907.2.9.1 Group R-2 Student Apartments
JUMP TO FULL CODE CHAPTER
Where the main use or dominant occupancy of a building is classified as R-2 student apartments, as defined in Section 310.2, fire alarm systems shall be installed in accordance with Section 907.2.8. Where the main use or dominant occupancy of a building is not classified as R-2 student apartments and the building is occupied partially by Group R-2 student apartments, fire alarm systems shall be installed in accordance with Sections 907.2.9.1.1 through 907.2.9.2.
A manual fire alarm system shall be installed throughout all public corridors serving student apartments and student-related uses. Student-related uses shall include common spaces such as recreation rooms, lounges, dining rooms, laundry rooms and storage rooms.
Exceptions:
- A manual fire alarm system is not required in buildings not over two stories in height where all individual dwelling units and contiguous attic and crawl spaces are separated from each other and public or common areas by at least 1-hour fire partitions and each individual dwelling unit has an exit directly to a public way, exit court or yard.
- A manual fire alarm system is not required in buildings containing fewer than 15 student apartments
An automatic fire alarm system without alarm notification appliances shall be installed in accordance with this section in Group R-2 student apartments and student- related uses. The activation of any smoke detector required by this section shall initiate a signal at a central station or a constantly attended location. Smoke detectors shall be located as follows:
- In each mechanical equipment, electrical, transformer, telephone equipment or similar room, in elevator machine rooms, and in elevator lobbies.
- In air distribution systems in accordance with Section 606 of the New York City Mechanical Code.
- Throughout all public corridors serving student apartments and student-related uses. Student-related uses shall include common spaces such as recreation rooms, lounges, dining rooms, laundry rooms and storage rooms. However, smoke detectors shall not be required in such public corridors in buildings containing fewer than 15 student apartments.
Exception: An automatic fire alarm system is not required in buildings not over two stories in height where all individual dwelling units and contiguous attic and crawl spaces are separated from each other and public or common areas by at least 1-hour fire barriers and each individual dwelling unit has an exit directly to a public way, exit court or yard.
Related Code Sections
907.2.9.1 Fire Protection Systems, Group R-2 Student Apartments
and the building is occupied partially by Group R-2 student apartments, fire alarm systems shall be installed in accordance with Sections 907.2.9.1.1 ...
NYC Building Code 2008 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required > 907.2.9 Group R-2 > 907.2.9.1 Group R-2 Student Apartments
907.2.9.1 Fire Protection Systems, Group R-2 Student Apartments
and the building is occupied partially by Group R-2 student apartments, fire alarm systems shall be installed in accordance with Sections 907.2.9.1.1 ...
NYC Building Code 2014 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required > 907.2.9 Group R-2 > 907.2.9.1 Group R-2 Student Apartments
907.2.9 Fire Protection Systems, Group R-2
and the building is occupied partially by Group R-2 student apartments, fire alarm systems shall be installed in accordance with Sections 907.2.9.1.1 ...
NYC Building Code 2008 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required > 907.2.9 Group R-2
907.2.9 Fire Protection Systems, Group R-2
of a building is not classified as R-2 student apartments and the building is occupied partially by Group R-2 student apartments, fire alarm systems shall ...
NYC Building Code 2014 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required > 907.2.9 Group R-2
908.7.1 Fire Protection Systems, Group I-1 and R Occupancies
of a building is classified as Group R-2 student apartments. Carbon monoxide detectors and audible notification appliances shall be installed ...
NYC Building Code 2014 > 9 Fire Protection Systems > 908 Emergency Alarm Systems > 908.7 Carbon Monoxide Alarms and Detectors > 908.7.1 Group I-1 and R Occupancies