1916.2.3 Horizontal Ties
JUMP TO FULL CODE CHAPTER
At each column, beam reinforcement or slab bottom reinforcement shall be provided at each level that can develop a tension force equal to the maximum of Item 1 or 2:
- Three times the load entering the column at that level, using a load combination of 1.0 × DL (self weight of structure only).
- One and a half times the load entering the column at that level using the load combinations of (1.2 DL + 1.6 LL) or 1.4 DL.
- For transfer elements only, in lieu of Item 1 or 2, the horizontal reinforcement shall be anchored at all supports.
This beam or slab bottom reinforcement shall be distributed around the column perimeter and shall be extended on all sides of the column into the adjacent slab for at least one-third of the span length. Where reinforcing bars cannot be extended beyond the column (e.g., at slab edges and openings), they shall be hooked or otherwise developed within the column.
Related Code Sections
1916.2.3 Concrete, Horizontal Ties
elements only, in lieu of Item 1 or 2, the horizontal reinforcement shall be anchored at all supports ...
NYC Building Code 2014 > 19 Concrete > 1916 Structural Integrity Requirements > 1916.2 Continuity and Ties > 1916.2.3 Horizontal Ties
1917.2.3 Concrete, Horizontal Ties
At each column, beam reinforcement or slab bottom reinforcement shall be provided at each level that can develop a tension force equal to the maximum ...
NYC Building Code 2008 > 19 Concrete > 1917 Structural Integrity Requirements > 1917.2 Continuity and Ties > 1917.2.3 Horizontal Ties
2114.2.1.1 Masonry, Location of Horizontal Ties
Ties shall be located within the thickness of walls or beams, where they occur, or within 1 foot (305 mm) of the edge of slab, where walls or beams ...
NYC Building Code 2008 > 21 Masonry > 2114 Structural Integrity Requirements > 2114.2 Continuity and Ties > 2114.2.1 Horizontal > 2114.2.1.1 Location of Horizontal Ties
2114.2.1.1 Masonry, Location of Horizontal Ties
Ties shall be located within the thickness of walls or beams, where they occur, or within 1 foot (305 mm) of the edge of slab, where walls or beams ...
NYC Building Code 2014 > 21 Masonry > 2114 Structural Integrity Requirements > 2114.2 Continuity and Ties > 2114.2.1 Horizontal > 2114.2.1.1 Location of Horizontal Ties
2114.2.1 Masonry, Horizontal
At each floor and roof level, continuous horizontal ties shall be provided in all load-bearing masonry walls, and around the perimeter ...
NYC Building Code 2014 > 21 Masonry > 2114 Structural Integrity Requirements > 2114.2 Continuity and Ties > 2114.2.1 Horizontal