1910.252(c) Health Protection and Ventilation
JUMP TO FULL CODE CHAPTER
Mechanical ventilation shall be provided when welding or cutting is done on metals not covered in paragraphs (c)(5) through(c)(12) of this section. (For specific materials, see the ventilation requirements of paragraphs (c)(5) through (c)(12) of this section.)
In a space of less than 10,000 cubic feet (284 m(3)) per welder.
In a room having a ceiling height of less than 16 feet (5 m).
In confined spaces or where the welding space contains partitions, balconies, or other structural barriers to the extent that they significantly obstruct cross ventilation.
Such ventilation shall be at the minimum rate of 2,000 cubic feet (57 m(3)) per minute per welder, except where local exhaust hoods and booths as per paragraph (c)(3) of this section, or airline respirators approved by the U.S. Bureau of Mines for such purposes are provided. Natural ventilation is considered sufficient for welding or cutting operations where the restrictions in paragraph (c)(2)(i) of this section are not present.
Mechanical local exhaust ventilation may be by means of either of the following:
Freely movable hoods intended to be placed by the welder as near as practicable to the work being welded and provided with a rate of air-flow sufficient to maintain a velocity in the direction of the hood of 100 linear feet (30 m) per minute in the zone of welding when the hood is at its most remote distance from the point of welding. The rates of ventilation required to accomplish this control velocity using a 3-inch (7.6 cm) wide flanged suction opening are shown in the following table:
Footnote(1) When brazing with cadmium bearing materials or when
cutting on such materials increased rates of ventilation may be
required.
Footnote(2) Nearest half-inch duct diameter based on 4,000 feet per minute velocity in pipe.
Welding zone | Minimum air flow 1 cubic feet/minute | Duct diameter, inches 2 |
---|---|---|
4 to 6 inches from arc or torch | 150 | 3 |
6 to 8 inches from arc or torch | 275 | 3 1/2 |
8 to 10 inches from arc or torch | 425 | 4 1/2 |
10 to 12 inches from arc or torch | 600 | 5 1/2 |
Footnote(2) Nearest half-inch duct diameter based on 4,000 feet per minute velocity in pipe.
A fixed enclosure with a top and not less than two sides which surround the welding or cutting operations and with a rate of airflow sufficient to maintain a velocity away from the welder of not less than 100 linear feet (30 m) per minute.
All welding and cutting operations carried on in confined spaces shall be adequately ventilated to prevent the accumulation of toxic materials or possible oxygen deficiency. This applies not only to the welder but also to helpers and other personnel in the immediate vicinity. All air replacing that withdrawn shall be clean and respirable.
In areas immediately hazardous to life, a full-facepiece, pressure-demand, self-contained breathing apparatus or a combination full-facepiece, pressure-demand supplied-air respirator with an auxiliary, self-contained air supply approved by NIOSH under 42 CFR part 84 must be used.
Where welding operations are carried on in confined spaces and where welders and helpers are provided with hose masks, hose masks with blowers or self-contained breathing equipment approved by the Mine Safety and Health Administration and the National Institute for Occupational Safety and Health, a worker shall be stationed on the outside of such confined spaces to insure the safety of those working within.
Oxygen shall never be used for ventilation.
In circumstances for which it is impossible to provide such ventilation, airline respirators or hose masks approved for this purpose by the National Institute for Occupational Safety and Health (NIOSH) under 42 CFR part 84 must be used.
In confined spaces, welding or cutting involving fluxes, coverings, or other materials which contain fluorine compounds shall be done in accordance with paragraph (c)(4) of this section. A fluorine compound is one that contains fluorine, as an element in chemical combination, not as a free gas.
The need for local exhaust ventilation or airline respirators for welding or cutting in other than confined spaces will depend upon the individual circumstances. However, experience has shown such protection to be desirable for fixed-location production welding and for all production welding on stainless steels. Where air samples taken at the welding location indicate that the fluorides liberated are below the maximum allowable concentration, such protection is not necessary.
In confined spaces welding or cutting involving zinc-bearing base or filler metals or metals coated with zinc-bearing materials shall be done in accordance with paragraph (c)(4) of this section.
Indoors, welding or cutting involving zinc-bearing base or filler metals coated with zinc-bearing materials shall be done in accordance with paragraph (c)(3) of this section.
In confined spaces, welding involving lead-base metals (erroneously called lead-burning) shall be done in accordance with paragraph (c)(4) of this section
In confined spaces or indoors, welding or cutting operations involving metals containing lead, other than as an impurity, or metals coated with lead-bearing materials, including paint, must be done using local exhaust ventilation or airline respirators. Such operations, when done outdoors, must be done using respirators approved for this purpose by NIOSH under 42 CFR part 84. In all cases, workers in the immediate vicinity of the cutting operation must be protected by local exhaust ventilation or airline respirators.
Indoors, welding involving lead-base metals shall be done in accordance with paragraph (c)(3) of this section.
Welding or cutting indoors, outdoors, or in confined spaces involving beryllium-containing base or filler metals shall be done using local exhaust ventilation and airline respirators unless atmospheric tests under the most adverse conditions have established that the workers' exposure is within the acceptable concentrations defined by 1910.1000 of this part. In all cases, workers in the immediate vicinity of the welding or cutting operations shall be protected as necessary by local exhaust ventilation or airline respirators.
In confined spaces or indoors, welding or cutting operations involving cadmium-bearing or cadmium-coated base metals must be done using local exhaust ventilation or airline respirators unless atmospheric tests under the most adverse conditions show that employee exposure is within the acceptable concentrations specified by 29 CFR 1910.1000. Such operations, when done outdoors, must be done using respirators, such as fume respirators, approved for this purpose by NIOSH under 42 CFR part 84.
Welding (brazing) involving cadmium-bearing filler metals shall be done using ventilation as prescribed in paragraph (c)(3) or (c)(4) of this section if the work is to be done in a confined space
In confined spaces or indoors, welding or cutting operations involving metals coated with mercury-bearing materials, including paint, must be done using local exhaust ventilation or airline respirators unless atmospheric tests under the most adverse conditions show that employee exposure is within the acceptable concentrations specified by 29 CFR 1910.1000. Such operations, when done outdoors, must be done using respirators approved for this purpose by NIOSH under 42 CFR part 84.
In the use of cleaning materials, because of their possible toxicity or flammability, appropriate precautions such as manufacturers instructions shall be followed.
Degreasing and other cleaning operations involving chlorinated hydrocarbons shall be so located that no vapors from these operations will reach or be drawn into the atmosphere surrounding any welding operation. In addition, trichloroethylene and perchlorethylene should be kept out of atmospheres penetrated by the ultraviolet radiation of gas-shielded welding operations.
Oxygen cutting, using either a chemical flux or iron powder or gas-shielded arc cutting of stainless steel, shall be done using mechanical ventilation adequate to remove the fumes generated.
First-aid equipment. First-aid equipment shall be available at all times. All injuries shall be reported as soon as possible for medical attention. First aid shall be rendered until medical attention can be provided.
Related Code Sections
1910.252(c) Welding, Cutting, and Brazing, Health Protection and Ventilation
CFR part 84. In all cases, workers in the immediate vicinity of the cutting operation must be protected by local exhaust ventilation or airline ...
OSHA 1910 General Industry > Q Welding, Cutting, and Brazing > 1910.252 General Requirements > 1910.252(c) Health Protection and Ventilation
1910.252(c)(7)(iii) Welding, Cutting, and Brazing, Local Ventilation
operation must be protected by local exhaust ventilation or airline respirators ...
OSHA 1910 General Industry > Q Welding, Cutting, and Brazing > 1910.252 General Requirements > 1910.252(c) Health Protection and Ventilation > 1910.252(c)(7) Lead > 1910.252(c)(7)(iii) Local Ventilation
1910.252(c)(10) Welding, Cutting, and Brazing, Mercury
using local exhaust ventilation or airline respirators unless atmospheric tests under the most adverse conditions show that employee exposure is within ...
OSHA 1910 General Industry > Q Welding, Cutting, and Brazing > 1910.252 General Requirements > 1910.252(c) Health Protection and Ventilation > 1910.252(c)(10) Mercury
1910.252(c)(11) Welding, Cutting, and Brazing, Cleaning Compounds
In the use of cleaning materials, because of their possible toxicity or flammability, appropriate precautions such as manufacturers instructions shall ...
OSHA 1910 General Industry > Q Welding, Cutting, and Brazing > 1910.252 General Requirements > 1910.252(c) Health Protection and Ventilation > 1910.252(c)(11) Cleaning Compounds
1910.252(c)(12) Welding, Cutting, and Brazing, Cutting of Stainless Steels
ventilation adequate to remove the fumes generated ...