[F] 502.9.7 Highly Toxic and Toxic Compressed Gases - Any Quantity
JUMP TO FULL CODE CHAPTER
Ventilation exhaust shall be provided for
highly toxic and toxic compressed gases in any quantity as
required by Sections 502.9.7.1 and 502.9.7.2.
Gas cabinets containing
highly toxic or toxic compressed gases in any quantity
shall comply with Section 502.8.2 and the following
requirements:
- The average ventilation velocity at the face of gas cabinet access ports or windows shall be not less than 200 feet per minute (1.02 m/s) with a minimum velocity of 150 feet per minute (0.76 m/s) at any point at the access port or window.
- Gas cabinets shall be connected to an exhaust system.
- Gas cabinets shall not be used as the sole means of exhaust for any room or area.
Exhausted enclosures
containing highly toxic or toxic compressed gases
in any quantity shall comply with Section 502.8.2 and
the following requirements:
- The average ventilation velocity at the face of the enclosure shall be not less than 200 feet per minute (1.02 m/s) with a minimum velocity of 150 feet per minute (0.76 m/s).
- Exhausted enclosures shall be connected to an exhaust system.
- Exhausted enclosures shall not be used as the sole means of exhaust for any room or area.
Related Code Sections
502.9.7 Exhaust Systems, Highly Toxic and Toxic Compressed Gases - Any Quantity
Ventilation exhaust shall be provided for
highly toxic and toxic compressed gases in any quantity as
required by Sections 502.9.7.1 and 502.9.7.2 ...
2015 Michigan Mechanical Code > 5 Exhaust Systems > 502 Required Systems > 502.9 Hazardous Materials-Requirements for Specific Materials > 502.9.7 Highly Toxic and Toxic Compressed Gases - Any Quantity
908.3 Fire Protection Systems, Highly Toxic and Toxic Materials
is not required for
reactors utilized for the production of highly toxic or
toxic compressed gases where such reactors are:
Operated at pressures less ...
2015 Michigan Building Code > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.3 Highly Toxic and Toxic Materials
502.9.6 Exhaust Systems, Highly Toxic and Toxic Liquids
Ventilation
exhaust shall be provided for highly toxic and toxic liquids
as required by Sections 502.9.6.1 and 502.9.6.2 ...
2015 Michigan Mechanical Code > 5 Exhaust Systems > 502 Required Systems > 502.9 Hazardous Materials-Requirements for Specific Materials > 502.9.6 Highly Toxic and Toxic Liquids
502.9.8.6 Exhaust Systems, Process Equipment
Effluent from
indoor and outdoor process equipment containing
highly toxic or toxic compressed gases which could be
discharged to the atmosphere ...
2015 Michigan Mechanical Code > 5 Exhaust Systems > 502 Required Systems > 502.9 Hazardous Materials-Requirements for Specific Materials > 502.9.8 Highly Toxic and Toxic Compressed Gases - Quantities Exceeding the Maximum Allowable Quantity Per Control Area > 502.9.8.4 Gas Rooms > 502.9.8.6 Process Equipment
502.8.2 Exhaust Systems, Gas Rooms, Exhausted Enclosures and Gas Cabinets
at a negative pressure
in relation to the surrounding area. Highly toxic and toxic
gases shall comply with Sections 502.9.7.1, 502.9.7.2 and
502.9.8.4 ...
2015 Michigan Mechanical Code > 5 Exhaust Systems > 502 Required Systems > 502.8 Hazardous Materials-General Requirements > 502.8.2 Gas Rooms, Exhausted Enclosures and Gas Cabinets