C406.7 High-Performance Dedicated Outdoor Air System (DOAS)
Go To Full Code Chapter
A whole building, building addition or tenant space which includes a DOAS complying with Section C406.6 shall also provide minimum sensible effectiveness of heat recovery of 80 percent and DOAS total combined fan power less than 0.5 W/cfm of outdoor air. For the purposes of this section, total combined fan power includes all supply, exhaust, recirculation and other fans utilized for the purpose of ventilation.
Related Code Sections
C406.7 [CE] Commercial Energy Efficiency, High-Performance Dedicated Outdoor Air System (DOAS)
effectiveness of heat recovery of 80 percent and DOAS total combined fan power less than 0.5 W/cfm of outdoor air. For the purposes of this section, total ...
C403.3.5 [CE] Commercial Energy Efficiency, Dedicated Outdoor Air Systems (DOAS)
For buildings with occupancies as shown in Table C403.3.5, outdoor air shall be provided to each occupied space by a dedicated outdoor air system ...
C406.6 [CE] Commercial Energy Efficiency, Dedicated Outdoor Air System (DOAS)
the International Mechanical Code, shall be served by DOAS installed in accordance with Section C403.6. This option is available to both buildings subject ...
C402.4.1.4 [CE] Commercial Energy Efficiency, Increased Vertical Fenestration Area With High-Performance Mechanical Systems
in Section C402.1.5, provided that the mechanical system complies with all requirements of Section C403.6, dedicated outdoor air systems (DOAS ...
CD602.11 Calculation of HVAC Total System Performance Ratio, HVAC Equipment
be simulated when outdoor air conditions allow free cooling. Economizer high limit shall be based on differential dry-bulb control. DOAS system continues ...