Dispensing of Class I, II or IIIA liquids into the fuel tanks of marine craft shall be by means of an approved-type hose equipped with a listed automatic-closing nozzle without a latch-open device.
Hoses used for dispensing or transferring Class I, II or IIIA liquids, when not in use, shall be reeled, racked or otherwise protected from mechanical damage.
Upcodes Diagrams

Related Code Sections

2310.3.3 Motor Fuel-Dispensing Facilities and Repair Garages, Hoses and Nozzles
automatic-closing nozzle without a latch-open device. Hoses used for dispensing or transferring Class I, II or IIIA liquids, when not in use, shall ...
2310.3.3 Motor Fuel-Dispensing Facilities and Repair Garages, Hoses and Nozzles
automatic-closing nozzle without a latch-open device. Hoses used for dispensing or transferring Class I, II or IIIA liquids, when not in use, shall ...
2006.3.3 Aviation Facilities, Dispensing Hoses and Nozzles
operations. Hoses shall be equipped with an approved shutoff nozzle. Fuel-transfer nozzles shall be self-closing and designed to be actuated by hand ...
2006.3.3 Aviation Facilities, Dispensing Hoses and Nozzles
operations. Hoses shall be equipped with an approved shutoff nozzle. Fuel-transfer nozzles shall be self-closing and designed to be actuated by hand ...
5707.5.1 Flammable and Combustible Liquids, Dispensing Hoses and Nozzles
Where equipped, the dispensing hose shall not exceed 50 feet (15 240 mm) in length. The dispensing nozzles and hoses shall be of an approved ...