The maximum height, in feet, of a building shall not exceed the limits specified in Table 504.3.
Exception: Towers, spires, steeples and other rooftop structures shall be constructed of materials consistent with the required type of construction of the building except where other construction is permitted by Section 1511.2.4. Such structures shall not be used for habitation or storage. The structures shall be unlimited in height where of noncombustible materials and shall not extend more than 20 feet (6096 mm) above the allowable building height where of combustible materials (see Chapter 15 for additional requirements).

ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANEa
OCCUPANCY CLASSIFICATION TYPE OF CONSTRUCTION
See
Footnotes
Type I Type II Type III Type IV Type V
A B A B A B A B C HT A B
A, B, E, F, M, S, U NSb UL 160 65 55 65 55 65 65 65 65 50 40
S UL 180 85 75 85 75 270 180 85 85 70 60
H-1, H-2, H-3, H-5 NSc, d UL 160 65 55 65 55 120 90 65 65 50 40
S
H-4 NSc, d UL 160 65 55 65 55 65 65 65 65 50 40
S UL 180 85 75 85 75 140 100 85 85 70 60
I-1 Condition 1, I-3 NSd, e UL 160 65 55 65 55 65 65 65 65 50 40
S UL 180 85 75 85 75 180 120 85 85 70 60
I-1 Condition 2, I-2 NSd, e, f UL 160 65 55 65 55 65 65 65 65 50 40
S UL 180 85
I-4 NSd, g UL 160 65 55 65 55 65 65 65 65 50 40
S UL 180 85 75 85 75 180 120 85 85 70 60
Rh NSd UL 160 65 55 65 55 65 65 65 65 50 40
S13D 60 60 60 60 60 60 60 60 60 60 50 40
S13R 60 60 60 60 60 60 60 60 60 60 60 60
S UL 180 85 75 85 75 270 180 85 85 70 60
For SI: 1 foot = 304.8 mm.
UL = Unlimited; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3.
  1. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
  2. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies.
  3. New Group H occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.5.
  4. The NS value is only for use in evaluation of existing building height in accordance with the International Existing Building Code.
  5. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies Condition 1, see Exception 1 of Section 903.2.6.
  6. New and existing Group I-2 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International Fire Code.
  7. For new Group I-4 occupancies, see Exceptions 2 and 3 of Section 903.2.6.
  8. New Group R occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.8.

Related Code Sections

504.3 General Building Heights and Areas, Height in Feet
The maximum height, in feet, of a building shall not exceed the limits specified in Table 504.3. Exception: Towers, spires, steeples ...
504.3 General Building Heights and Areas, Height in Feet
The maximum height, in feet, of a building shall not exceed the limits specified in Table 504.3. Exception: Towers, spires, steeples and other roof ...
2308.2.2 Wood, Allowable Floor-to-Floor Height
Maximum floor-to-floor height shall not exceed 11 feet, 7 inches (3531 mm). Exterior bearing wall and interior braced wall heights shall not exceed ...