50.4.4.8 Hoods With Water Wash
Go To Full Code Chapter
50.4.4.8.1
50.4.4.8.2
50.4.4.8.3
The water supply for water-wash fire-extinguishing
systems shall be permitted to be supplied from the domestic
water supply when the minimum water pressure and flow are
provided in accordance with the terms of the listing.
[96:10.2.8.3]
50.4.4.8.4
The water supply for water-wash fire-extinguishing
systems shall be controlled by a listed indicating valve.
[96:10.2.8.4]
50.4.4.8.5
Where a separate fire-extinguishing system is used for protection of cooking equipment only, a water-wash fire-extinguishing system listed for protection of the grease removal device(s), hood exhaust plenum(s), exhaust duct(s), or combination thereof shall be provided with instructions and appropriate means for electrical interface for simultaneous actuation. [96:10.2.8.5]
50.4.4.8.6
A water-wash system approved to be used for protection of the grease removal device(s), hood exhaust plenum(s), exhaust duct(s), or combination thereof shall include instructions and appropriate electrical interface for simultaneous actuation of the water-wash system from an automatic fire-extinguishing system, where the automatic fire-extinguishing system is used for cooking equipment protection only. [96:10.2.8.6]
50.4.4.8.7
Where the automatic fire-extinguishing system in accordance with NFPA 17A provides protection for the hood and duct in a hood containing a water-wash system, the water-wash system shall be made inoperable or delayed for a minimum of 60 seconds upon operation of the automatic fire-extinguishing system. [96:10.2.8.7]
Related Code Sections
50.4.4.8 Commercial Cooking, Hoods With Water Wash
] A water-wash system approved to be used for protection of the grease removal device(s), hood exhaust ...
50.4.4.8 Commercial Cooking, Hoods With Water Wash
] A water-wash system approved to be used for protection of the grease removal device(s), hood ...
50.4.4.8.2 Commercial Cooking,
Each such area not provided with a listed water-wash fire-extinguishing system shall be provided with a fire-extinguishing system listed ...
50.4.4.8.1 Commercial Cooking,
Areas requiring protection in accordance with 50.4.3.1 shall be permitted to be protected by a water-wash system that is listed as a fire ...
50.4.4.8.5 Commercial Cooking,
Where a separate fire-extinguishing system is used for protection of cooking equipment only, a water-wash fire-extinguishing system listed ...