// CODE SNIPPET
(1) Horsepower Rating
Go To Full Code Chapter
The horsepower rating of the disconnecting means shall be determined from the sum of all currents, including resistance loads, at the rated-load condition and also at the locked-rotor condition. The combined rated-load current and the combined locked-rotor current so obtained shall be considered as a single motor for the purpose of this requirement as required by 440.12(B)(1)(a) and (B)(1)(b).
(a) The full-load current equivalent to the horsepower rating of each motor, other than a hermetic refrigerant motor-compressor, and fan or blower motors as covered in 440.6(B) shall be selected from Table 430.248, Table 430.249, or Table 430.250. These full-load currents shall be added to the motor-compressor rated-load current(s) or branch-circuit selection current(s), whichever is greater, and to the rating in amperes of other loads to obtain an equivalent full-load current for the combined load.
(b) The locked-rotor current equivalent to the horsepower rating of each motor, other than a hermetic refrigerant motor-compressor, shall be selected from Table 430.251(A) or Table 430.251(B), and, for fan and blower motors of the shaded-pole or permanent split-capacitor type marked with the locked-rotor current, the marked value shall be used. The locked-rotor currents shall be added to the motor-compressor locked-rotor current(s) and to the rating in amperes of other loads to obtain an equivalent locked-rotor current for the combined load. Where two or more motors or other loads such as resistance heaters, or both, cannot be started simultaneously, appropriate combinations of locked-rotor and rated-load current or branch-circuit selection current, whichever is greater, shall be an acceptable means of determining the equivalent locked-rotor current for the simultaneous combined load.
Exception: Where part of the concurrent load is a resistance load and the disconnecting means is a switch rated in horsepower and amperes, the switch used shall be permitted to have a horsepower rating not less than the combined load to the motor-compressor(s) and other motor(s) at the locked-rotor condition, if the ampere rating of the switch is not less than this locked-rotor load plus the resistance load.
Related Code Sections
(1) Equipment for General Use, Horsepower Rating
motor for the purpose of this requirement as follows.
The full-load current equivalent to the horsepower rating of each motor shall be selected from ...
(1) Equipment for General Use, Horsepower Rating
motor for the purpose of this requirement as follows. The full-load current equivalent to the horsepower rating of each motor shall be selected from ...
(1) Equipment for General Use, Horsepower Rating
The horsepower rating of the disconnecting means shall be determined from the sum of all currents, including resistance loads, at the rated-load ...
(1) Equipment for General Use, Horsepower Rating
The horsepower rating of the disconnecting means shall be determined from the sum of all currents, including resistance loads, at the rated-load ...
(2) Equipment for General Use, Horsepower Rated Disconnect
The disconnecting means shall be a switch with a horsepower rating. The equivalent locked rotor current of the horsepower rating of the switch shall ...