Section 3118B Hose Bibbs

Go To Full Code Chapter
Potable water outlets with hose attachments shall be protected by a nonremovable hose bibb backflow preventer, a nonremovable hose bibb vacuum breaker or by an atmospheric vacuum breaker installed not less than 6 inches (152 mm) above the highest point of usage located on the discharge side of the last valve as required by the California Plumbing Code. In climates where freezing temperatures occur, a listed self-draining frost-proof hose bibb with an integral backflow preventer or vacuum breaker shall be used. Hose bibbs shall be provided so that all portions of the pool deck area may be reached with a 75 foot length of hose attached to the hose bibb. A hose bibb shall be provided in the equipment area. Hose bibbs shall be located so that they do not constitute a hazard.
Upcodes Diagrams

Related Code Sections

1503.9 Alternate Water Sources for Nonpotable Applications, Hose Bibbs
Hose bibbs shall not be allowed on reclaimed (recycled) water piping systems. Only quick couplers that differ from those installed on the potable ...
1505.9 Alternate Water Sources for Nonpotable Applications, Hose Bibbs
Hose bibbs shall not be allowed on reclaimed (recycled) water piping systems. Only quick couplers that differs from those installed on the potable ...
1505.9 Alternate Water Sources for Nonpotable Applications, Hose Bibbs
Hose bibbs shall not be allowed on reclaimed (recycled) water piping systems. Only quick couplers that differs from those installed on the potable ...
Section 3118B [DPH] Public Pools, Hose Bibbs
Potable water outlets with hose attachments shall be protected by a nonremovable hose bibb backflow preventer, a nonremovable hose bibb vacuum ...
Section 3118B [DPH] Public Pools, Hose Bibbs
Potable water outlets with hose attachments shall be protected by a nonremovable hose bibb backflow preventer, a nonremovable hose bibb vacuum ...