3206.3 High-Piled Storage Areas
Go To Full Code Chapter
For the application of Table 3206.2, the size of the high-piled storage areas shall be determined in accordance with Sections 3206.3.1 through 3206.3.2.1.
3206.3.1 Size of High-Piled Storage Area
The size of each high-piled storage area shall include the footprint of the actual high-piled storage racks, shelves or piles and the following aisles:
- Interior aisles within the footprint of the storage area.
- An aisle around the perimeter of the footprint with a minimum width as required in Section 3206.10.1 or the dimension to a full height wall, whichever is less.
3206.3.2 Multiple High-Piled Storage Areas
Where a building contains multiple high-piled storage areas, the aggregate of all high-piled storage areas shall be used for the application of Table 3206.2 unless the high-piled storage areas are separated in accordance with one of the following:
- High-piled storage areas separated by fire barriers with a minimum fire-resistance-rating of 1 hour constructed in accordance with Section 707 of the International Building Code.
- In buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, high-piled storage areas separated by 100 feet (30 480 mm) or more. The area providing the separation shall not contain high-piled combustible storage.
3206.3.2.1 Multiple Class High-Piled Storage Areas
High-piled storage areas classified as Class I through IV not separated from high-piled storage areas classified as high hazard shall utilize the aggregate of all high-piled storage areas as high hazard for the purposes of the application of Table 3206.2. Multiple class high-piled storage areas meeting the separation requirements in Section 3206.3.2 shall be considered as separated. The fire safety features in Table 3206.2 shall be extended beyond the higher-hazard storage area in accordance with Section 3206.2.1.
Exception: Multiple class high-piled storage areas do not need to be separated where in accordance with Section 3204.2.
Upcodes Diagrams
Related Code Sections
3206.3 High-Piled Combustible Storage, High-Piled Storage Areas
For the application of Table 3206.2, the size of the high-piled storage areas shall be determined in accordance with Sections 3206.3.1 through ...
3206.3 High-Piled Combustible Storage, High-Piled Storage Areas
For the application of Table 3206.2, the size of the high-piled storage areas shall be determined in accordance with Sections 3206.3.1 through ...
Section 3204 High-Piled Combustible Storage, Designation of High-Piled Storage Areas
High-piled storage areas, and portions of high-piled storage areas intended for storage of a different commodity class than adjacent areas, shall ...
Section 3204 High-Piled Combustible Storage, Designation of High-Piled Storage Areas
High-piled storage areas, and portions of high-piled storage areas intended for storage of a different commodity class than adjacent areas, shall ...
3206.3.2.1 High-Piled Combustible Storage, Multiple Class High-Piled Storage Areas
High-piled storage areas classified as Class I through IV not separated from high-piled storage areas classified as high hazard shall utilize ...