1810.3.1.5.1 Helical Piles Seismic Requirements
JUMP TO FULL CODE CHAPTER
[OSHPD 2] For structures assigned to Seismic Design Category D, E or F, capacities of helical piles shall be determined in accordance with Section 1810.3.3 by at least two project specific pre-production tests for each soil profile, size and depth of helical pile. At least two percent of all production piles shall be proof tested to design ultimate strength determined by using load combinations in Section 1605.2.1.
Helical piles shall satisfy corrosion resistance requirements of ICC-ES AC 358. In addition, all helical pile materials that are subject to corrosion shall include at least 1/16" corrosion allowance.
Helical piles shall not be considered as carrying any horizontal loads.
Related Code Sections
1810.3.1.5.1 Soils and Foundations, Helical Piles Seismic Requirements
[OSHPD 2] For structures assigned to Seismic Design Category D, E or F, capacities of helical piles shall be determined in accordance with Section ...
Los Angeles Building Code > 18 Soils and Foundations > 1810 Deep Foundations > 1810.3 Design and Detailing > 1810.3.1 Design Conditions > 1810.3.1.5 Helical Piles > 1810.3.1.5.1 Helical Piles Seismic Requirements
1810A.3.1.5.1 Soils and Foundations, Helical Piles Seismic Requirements
For structures assigned to Seismic Design Category D, E or F, capacities of helical piles shall be determined in accordance with Section 1810A.3.3 ...
Los Angeles Building Code > 18A Soils and Foundations > 1810A Deep Foundations > 1810A.3 Design and Detailing > 1810A.3.1 Design Conditions > 1810A.3.1.5 Helical Piles > 1810A.3.1.5.1 Helical Piles Seismic Requirements
1810.3.3.1.9 Soils and Foundations, Helical Piles
The allowable axial design load, P a , of helical piles shall be determined as follows: (Equation 18-4) where P u is the least value ...
Los Angeles Building Code > 18 Soils and Foundations > 1810 Deep Foundations > 1810.3 Design and Detailing > 1810.3.3 Determination of Allowable Loads > 1810.3.3.1 Allowable Axial Load > 1810.3.3.1.9 Helical Piles