Horizontal safety netting systems shall meet the requirements of Sections 5, 6.3, 6.4, 6.5, 6.6, 7, 8, 10.1, 10.4, 10.5, 10.6, 10.7, 11, and 13 of ANSI/ASSP A10.11, as modified as follows.
3308.6.2.1 Personnel Net
Throughout the standard, the term "personnel net" shall be amended to read "structural net."
3308.6.2.2 Should and Shall
Throughout the standard, the term "should" shall be amended to read "shall."
3308.6.2.3 Entanglement
The phrase, "and to minimize entanglement of the persons head, arms, and legs when arresting the fall," shall be deleted from Section 6.3 of ANSI/ASSP A10.11.
3308.6.2.4 Arresting a Fall
The phrase "when arresting a fall," shall be deleted from Section 6.4 of ANSI/ASSP A10.11.
3308.6.2.5 Size of Debris Net Openings
Section 6.6 of ANSI/ASSP A10.11 shall be amended by adding a new sentence at the end of the section, as follows, "However, in no case shall the largest opening area for debris netting when used horizontally be larger than 1/2 square inch (323 mm2 ), with no opening larger than 1/2 inch (13 mm2 ) in the vertical or horizontal dimensions and 3/4 inch (19 mm) in any other dimension."
3308.6.2.6 Projection of Nets
The phrase, "as to capture falling personnel" in Section 10.6 of ANSI/ASSP A10.11 shall be amended to read "as to capture falling material."
3308.6.2.7 Supports
The phrase, "or personnel" in Section 10.7 of ANSI/ASSP A10.11 shall be amended to read, "or material."
3308.6.2.8 Inspection
Section 11.1 of ANSI/ASSP A10.11 shall be deleted in its entirety and replaced with the following, "Horizontal safety netting systems shall be inspected in accordance with Section 3308.9.3."
3308.6.2.9 Dates Tested
The phrase "Dates inspected" in Item 5 of Section 11.4 of ANSI/ASSP A10.11 shall be amended to read "Dates tested".
3308.6.2.10 Moving
Section 11.4 of ANSI/ASSP A10.11 shall be amended to add a new Item 9, which shall read, "Dates nets were moved to a higher or lower level."
3308.6.2.11 Cleaning
Section 13.2 of ANSI/ASSP A10.11 shall be deleted and replaced with the following: "Horizontal safety netting shall not be used for storing material. Horizontal netting shall be cleaned, at least daily, to remove any items that fall into the nets."