1910.106(e)(2)(iv) Handling Liquids at Point of Final Use
JUMP TO FULL CODE CHAPTER
Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be kept in covered containers when not actually in use.
Where flammable liquids are used or handled, except in closed containers, means shall be provided to dispose promptly and safely of leakage or spills.
Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), may be used only where there are no open flames or other sources of ignition within the possible path of vapor travel.
flammable liquids shall be drawn from or transferred into vessels, containers, or portable tanks within a building only through a closed piping system, from safety cans, by means of a device drawing through the top, or from a container or portable tanks by gravity through an approved self-closing valve. Transferring by means of air pressure on the container or portable tanks shall be prohibited.
Related Code Sections
1910.106(e)(2)(iv) Hazardous Materials, Handling Liquids at Point of Final Use
not actually in use. Where flammable liquids ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(e) Industrial Plants > 1910.106(e)(2) Incidental Storage or Use of Flammable Liquids > 1910.106(e)(2)(iv) Handling Liquids at Point of Final Use
1910.110(b)(14) Hazardous Materials, Transfer of Liquids
attendant shall remain close to the transfer connection from the time the connections are first made until they are finally disconnected, during ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.110 Storage and Handling of Liquefied Petroleum Gases > 1910.110(b) Basic Rules > 1910.110(b)(14) Transfer of Liquids
1910.106(a)(19) Hazardous Materials, Flammable Liquid
flammable liquid is heated for use to within 30 °F (16.7 °C) of its flashpoint, it shall be handled in accordance with the requirements for a Category ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(a) Definitions > 1910.106(a)(19) Flammable Liquid
1910.263(d)(1)(i)(b) Special Industries,
Wherever a flour-handling system is of such size that the beginning of its operation is far remote from its final delivery end, all electric motors ...
OSHA 1910 General Industry > R Special Industries > 1910.263 Bakery Equipment > 1910.263(d) Flour-Handling Equipment > 1910.263(d)(1) General Requirements for Flour Handling > 1910.263(d)(1)(i) > 1910.263(d)(1)(i)(b)
1910.110(b)(13)(ii)(b)(5) Hazardous Materials,
The use of hose to carry liquid between the container and the building or at any point in the liquid line, except at the appliance connector, shall ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.110 Storage and Handling of Liquefied Petroleum Gases > 1910.110(b) Basic Rules > 1910.110(b)(13) LP-gas in Buildings > 1910.110(b)(13)(ii) > 1910.110(b)(13)(ii)(b) > 1910.110(b)(13)(ii)(b)(5)