907.20.7 Hold-Open Devices
JUMP TO FULL CODE CHAPTER
The fire alarm system connections for hold-open devices installed on fire doors pursuant to the Building Code, including hold-open devices provided for vertical exit enclosure doors pursuant to the exception to Section BC 708.7 of the Building Code, shall be inspected, tested and otherwise maintained in accordance with FC 703.2 and 907.20 and NFPA 72. Hold-open devices and automatic door closers provided for such vertical exit enclosure doors shall be inspected and tested annually to ensure the proper functioning of:
- the manual control on the fire alarm system control panel, or the fire command center where a fire command center is required, that transmits a signal to release the hold-open devices;
- the fire alarm system output programming, which automatically transmits a signal to release the hold-open devices upon activation of an automatic alarm initiating device or manual elevator recall;
- the circuitry for each hold-open device, which upon receipt of a manual or automatic signal, releases the door; and
- each automatic door closer, which, upon release of the door by the hold-open device, mechanically moves the door to its fully closed position.
Related Code Sections
907.3.5 Fire Protection Systems, Monitoring of Hold-Open Devices and Closers
All hold-open devices used in automatic-closing doors pursuant to the exception to Section 708.7 shall be electrically supervised to monitor ...
NYC Building Code 2014 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire Safety Functions > 907.3.5 Monitoring of Hold-Open Devices and Closers
907.3.5 Fire Protection Systems, Monitoring of Hold-Open Devices and Closers
All hold-open devices used in automatic-closing doors pursuant to the exception to Section 713.7 shall be electrically supervised to monitor ...
NYC Building Code 2022 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Fire Safety Functions > 907.3.5 Monitoring of Hold-Open Devices and Closers
715.3.7.3 Fire-Resistance-Rated Construction, Smoke-Activated Doors
in accordance with Section 907.10 or by loss of power to the smoke detector or hold-open device. Fire doors that are automatic-closing by smoke detection shall ...
NYC Building Code 2008 > 7 Fire-Resistance-Rated Construction > 715 Opening Protectives > 715.3 Fire Door and Shutter Assemblies > 715.3.7 Door Closing > 715.3.7.3 Smoke-Activated Doors
703.3.11 Communication Elements and Features, Location
containing raised characters and braille shall be permitted on the push side of doors with closers and without hold-open devices. FIG. 703.3.11 ...
Accessible and Usable Buildings and Facilities 2009 of New York City > 7 Communication Elements and Features > 703 Signs > 703.3 Raised Characters > 703.3.11 Location
715.4.8.3 Fire and Smoke Protection Features, Smoke-Activated Doors
in accordance with Section 907.3 or by loss of power to the smoke detector or hold-open device. Doors that are automatic-closing by smoke detection shall ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 715 Opening Protectives > 715.4 Fire Door and Shutter Assemblies > 715.4.8 Door Closing > 715.4.8.3 Smoke-Activated Doors