Section 1408 High-Pressure Decorative Exterior-Grade Compact Laminates (HPL)

Go To Full Code Chapter
1408.1 General
The provisions of this section shall govern the materials, construction and quality of High-Pressure Decorative Exterior-Grade Compact Laminates (HPL) for use as exterior wall coverings in addition to other applicable requirements of Chapters 14 and 16.
1408.2 Exterior Wall Covering
HPL used as exterior wall covering or as elements of balconies and similar projections and bay and oriel windows to provide cladding or weather resistance shall comply with Sections 1408.4 through 1408.14.
1408.3 Architectural Trim and Embellishments
HPL used as architectural trim or embellishments shall comply with Sections 1408.7 through 1408.14.
[BS] 1408.4 Structural Design
HPL systems shall be designed and constructed to resist wind loads as required by Chapter 16 for components and cladding.
1408.5 Approval
Results of approved tests or an engineering analysis shall be submitted to the building official to verify compliance with the requirements of Chapter 16 for wind loads.
1408.6 Weather Resistance
HPL systems shall comply with Section 1402 and shall be designed and constructed to resist wind and rain in accordance with this section and the manufacturer's instructions.
1408.7 Durability
HPL systems shall be constructed of approved materials that maintain the performance characteristics required in Section 1408 for the duration of use.
1408.8 Fire-Resistance Rating
Where HPL systems are used on exterior walls required to have a fire-resistance rating in accordance with Section 705, evidence shall be submitted to the building official that the required fire-resistance rating is maintained.
Exception: HPL systems not containing foam plastic insulation, which are installed on the outer surface of a fire-resistance-rated exterior wall in a manner such that the attachments do not penetrate through the entire exterior wall assembly, shall not be required to comply with this section.
1408.9 Surface-Burning Characteristics
Unless otherwise specified, HPL shall have a flame spread index of 75 or less and a smoke-developed index of 450 or less when tested in the minimum and maximum thicknesses intended for use in accordance with ASTM E84 or UL 723.
1408.10 Types I, II, III and IV Construction
Where installed on buildings of Type I, II, III and IV construction, HPL systems shall comply with Sections 1408.10.1 through 1408.10.4, or Section 1408.11.
1408.10.1 Surface-Burning Characteristics
HPL shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450 when tested in the minimum and maximum thicknesses intended for use in accordance with ASTM E84 or UL 723.
1408.10.2 Thermal Barriers
HPL shall be separated from the interior of a building by an approved thermal barrier consisting of 1/2-inch (12.7 mm) gypsum wallboard or a material that is tested in accordance with and meets the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275.
1408.10.3 Thermal Barrier Not Required
The thermal barrier specified for HPL in Section 1408.10.2 is not required where:
  1. The HPL system is specifically approved based on tests conducted in accordance with NFPA 286, and with the acceptance criteria of Section 803.1.1.1, or with UL 1040 or UL 1715. Such testing shall be performed with the HPL in the minimum and maximum thicknesses intended for use. The HPL system shall include seams, joints and other typical details used in the installation and shall be tested in the manner intended for use.
  2. The HPL is used as elements of balconies and similar projections, architectural trim or embellishments.
1408.10.4 Full-Scale Tests
The HPL system shall be tested in accordance with, and comply with, the acceptance criteria of NFPA 285. Such testing shall be performed on the HPL system with the HPL in the minimum and maximum thicknesses intended for use.
1408.11 Alternate Conditions
HPL and HPL systems shall not be required to comply with Sections 1408.10.1 through 1408.10.4 provided that such systems comply with Section 1408.11.1.
1408.11.1 Installations Up to 40 Feet in Height
HPL shall be permitted to be installed up to 40 feet (12 190 mm) in height above grade plane where installed in accordance with Section 1408.11.1.1 or 1408.11.1.2.
1408.11.1.1 Fire Separation Distance of 5 Feet or Less
Where the fire separation distance is 5 feet (1524 mm) or less, the area of HPL shall not exceed 10 percent of the exterior wall surface.
1408.11.1.2 Fire Separation Distance Greater Than 5 Feet
Where the fire separation distance is greater than 5 feet (1524 mm), the area of exterior wall surface coverage using HPL shall not be limited.
1408.12 Type V Construction
HPL shall be permitted to be installed on buildings of Type V construction.
1408.13 Foam Plastic Insulation
HPL systems containing foam plastic insulation shall comply with the requirements of Section 2603.
1408.14 Labeling
HPL shall be labeled in accordance with Section 1703.5.

Related Code Sections

Section 1408 Exterior Walls, High-Pressure Decorative Exterior-Grade Compact Laminates (HPL)
The provisions of this section shall govern the materials, construction and quality of High-Pressure Decorative Exterior-Grade Compact Laminates (HPL ...
Section 1408 Exterior Walls, High-Pressure Decorative Exterior-Grade Compact Laminates (HPL)
The provisions of this section shall govern the materials, construction and quality of High-Pressure Decorative Exterior-Grade Compact Laminates (HPL ...
1408.1 Exterior Walls, General
The provisions of this section shall govern the materials, construction and quality of High-Pressure Decorative Exterior-Grade Compact Laminates (HPL ...
1408.8 Exterior Walls, Fire-Resistance Rating
Where HPL systems are used on exterior walls required to have a fire-resistance rating in accordance with Section 705, evidence shall be submitted ...
1408.8 Exterior Walls, Fire-Resistance Rating
Where HPL systems are used on exterior walls required to have a fire-resistance rating in accordance with Section 705, evidence shall be submitted ...