R608.7.2.2.1 Horizontal Shear Reinforcement
JUMP TO FULL CODE CHAPTER
Where reduction factors for design strength, R3, from Table R608.7(4) based on horizontal and vertical shear reinforcement being provided are used, solid wall segments shall have horizontal reinforcement consisting of minimum No. 4 bars. Horizontal shear reinforcement shall be the same grade of steel required for the vertical reinforcement at the ends of solid wall segments by Section R608.7.2.2.2.
The spacing of horizontal reinforcement shall not exceed the smaller of one-half the length of the solid wall segment, minus 2 inches (51 mm), and 18 inches (457 mm). Horizontal shear reinforcement shall terminate in accordance with Section R608.6.4.
The spacing of horizontal reinforcement shall not exceed the smaller of one-half the length of the solid wall segment, minus 2 inches (51 mm), and 18 inches (457 mm). Horizontal shear reinforcement shall terminate in accordance with Section R608.6.4.
Related Code Sections
R608.7.2.2.1 Wall Construction, Horizontal Shear Reinforcement
Where reduction factors for design strength, R 3 , from Table R608.7(4) based on horizontal and vertical shear reinforcement being provided ...
Residential Code 2015 of Utah > 6 Wall Construction > R608 Exterior Concrete Wall Construction > R608.7 Solid Walls for Resistance to Lateral Forces > R608.7.2 Solid Wall Segments > R608.7.2.2 Reinforcement in Solid Wall Segments > R608.7.2.2.1 Horizontal Shear Reinforcement
R606.12.3.2.1 Wall Construction, Shear Wall Reinforcement Requirements
The maximum spacing of vertical and horizontal reinforcement shall be the smaller of one-third the length of the shear wall, one-third the height ...
Residential Code 2015 of Utah > 6 Wall Construction > R606 General Masonry Construction > R606.12 Seismic Requirements > R606.12.3 Seismic Design Category D0 or D1 > R606.12.3.2 Minimum Reinforcement Requirements for Masonry Walls > R606.12.3.2.1 Shear Wall Reinforcement Requirements
R608.7 Wall Construction, Solid Walls for Resistance to Lateral Forces
Horizontal and vertical shear reinforcement shall be provided in accordance with Section R608.7.2.2.
Each end of each solid wall segment shall ...
Residential Code 2015 of Utah > 6 Wall Construction > R608 Exterior Concrete Wall Construction > R608.7 Solid Walls for Resistance to Lateral Forces
R606.12.3 Wall Construction, Seismic Design Category D0 or D1
and horizontal direction. The sum of the cross-sectional area of horizontal and vertical reinforcement shall be not less than 0.002 times the gross cross ...
Residential Code 2015 of Utah > 6 Wall Construction > R606 General Masonry Construction > R606.12 Seismic Requirements > R606.12.3 Seismic Design Category D0 or D1
A206.8 Earthquake Hazard Reduction in Existing Reinforced Concrete and Reinforced Masonry Wall Buildings With Flexible Diaphragms, Collectors
or the tributary shear based on 75 percent of the horizontal forces specified in Chapter 16 of the International Building Code . The capacity of the collector need ...
Existing Building Code 2015 of Utah > A2 Earthquake Hazard Reduction in Existing Reinforced Concrete and Reinforced Masonry Wall Buildings With Flexible Diaphragms > A206 Analysis and Design > A206.8 Collectors