tables 702.7.2(2) through 702.7.2(10) as appropriate for the type of pipe. Where the type of pipe is unknown or the type of pipe is not covered by Tables 702.7.2(2) through 702.7.2(10), Table 702.7.2(1) shall be used to determine the volume. The volume contained within fixture shutoff valves, flexible water supply connectors to a fixture fitting, or within a fixture fitting shall not be included in the water volume determination. Where hot or tempered water is supplied by a circulation loop pipe or an electrically heat-traced pipe, the volume shall include the portion of the fitting on the source pipe that supplies water to the fixture.

Related Code Sections


702.7 Water Resource Conservation, Quality and Efficiency, Hot and Tempered Water Distribution
maximum allowable pipe length from the source of hot or tempered water to the termination of the fixture supply pipe shall be in accordance ...
Dallas Green Construction Code > 7 Water Resource Conservation, Quality and Efficiency > 702 Fixtures, Fittings, Equipment and Appliances > 702.7 Hot and Tempered Water Distribution
1002.2.2 Boilers, Water Heaters and Pressure Vessels, Temperature Limitation
), a temperature-actuated mixing valve that conforms to ASSE 1017 shall be provided to temper the water supplied to the potable hot water distribution system ...
Dallas Mechanical Code > 10 Boilers, Water Heaters and Pressure Vessels > 1002 Water Heaters > 1002.2 Water Heaters Utilized for Space Heating > 1002.2.2 Temperature Limitation
Help Contact Us Privacy Terms
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING