// CODE SNIPPET
602.3 Heat Supply
Go To Full Code Chapter
Every owner and operator of any building who rents, leases or lets one or more dwelling units or sleeping units on terms, either expressed or implied, to furnish heat to the occupants thereof shall supply heat during the period from [DATE] to [DATE] to maintain a minimum temperature of 68°F (20°C) in all habitable rooms, bathrooms and toilet rooms.
Exceptions:
- When the outdoor temperature is below the winter outdoor design temperature for the locality, maintenance of the minimum room temperature shall not be required provided that the heating system is operating at its full design capacity. The winter outdoor design temperature for the locality shall be as indicated in Appendix D of the International Plumbing Code.
- In areas where the average monthly temperature is above 30°F (-1°C), a minimum temperature of 65°F (18°C) shall be maintained.
Related Code Sections
602.3 Mechanical and Electrical Requirements, Heat Supply
, to furnish heat to the occupants thereof shall supply heat during the period from [DATE] to [DATE] to maintain a minimum temperature of 68°F (20°C ...
602.3 Mechanical and Electrical Requirements, Heat Supply
, to furnish heat to the occupants thereof shall supply heat during the period from [DATE] to [DATE] to maintain a minimum temperature of 68°F (20°C ...
C404.5 [CE] Commercial Energy Efficiency, Heated Water Supply Piping
Heated water supply piping shall be in accordance with Section C404.5.1 or C404.5.2. The flow rate through 1/4-inch (6.4 mm) piping shall ...
665.12 Special Equipment, Disconnecting Means
A readily accessible disconnecting means shall be provided to disconnect each heating equipment from its supply circuit. The disconnecting means ...
410.104 Equipment for General Use, Electric-Discharge Lamp Auxiliary Equipment
Auxiliary equipment for electric-discharge lamps shall be enclosed in noncombustible cases and treated as sources of heat ...