P3005.3 Horizontal Drainage Piping Slope
JUMP TO FULL CODE CHAPTER
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes not less than 1/4 unit vertical in 12 units horizontal (2-percent slope) for 21/2-inch (64 mm) diameter and less, and not less than 1/8 unit vertical in 12 units horizontal (1-percent slope) for diameters of 3 inches (76 mm) or more.
Related Code Sections
P3005.3 Sanitary Drainage, Horizontal Drainage Piping Slope
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes not less than 1 / 4 unit vertical in 12 units horizontal (2 ...
Residential Code 2009 of Pennsylvania > 30 Sanitary Drainage > P3005 Drainage System > P3005.3 Horizontal Drainage Piping Slope
P3005.3 Sanitary Drainage, Horizontal Drainage Piping Slope
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes not less than 1 / 4 unit vertical in 12 units horizontal (2 ...
Residential Code 2015 of Pennsylvania > 30 Sanitary Drainage > P3005 Drainage System > P3005.3 Horizontal Drainage Piping Slope
704.1 Sanitary Drainage, Slope of Horizontal Drainage Piping
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The minimum slope of a horizontal drainage pipe shall ...
Plumbing Code 2009 of Pennsylvania > 7 Sanitary Drainage > 704 Drainage Piping Installation > 704.1 Slope of Horizontal Drainage Piping
704.1 Sanitary Drainage, Slope of Horizontal Drainage Piping
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The slope of a horizontal drainage pipe shall be not less than ...
Plumbing Code 2015 of Pennsylvania > 7 Sanitary Drainage > 704 Drainage Piping Installation > 704.1 Slope of Horizontal Drainage Piping
714.3.2 Sanitary Drainage, Slope of Horizontal Drainage Piping
Horizontal drainage piping shall be designed and installed at slopes in accordance with Table 704.1 ...