The ampacity of conductors that supply two or more welders shall not be less than the sum of the value obtained in accordance with 630.31(A) for the largest welder supplied and 60 percent of the values obtained for all the other welders supplied.
Informational Note: Explanation of Terms
  1. The rated primary current is the rated kilovolt-amperes (kVA) multiplied by 1000 and divided by the rated primary voltage, using values given on the nameplate.
  2. The actual primary current is the current drawn from the supply circuit during each welder operation at the particular heat tap and control setting used.
  3. The duty cycle is the percentage of the time during which the welder is loaded. For instance, a spot welder supplied by a 60-Hz system (216,000 cycles per hour) and making 400 15-cycle welds per hour would have a duty cycle of 2.8 percent (400 multiplied by 15, divided by 216,000, multiplied by 100). A seam welder operating 2 cycles "on" and 2 cycles "off" would have a duty cycle of 50 percent.

Related Code Sections

(B) Special Equipment, Group of Welders
Minimum conductor ampacity shall be based on the individual currents determined in 630.11(A) as the sum of 100 percent of the two largest welders ...
(B) Special Equipment, Group of Welders
Minimum conductor ampacity shall be based on the individual currents determined in 630.11(A) as the sum of 100 percent of the two largest welders ...
(A) Special Equipment, Individual Welders
on the welder rating plate by the factor shown in Table 630.11(A) based on the duty cycle of the welder. Table 630.11(A) Duty Cycle Multiplication Factors ...
(A) Special Equipment, For Welders
Each welder shall have overcurrent protection rated or set at not more than 200 percent of I 1max. Alternatively, if the I 1max is not given ...
(A) Special Equipment, For Welders
Each welder shall have overcurrent protection rated or set at not more than 200 percent of I1max. Alternatively, if the I1max is not given ...