110.27 Guarding of Live Parts
JUMP TO FULL CODE CHAPTER
Except as elsewhere required or permitted by this Code, live parts of electrical equipment operating at 50 to 1000 volts, nominal shall be guarded against accidental contact by approved enclosures or by any of the following means:
- By location in a room, vault, or similar enclosure that is accessible only to qualified persons.
- By permanent, substantial partitions or screens arranged so that only qualified persons have access to the space within reach of the live parts. Any openings in such partitions or screens shall be sized and located so that persons are not likely to come into accidental contact with the live parts or to bring conducting objects into contact with them.
- By location on a balcony, gallery, or platform elevated and arranged so as to exclude unqualified persons.
- By elevation above the floor or other working surface as follows:
- A minimum of 2.5 m (8 ft) for 50 volts to 300 volts between ungrounded conductors
- A minimum of 2.6 m (8 ft 6 in.) for 301 volts to 600 volts between ungrounded conductors
- A minimum of 2.62 m (8 ft 7 in.) for 601 volts to 1000 volts between ungrounded conductors
In locations where electrical equipment is likely to be exposed to physical damage, enclosures or guards shall be so arranged and of such strength as to prevent such damage.
Entrances to rooms and other guarded locations that contain exposed live parts shall be marked with conspicuous warning signs forbidding unqualified persons to enter. The marking shall meet the requirements in 110.21(B).
Related Code Sections
110.27 General, Guarding of Live Parts
Except as elsewhere required or permitted by this Code, live parts of electrical equipment operating at 50 to 1000 volts, nominal shall be guarded ...
National Electrical Code 2017 of Illinois > 1 General > 110 Requirements for Electrical Installations > 110.27 Guarding of Live Parts
110.27 General, Guarding of Live Parts
Except as elsewhere required or permitted by this Code, live parts of electrical equipment operating at 50 to 1000 volts, nominal shall be guarded ...
National Electrical Code 2020 of Illinois > 1 General > 110 Requirements for Electrical Installations > 110.27 Guarding of Live Parts
(B) Special Conditions, Guarding of Live Parts
Guarding of live parts shall comply with 110.27 ...
National Electrical Code 2017 of Illinois > 7 Special Conditions > 706 Energy Storage Systems > 706.10 Energy Storage System Locations > (B) Guarding of Live Parts
(C) General, Warning Signs
Entrances to rooms and other guarded locations that contain exposed live parts shall be marked with conspicuous warning signs forbidding unqualified ...
National Electrical Code 2020 of Illinois > 1 General > 110 Requirements for Electrical Installations > 110.27 Guarding of Live Parts > (C) Warning Signs
520.7 Special Occupancies, Enclosing and Guarding Live Parts
Live parts shall be enclosed or guarded to prevent accidental contact by persons and objects. All switches shall be of the externally operable type ...
National Electrical Code 2020 of Illinois > 5 Special Occupancies > 520 Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations > 520.7 Enclosing and Guarding Live Parts