• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

606.4 Heating, Ventilating and Air-Conditioning (HVAC) Piping Insulation

Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 606 Building Mechanical Systems > 606.4 Heating, Ventilating and Air-Conditioning (HVAC) Piping Insulation
JUMP TO FULL CODE CHAPTER
Piping with a nominal diameter greater than 1/4 inch (6.4 mm), including associated valves, fittings and piping system components, in heating, ventilating and air-conditioning (HVAC) systems shall be thermally insulated in accordance with Table 606.4. For insulation outside of the conductivity ranges specified in Table 606.4, the minimum thickness of the insulation shall be determined in accordance with Equation 6-4.
T = r [(1 + t/r)K/k - 1](Equation 6-4)
where:
T=minimum insulation thickness (inches).
r=actual outside radius of pipe (inches).
t = insulation thickness specified in Table 606.4 for applicable fluid temperature and pipe size.
K=Conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature (Btu × in/h × ft2 × °F).
k = the upper value of the conductivity range specified in Table 606.4 for the applicable fluid temperature.
Building cavities and interstitial framing spaces shall be large enough to accommodate the combined diameter of the pipe plus the insulation, plus the full thickness of the insulation plus any other objects in the cavity that the piping must cross.
Exception: Piping insulation is not required for the following:
  1. Factory-installed piping within HVAC equipment tested and rated in accordance with Section 606.2.
  2. Piping conveying fluids having a design operating temperature range between 60°F (15.6°C) and 105°F (40.6°C).
  3. Piping conveying fluids not heated or cooled such as roof and condensate drains, cold water supply, and natural gas piping.
  4. Where heat gain or heat loss will not increase energy usage such as liquid refrigerant piping.
  5. Piping having an outside diameter of 1 inch (25 mm) or less, associated with strainers, control valves, and balancing valves.
TABLE 606.4
MINIMUM PIPE INSULATION THICKNESS
FLUIDCONDUCTIVITY
Btu-in/(h
× ft2 × F)
RATIO OF WALL THICKNESS OF
PIPE INSULATION TO NOMINAL
PIPE DIAMETERa, b
Steam0.27 — 0.34≥ 2:1
Hot Water0.22 — 0.29≥ 1:1
Chilled Water0.22 — 0.28≥ 1:1
For SI: 1 inch = 25.4 mm, 1 Btu-in = W/m × K.
  1. The proportions apply to all nominal pipe diameters greater than 1/4 inch and less than or equal to 2 inches. For nominal pipe diameters larger than 2 inches, outside diameter, the minimum wall thickness of the insulation shall be equal to the wall thickness required for 2-inch pipe.
  2. These thicknesses are based on energy-efficiency considerations only.

Related Code Sections


606.4 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Heating, Ventilating and Air-Conditioning (HVAC) Piping Insulation
, ventilating and air-conditioning (HVAC) systems shall be thermally insulated in accordance with Table 606.4. For insulation outside of the conductivity ...
Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 606 Building Mechanical Systems > 606.4 Heating, Ventilating and Air-Conditioning (HVAC) Piping Insulation
1003.2.2 Existing Buildings, Heating, Ventilating and Air-Conditioning
Heating, ventilating and air-conditioning systems and equipment shall be in accordance with the following: Time clock and automatic time switch ...
Green Construction Code 2012 of Maryland > 10 Existing Buildings > 1003 Alterations to Existing Buildings > 1003.2 Requirements for Alterations > 1003.2.2 Heating, Ventilating and Air-Conditioning
513.4.4 Exhaust Systems, HVAC Systems
The design shall consider the effects of the heating, ventilating and air-conditioning (HVAC) systems on both smoke and fire transport. The analysis ...
Mechanical Code 2018 of Maryland > 5 Exhaust Systems > 513 Smoke Control Systems > 513.4 Analysis > 513.4.4 HVAC Systems
909.4.4 Fire Protection Systems, HVAC Systems
The design shall consider the effects of the heating, ventilating and air-conditioning (HVAC) systems on both smoke and fire transport. The analysis ...
Building Code 2015 of Maryland > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.4 Analysis > 909.4.4 HVAC Systems
909.4.4 Fire Protection and Life Safety Systems, HVAC Systems
The design shall consider the effects of the heating, ventilating and air-conditioning (HVAC) systems on both smoke and fire transport. The analysis ...
Building Code 2018 of Maryland > 9 Fire Protection and Life Safety Systems > 909 Smoke Control Systems > 909.4 Analysis > 909.4.4 HVAC Systems
Help Contact Us Privacy Terms
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING