807.5.3 Groups I-1 and I-2
JUMP TO FULL CODE CHAPTER
In Group I-1 and I-2 occupancies, combustible decorative materials shall comply with Sections 807.5.3.1 through 807.5.3.4.
In Group I-1 and Group I-2 Condition 1 occupancies, equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, within sleeping units and dwelling units, combustible decorative materials placed on walls shall be limited to not more than 50 percent of the wall area to which they are attached.
In Group I-1 and Group I-2 Condition 1 occupancies, equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, combustible decorative materials placed on walls in areas other than within dwelling and sleeping units shall be limited to not more than 30 percent of the wall area to which they are attached.
In Group I-2 Condition 2 occupancies, equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, combustible decorative materials placed on walls shall be limited to not more than 30 percent of the wall area to which they are attached.
In Group I-1 and I-2 occupancies, in areas not equipped throughout with an approved automatic sprinkler system, combustible decorative materials shall be of such limited quantities that a hazard of fire development or spread is not present.
Related Code Sections
807.5.3 Interior Finish, Decorative Materials and Furnishings, Groups I-1 and I-2
In Group I-1 and I-2 occupancies, combustible decorative materials shall comply with Sections 807.5.3.1 through 807.5.3.4 ...
2020 Fire Code of NYS > 8 Interior Finish, Decorative Materials and Furnishings > 807 Decorative Materials Andartificial Decorative Vegetationin New and Existing Buildings > 807.5 Occupancy-Based Requirements > 807.5.3 Groups I-1 and I-2
807.5.3 Interior Finish, Decorative Materials and Furnishings, Groups I-1 and I-2
In Group I-1 and I-2 occupancies, combustible decorative materials shall comply with Sections 807.5.3.1 through 807.5.3.4 ...
Fire Code 2015 of New York State > 8 Interior Finish, Decorative Materials and Furnishings > 807 Decorative Materials Other Than Decorative Vegetation in New and Existing Buildings > 807.5 Occupancy-Based Requirements > 807.5.3 Groups I-1 and I-2
1010.1.9.6 Means of Egress, Controlled Egress Doors in Groups I-1 and I-2
in the means of egress in Group I-1 or I-2 occupancies where the clinical needs of persons receiving care require their containment. Controlled egress doors ...
Fire Code 2015 of New York State > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.9 Door Operations > 1010.1.9.6 Controlled Egress Doors in Groups I-1 and I-2
1010.1.9.6 Means of Egress, Controlled Egress Doors in Groups I-1 and I-2
in the means of egress in Group I-1 or I-2 occupancies where the clinical needs of persons receiving care require their containment. Controlled egress doors ...
Building Code 2015 of New York State > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.9 Door Operations > 1010.1.9.6 Controlled Egress Doors in Groups I-1 and I-2
1010.1.9.7 Means of Egress, Controlled Egress Doors in Groups I-1 and I-2
in the means of egress in Group I-1 or I-2 occupancies where the clinical needs of persons receiving care require their containment. Controlled egress doors ...
2020 Fire Code of NYS > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.9 Door Operations > 1010.1.9.7 Controlled Egress Doors in Groups I-1 and I-2