// CODE SNIPPET
[F] 502.9.7 Highly Toxic and Toxic Compressed Gases—Any Quantity
Go To Full Code Chapter
Ventilation exhaust shall be provided for highly toxic and toxic compressed gases in any quantity as required by Sections 502.9.7.1 and 502.9.7.2.
[F] 502.9.7.1 Gas Cabinets
Gas cabinets containing highly toxic or toxic compressed gases in any quantity shall comply with Section 502.8.2 and the following requirements:
- The average ventilation velocity at the face of gas cabinet access ports or windows shall be not less than 200 feet per minute (1.02 m/s) with a minimum velocity of 150 feet per minute (0.76 m/s) at any point at the access port or window.
- Gas cabinets shall be connected to an exhaust system.
- Gas cabinets shall not be used as the sole means of exhaust for any room or area.
[F] 502.9.7.2 Exhausted Enclosures
Exhausted enclosures containing highly toxic or toxic compressed gases in any quantity shall comply with Section 502.8.2 and the following requirements:
- The average ventilation velocity at the face of the enclosure shall be not less than 200 feet per minute (1.02 m/s) with a minimum velocity of 150 feet per minute (0.76 m/s).
- Exhausted enclosures shall be connected to an exhaust system.
- Exhausted enclosures shall not be used as the sole means of exhaust for any room or area.
Related Code Sections
502.9.7 Exhaust Systems, Highly Toxic and Toxic Compressed Gases—Any Quantity
Ventilation exhaust shall be provided for highly toxic and toxic compressed gases in any quantity as required by Sections 502.9.7.1 and 502.9.7.2 ...
502.9.7 Exhaust Systems, Highly Toxic and Toxic Compressed Gases—Any Quantity
Ventilation exhaust shall be provided for highly toxic and toxic compressed gases in any quantity as required by Sections 502.9.7.1 and 502.9.7.2 ...
502.9.7 Exhaust Systems, Highly Toxic and Toxic Compressed Gases— Any Quantity
Ventilation exhaust shall be provided for highly toxic and toxic compressed gases in any quantity as required by Sections 502.9.7.1 and 502.9.7.2 ...
502.9.7.1 Exhaust Systems, Gas Cabinets
Gas cabinets containing highly toxic or toxic compressed gases in any quantity shall comply with Section 502.8.2 and the following requirements ...
502.9 Exhaust Systems, Hazardous Materials—Requirements for Specific Materials
Ventilation exhaust shall be provided for highly toxic and toxic compressed gases in any quantity as required by Sections ...