A5.106.11.1 Hardscape Alternatives
JUMP TO FULL CODE CHAPTER
Use one or a combination of strategies 1 and 2 for 50 percent of site hardscape or put 50 percent of parking underground.
- Use light colored materials with an initial solar reflectance value of at least 30 as determined in accordance with American Society for Testing and Materials (ASTM) Standards E1918 or C1549.
- Use open-grid pavement system or pervious or permeable pavement system.
Related Code Sections
A5.106.11.1 Nonresidential Voluntary Measures, Hardscape Alternatives
Use one or a combination of strategies 1 and 2 for 50 percent of site hardscape or put 50 percent of parking underground. Use light colored ...
California Green Building Standards Code 2016 > A5 Nonresidential Voluntary Measures > A5.106 Site Development > A5.106.11 Heat Island Effect > A5.106.11.1 Hardscape Alternatives
A5.106.11.1 Nonresidential Voluntary Measures, Hardscape Alternatives
Use one or a combination of strategies 1 and 2 for 50 percent of site hardscape or put 50 percent of parking underground. Use light colored ...
California Green Building Standards Code 2019 > A5 Nonresidential Voluntary Measures > A5.106 Site Development > A5.106.11 Heat Island Effect > A5.106.11.1 Hardscape Alternatives
5.106.12.3 Nonresidential Mandatory Measures, Hardscape Areas
Shade tree plantings, minimum No. 10 container size or equal shall be installed to provide shade over 20 percent of the hardscape area within 15 ...
California Green Building Standards Code 2019 > 5 Nonresidential Mandatory Measures > 5.106 Site Development > 5.106.12 Shade Trees > 5.106.12.3 Hardscape Areas
A5.209.4.4.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], General Hardscape Lighting Allowance
Determine the general hardscape lighting power allowances as follows ...
California Green Building Standards Code 2016 > A6.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4] > A5.209 [OSHPD 1, 2 & 4] Lighting > A5.209.4 Outdoor Lighting > A5.209.4.4 Calculation of Allowed Lighting Power > A5.209.4.4.1 General Hardscape Lighting Allowance
A5.209.4.4.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], General Hardscape Lighting Allowance
Determine the general hardscape lighting power allowances as follows ...
California Green Building Standards Code 2019 > A6.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4] > A5.209 [OSHPD 1, 2 & 4] Lighting > A5.209.4 Outdoor Lighting > A5.209.4.4 Calculation of Allowed Lighting Power > A5.209.4.4.1 General Hardscape Lighting Allowance