3006.2 Hoistway Opening Protection Required
JUMP TO FULL CODE CHAPTER
Elevator hoistway door openings shall be protected in accordance with Section 3006.3 where an elevator hoistway connects more than three stories, is required to be enclosed within a shaft enclosure in accordance with Section 712.1.1 and any of the following conditions apply:
- The building is not protected throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
- The building contains a Group I-1, Condition 2 occupancy.
- The building contains a Group I-2 occupancy.
- The building contains a Group I-3 occupancy.
- The building is a high rise and the elevator hoistway is more than 75 feet (22 860 mm) in height. The height of the hoistway shall be measured from the lowest floor to the highest floor of the floors served by the hoistway.
Exception:
- Protection of elevator hoistway door openings is not required where the elevator serves only open parking garages in accordance with Section 406.5.
- Protection of elevator hoistway door openings is not required at the level(s) of exit discharge, provided that the level(s) of exit discharge is equipped with an automatic sprinkler system in accordance with Section 903.3.1.1.
- Enclosed elevator lobbies and protection of elevator hoistway door openings are not required on levels where the elevator hoistway opens to the exterior.
Where corridors are required to be fire-resistance rated in accordance with Section 1020.1, elevator hoistway openings shall be protected in accordance with Section 3006.3.
Related Code Sections
3006.2 Elevators and Conveying Systems, Hoistway Opening Protection Required
of the floors served by the hoistway. Exception: Protection of elevator hoistway door openings is not required where the elevator serves only ...
Building Code 2018 of Illinois > 30 Elevators and Conveying Systems > 3006 Elevator Lobbies and Hoistway Opening Protection > 3006.2 Hoistway Opening Protection Required
3002.1.1 Elevators and Conveying Systems, Opening Protectives
Openings in hoistway enclosures shall be protected as required in Chapter 7. Exception: The elevator car doors and the associated hoistway ...
Building Code 2018 of Illinois > 30 Elevators and Conveying Systems > 3002 Hoistway Enclosures > 3002.1 Hoistway Enclosure Protection > 3002.1.1 Opening Protectives
1009.4 Means of Egress, Elevators
with Section 1009.6. Exceptions: Areas of refuge are not required at the elevator in open parking garages . Areas of refuge are not required ...
Building Code 2018 of Illinois > 10 Means of Egress > 1009 Accessible Means of Egress > 1009.4 Elevators
3002.1 Elevators and Conveying Systems, Hoistway Enclosure Protection
Openings in hoistway enclosures shall be protected as required in Chapter 7 ...
Building Code 2018 of Illinois > 30 Elevators and Conveying Systems > 3002 Hoistway Enclosures > 3002.1 Hoistway Enclosure Protection
3008.6.1 Elevators and Conveying Systems, Access to Interior Exit Stairway or Ramp
not less than the elevator lobby enclosure. The protected path shall be separated from the enclosed elevator lobby through an opening protected ...
Building Code 2018 of Illinois > 30 Elevators and Conveying Systems > 3008 Occupant Evacuation Elevators > 3008.6 Occupant Evacuation Elevator Lobby > 3008.6.1 Access to Interior Exit Stairway or Ramp